Spec Sheet

4 www.honeywellgenerators .com
60 kW
LIQUID-COOLED GENERATOR SETS
Interconnections
Single and three phase connections may vary, refer to the owner’s manual for specific connection information.
CONTROL FEATURES
• 2-Line Plain Text LCD Display Simple user interface for ease of operation.
• Mode Switch
-Auto Automatic Start on Utility failure. 7 day exerciser
-Off Stops unit. Power is removed. Control and charger
still operate.
-Manual/Test (start) Start with starter control, unit stays on. If utility
fails, transfer to load takes place.
• Programmable start delay between 10-30 seconds Standard
• Engine Start Sequence Cyclic cranking: 16 sec. on, 7 rest (90 sec.
maximum duration).
• Engine Warm-up 5 seconds
• Engine Cool-Down 1 minute
• Starter Lock-out Starter cannot re-engage until 5 sec. after engine
has stopped.
• Smart Battery Charger Standard
• Automatic Voltage Regulation with Over and Under
Voltage Protection
Standard
Automatic Low Oil Pressure Shutdown Standard
Overspeed Shutdown Standard
High Temperature Shutdown Standard
Overcrank Protection Standard
• Safety Fused Standard
Failure to Transfer Protection Standard
Low Battery Protection Standard
50 Event Run Log Standard
Future Set Capable Exerciser Standard
Incorrect Wiring Protection Standard
Internal Fault Protection Standard
Common External Fault Capability Standard
Governor Failure Protection Standard
NEUTRAL BLOCK
GROUND
0 GROUND
15B +12V
23 TRANSFER
AIR 1
AIR 2
PRIORITY 1
PRIORITY 2
PRIORITY 3
PRIORITY 4
T1
NEUTRAL
CONTACTOR
1
CONTACTOR
2
CONTACTOR
3
CONTACTOR
4
NOTE WIRE ORIENTATION
WARNING
TRANSFER
DC COMMON
CUSTOMER CONNECTIONS
23
0
194
+12VDC
GROUND
NEUTRAL BLOCK
LOAD SHED
MODULE
194
23
0
N1
N2
E1 E2
NOTE:
MATCH WIRE
TERMINAL NUMBERS
NUMBERS TO
N1
N2
T1/LINE
NEU
178
183
23
194
T1
CUSTOMER SUPPLIED
NEUTRAL WIRE
NEUT
NOTE: INSTALLATION TO BE DONE BY A
LICENSED ELECTRICIAN AND MUST
MEET ALL NATIONAL, STATE AND
LOCAL ELECTRICAL CODES.
(C2 & VR2)
(C1 & VR1)
STANDBY
UTILITY
N1 N2
E2E1
T1 T2
0
194
23
N2
N1
T1
E1
E2
T2
N1
N2
T1
ON
SERVICE DISCONNECT
UTILITY SUPPLY FROM
CUSTOMER LOAD
(DISTRIBUTION PANEL)
QT SERIES ENGINE GENERATOR
CONNECTION PANEL
LIQUID COOLED INSTALLATION
RTS TRANSFER SWITCH
GROUP
EXPLODED VIEW:
DRAWING #:
PAGE 1 OF 2
DATE:
REVISION:
RTS SINGLE PHASE INTERCONNECTION
0H7452
G
11/2/12
J-3216-D
48850-T
0C4449A-T
HT