Install Instructions

APPENDICES
2 IN. PER FT
2 IN. PER FT
2 IN. PER FT
2 IN. PER FT
20 FT MAX
P - TRAP
DRAIN
WITH TRAP
5 FT MAX
3 FT max.
DRAIN
P - TRAP
IF NO SLOPE
10 FT MAX
GENTLE BEND
OBSTRUCTION
SUPPORTED REMOTE HOSE
20 FT MAX
DRAIN
P - TRAP
NOTE: HEIGHT OF TRAP MUST BE GREATER
THAN THE DUCT STATIC PRESSURE
DRAIN
P - TRAP
IF NO SLOPE
TYPICAL INSTALLATION
WHEN Tr ueSTEAM IS ABOVE
REMOTE NOZZLE
KINKED
SAG
NO SLOPE
NO SLOPE
M24915
M24915
UNDRAINED
ELBOW
NOTES:
Slope hose up in direction of steam flow at 2 in. per foot;
Slope hose down in direction of steam flow at 3/4 in. per foot;
Maximum length of remote steam hose is 20 ft.
Height of P-traps must be greater than the duct static pressure. (Typical 3 in.
will suffice.)
Minimize sharp bends and elbows.
Insulating the remote hose in unconditioned spaces will sustain efficiency better
than not insulating the hose.
TrueSTEAM Humidication System 69-2285—05
22