Install Instructions

OPERATION
AND SERVICE
TrueSTEAM Humidication System 69-2285—05 51
No. of
Service LED
Blinks
Fault Description Auto-Recoverable? Steps to Fix
(Performed Only By Professional HVAC Technician)
1 Water Heater
temperature sensor is
out of range.
Yes, TrueSTEAM
will reset if fault no
longer exists in one
hour.
1. Unplug TrueSTEAM & remove cover
2. Check Water sensor connection to board. Remove and plug
back in.
3. Press the Go button.
4. If fault returns, replace TrueSTEAM
2 Water sensors failed. Yes, TrueSTEAM
will reset if fault no
longer exists in one
hour.
1. Unplug TrueSTEAM and remove cover.
2. Disconnect water level sensor wiring.
3. Ohm out water sensor
4. Readings between P1 & P3, P1 & P4, P2 & P4 and P4 & P5
should all show innite resistance. If they do not replace the
sensor.
3 Failure to ll tank
with water.
Yes, system will
return to “Ready”
if fault no longer
exists in
three hours.
1. Ensure inlet water is on.
2. Check for voltage on the ll terminals for the solenoid valve
(should be appox. 120vac)
3. Check for leaks around the tank seal and solenoid.
4. If using an RO lter make sure the ush timer is set for 30
hours
5. If using an RO lter, follow troubleshooting information as
outlined in RO install guide.
6. If not using an RO lter, turn off water supply and replace any
in line water lter.
7. Press and hold the go button until res Service light turns off.
8. If tank still fails to ll, press the Drain button.
9. If tank fails to drain, unplug TrueSTEAM (and make sure water
in tank is cool before proceeding).
10. Follow the tank cleaning steps.
11. Ensure you have a rm grip on the tank before releasing the
tank, especially if water is present.
12. Clear any excess debris from the tank’s bottom orice to the
solenoid.
13. Reassemble tank and plug TrueSTEAM back in. Press the
button to reset. If water still fails to ll into the tank, replace the
solenoid valve
Troubleshooting
TrueSTEAM has internal system diagnostics that monitor operation, maintenance schedules, and faults. If a
system fault is detected, TrueSTEAM will attempt to recover up to ve times in a 24-hour period.
If TrueSTEAM is unable to recover by itself within 24 hours, the red Service light blinks in a series that
indicates the fault detected.
Refer to the table below for the fault indicated, along with the steps to x TrueSTEAM.
Press and hold the Go button until the Service light turns off.