User Manual

HIH-4000 Series
Issue 3 50009357
2 Honeywell Sensing and Control
TABLE 2. PERFORMANCE SPECIFICATIONS (At 5 Vdc supply and 25 ºC [77 ºF] unless otherwise noted.)
Parameter Minimum Typical Maximum Unit Specific
Note
Interchangeability (first order curve)
0% RH to 59% RH -5 5 % RH
60% RH to 100% RH -8 8 % RH
Accuracy (best fit straight line) -3.5 +3.5 % RH 1
Hysterisis – 3 % RH
Repeatability – ±0.5 % RH
Settling time 70 ms
Response time (1/e in slow moving air) 15 s
Stability (at 50% RH) 1.2 % RH
Voltage supply 4 5.8 Vdc 2
Current supply 200 500 µA
Voltage output (1
st
order curve fit) V
OUT
=(V
SUPPLY
)(0.0062(sensor RH) + 0.16), typical at 25 ºC
Temperature compensation True RH = (Sensor RH)/(1.0546 – 0.00216T), T in ºC
Output voltage temperature coefficient at
50% RH, 5V
– -4 mV/ºC
Operating temperature -40[-40] See Figure 1. 85[185] ºC[ºF] –
Operating humidity 0 See Figure 1. 100 % RH 3
Storage temperature -50[-58] 125[257] ºC[ºF] –
Storage humidity See Figure 2. % RH 3
Specific Notes:
1. Can only be achieved with the supplied slope and offset.
For HIH-4000-003 and HIH-400-004 catalog listings only.
2. Device is calibrated at 5 Vdc and 25 ºC.
3. Non-condensing environment.
General Notes:
Sensor is ratiometric to supply voltage.
Extended exposure to >
90% RH causes a reversible shift of
3% RH.
Sensor is light sensitive. For best performance, shield sensor
from bright light.
FIGURE 1. OPERATING ENVIRONMENT (Non-condensing environment.)