Datasheet

HIH-4000 Series
2 www.honeywell.com/sensing
TABLE 1. PERFORMANCE SPECIFICATIONS (At 5 Vdc supply and 25 ºC [77 ºF] unless otherwise noted.)
Parameter Minimum Typical Maximum Unit Specific Note
Interchangeability (first order curve)
0% RH to 59% RH -5
5 % RH
60% RH to 100% RH -8
8 % RH
Accuracy (best fit straight line)
-3.5 +3.5
% RH 1
Hysterisis
3
% RH
Repeatability
±0.5
% RH
Settling time
70 ms
Response time (1/e in slow moving air)
15
s
Stability (at 50% RH)
1.2
% RH
Voltage supply 4
5.8 Vdc
2
Current supply
200
500 μA
Voltage output (1
st
order curve fit) V
OUT
=(V
SUPPLY
)(0.0062(sensor RH) + 0.16), typical at 25 ºC
Temperature compensation True RH = (Sensor RH)/(1.0546 – 0.00216T), T in ºC
Output voltage temperature, coefficient at
50% RH, 5 V
-4
mV/ºC
Operating temperature -40[-40] See Figure 1. 85[185] ºC[ºF]
Operating humidity 0 See Figure 1. 100 % RH
3
Storage temperature -50[-58]
125[257] ºC[ºF]
Storage humidity See Figure 2. % RH
3
Specific Notes:
1. Can only be achieved with the supplied slope and offset.
For HIH-4000-003 and HIH-4000-004 catalog listings only.
2. Device is calibrated at 5 Vdc and 25 ºC.
3. Non-condensing environment.
General Notes:
Sensor is ratiometric to supply voltage.
Extended exposure to >
90% RH causes a reversible shift
of 3% RH.
Sensor is light sensitive. For best performance, shield
sensor from bright light.
FACTORY CALIBRATION DATA
HIH-4000 Sensors may be ordered with a calibration and data
printout. See Table 2 and the order guide on the back page.
TABLE 2. EXAMPLE DATA PRINTOUT
Model HIH-4000-003
Channel 92
Wafer 030996M
MRP 337313
Calculated values at 5 V
V
OUT
at 0% RH
V
OUT
at 75.3% RH
0.826 V
3.198 V
Linear output for 3.5% RH
accuracy at 25 °C
Zero offset
Slope
RH
0.826 V
31.483 mV/%RH
(V
OUT
- zero offset)/slope
(V
OUT
- 0.826)/0.0315
Ratiometric response for
0% RH to 100% RH
V
OUT
V
SUPPLY
(0.1652 to 0.7952)