TrueSTEAM Humidification System
9 69-2036EFS—07
2 IN. PER FT
2 IN. PER FT
2 IN. PER FT
2 IN. PER FT
20 FT MAX
P - TRAP
DRAIN
WITH TRAP
5 FT MAX
3 FT MAXIMUM
DRAIN
P - TRAP
IF NO SLOPE
10 FT MAX
GENTLE BEND
OBSTRUCTION
SUPPORTED REMOTE HOSE
20 FT MAX
DRAIN
WETTED P - TRAP
NOTE: HEIGHT OF TRAP MUST BE GREATER
THAN THE DUCT STATIC PRESSURE
DRAIN
P - TRAP
IF NO SLOPE
TYPICAL INSTALLATION
WHEN TrueSTEAM IS ABOVE
REMOTE NOZZLE
KINKED
SAG
NO SLOPE
NO SLOPE
M24915A
UNDRAINED
ELBOW
NOTES:
Slope hose up in direction of steam flow at 2 in. per foot;
Slope hose down in direction of steam flow at 3/4 in. per foot;
Maximum length of remote steam hose is 20 ft.
Height of P-traps must be greater than the duct static pressure. (Typical
3 in. will suffice.) P-trap must also be wetted (see page 7).
Minimize sharp bends and elbows.
Insulating the remote hose in unconditioned spaces will sustain
efficiency better than not insulating the hose.
PRoPeR hose InsTalls
AVOID THESE INSTALLATION MISTAKES.