Install Instructions

APPENDICES
OPTION 14: TrueSTEAM humidier wired to equipment with powered terminals with TrueSTEAM
controlling the fan
1
3
FURNACE TERMINALS
HUM
W2
Y1 DHUM GCOM W/W1
AIR-FLOW
SWITCH
Y/Y2
R
TrueSTEAM
24 V
24 V
HUM
HUM
C
GT
R
RT
GF
EXT
YOU MUST ADD A 24VAC ISOLATION RELAY BETWEEN THE TRUESTEAM HUMIDIFIER AND
THE AIR HANDLER. AN R8222B1067 COULD BE USED.
THE 50027910-001 AIR-FLOW SWITCH (AFS) IS RECOMMENDED TO ENSURE THERE IS
AIR-FLOW WHEN THE HUMIDIFIER IS RUNNING. IF THE AFS IS NOT USED, THE 4
DIPSWITCH MUST BE SET TO THE ON POSITION AT THE HUMIDIFIER (UP).
INFINITY/EVOLUTION CONFIGURATION
1. IN SETUP UNDER THE INSTALL/SERVICE MENU:
A. SELECT ACCESSORIES AND CHOOSE YES FOR HUMIDIFIER AND SET THE OPTION
HUMIDIFY WITH FAN TO YES.
B. SELECT FURNACE SETUP. UNDER THE G TERMINAL SET UP, SELECT THE FAN
OPTION AND SET THE FAN SPEED TO LOW.
1
2
3
1
2
3
NOTES:
A 24VAC ISOLATION RELAY MUST BE USED BETWEEN THE FURNACE AND THE HUMIDIFIER TO
ISOLATE THE TWO TRANSFORMERS. EQUIPMENT DAMAGE WILL OCCUR IF NOT USED.
THE HUMIDIFY WITH FAN OPTION MUST BE SELECTED. THIS WILL ALLOW THE SYSTEM TO
CALL FOR HUMIDIFICATION WITHOUT A HEAT CALL.
THE G TERMINAL MUST BE SET TO FAN. THIS WILL ALLOW THE HUMIDIFIER TO CONTINUE TO
RUN THE FAN AFTER THE HUMIDIFICATION CALL IS SATISFIED. THE TRUESTEAM HUMIDIFIER
REQUIRES THE FAN TO CONTINUE TO RUN UNTIL THE WATER TEMPERATURE IN THE RESERVOIR
IS COOLED TO 170 DEG TO PREVENT STEAM FROM CONDENSING IN THE DUCTWORK.
THE INFINITY SYSTEM WILL RUN ITS FAN AT LOW SPEED WHEN IT HAS A CALL FOR
HUMIDIFICATION WITHOUT A HEATING CALL. THIS AIRFLOW IS 50% OF HEATING OR COOLING
AIRFLOW (WHICHEVER IS GREATER). MAKE SURE AIRFLOW SATISFIES ANY MINIMUM
REQUIREMENT FOR YOUR TRUESTEAM HUMIDIFIER.
FURNACE SET UP IS SHOWN. FAN COIL SET UP WILL BE SIMILAR.
M33044
6
543
2
On
Off
1
AFS Monitor Recommended
TrueSTEAM Humidication System 69-2285—05
66
B: Advanced TrueSTEAM Wiring