Spec Sheet

2 www.honeywellgenerators .com
60 kW
LIQUID-COOLED GENERATOR SET
Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with
BS5514, ISO3046 and DIN6271). (All ratings in accordance with BS5514, ISO3046, ISO8528, SAE J1349 and DIN6271).
Application &
Engineering Data
GENERATOR FEATURES
• Revolving field heavy duty generator
• Directly connected to the engine
• Operating temperature rise 120 °C above a 40 °C ambient
• Insulation is Class H rated at 150 °C rise
• All models are fully prototyped tested
GENERATOR SPECIFICATIONS
• Type
• Rotor Insulation
• Stator Insulation
• Telephone Interference Factor (TIF)
• Alternator Output Leads Phase 3
• Bearings
• Coupling
• Load Capacity (Standby Rating)
• Excitation System
Synchronous
Class H
Class H
<50
4 wire
Sealed Ball
Flexible Disc
60 kW
Direct
ENGINE SPECIFICATIONS
• Make
• Model
• Cylinders
• Displacement
• Bore
• Stroke
• Compression Ratio
• Intake Air System
• Lifter Type
Generac
In Line
4
2.4 Liter
3.41
3.94
8.5:1
Turbcharged/Aftercooled
Hydraulic
GOVERNOR SPECIFICATIONS
• Type
• Frequency Regulation
• Steady State Regulation
Electronic
Isochronous
± 0.25%
VOLTAGE REGULATION
• Type
• Sensing
• Regulation
Electronic
Single Phase
± 1%
ENGINE LUBRICATION SYSTEM
• Oil Pump
• Oil Filter
• Crankcase
Gear
Full flow spin-on
cartridge
4 Quarts
ENGINE COOLING SYSTEM
• Type
• Water Pump
• Fan Speed
• Fan Diameter
• Fan Mode
Pressurized Closed
Belt driven
2100
22 inches
Puller
FUEL SYSTEM
• Fuel Type
• Carburetor
• Secondary Fuel Regulator
• Fuel Shut Off Solenoid
• Operating Fuel Pressure
Natural gas, propane
vapor
Down Draft
Standard
Standard
5” - 14” H
2
O
ELECTRICAL SYSTEM
• Battery Charge Alternator
• Static Battery Charger
• Recommended Battery
• System Voltage
12V 30 Amp
2 Amp
Group 26, 525CCA
12 Volts
ENCLOSURE FEATURES
Aluminum all weather protective enclosure – Ensures protection
against mother nature. Electrostatically applied textured epoxy paint
for added durability.
Enclosed critical grade muffler – Quiet, critical grade muffler is
mounted inside the unit.
Small, compact, attractive – Makes for easy installation of an eye
appealing unit.
• SAE – Sound attenuated eclosure ensures quiet operation.