IMPORTANT Read and save these instructions. This guide should be kept by the installer. HM750A1000 ADVANCED ELECTRODE STEAM HUMIDIFIER INSTALLATION INSTRUCTIONS Tools Needed — — — — — — Flat-head screwdriver Phillips screwdriver Wrench Copper pipe (optional) Level Hole saw Humidifier Configuration The HM750 is configured at the factory to operate under most conditions without the need to change its configuration.
HM750A1000 Table 1. Specifications. Volts Steam Output GPD KW 110/120 11 1.5 220/240 22 3.0 Max Ext. Fuse Amps Phase (Amps) 12 1 15 Standard Cylinder HM750ACYL Net/Full Weight lbs. (kg) Dimensions WxHxD 10.5 / 18.5 (4.8 / 8.4) 10 x 18 x 7 in. 254 x 457 x 178 mm CAUTION Electrical S/N DATECODE 110-120 12 220-240 12 S/N 22 1.5 3.0 AMP KW S/N 110-120 12 11 1.5 Country Pays of origin: d’origine Canada : Canada 220-240 12 22 3.
HM750A1000 Parts and Accessories The following parts and accessories are available and may have been included with your HM750 humidifier. The cylinder is the only item that will need periodic replacement to maintain proper humidifier operation. Table 2. Parts and accessories. Part/Accessory Part Number Replacement Cylinder HM750ACYL HumidiPRO Humidistat H6062A1000 Drain and Fill Valve Kit HM750AVKIT Remote and Duct Nozzle Kit HM750ANKIT Replacement PC Board HM750APCB 15 ft.
HM750A1000 SIZING IMPORTANT The HM750 should only be installed if it has been sized properly. Do not use square feet when sizing a humidifier installation. Instead, cubic feet must be used, since the humidity is filling a volume of space (width x length x height). Also, take into consideration the “tightness” of a home’s construction. The HM750 produces 11 gallons per day (GPD) when run on 120 V and 22 GPD when run on 240 V. See Figure 20 for details on configuring the HM750 to run on a different voltage.
HM750A1000 MOUNTING 12 (305) 4 (102) STEAM DISTRIBUTION 4 (102) 1 (25) 2 (51) SCREWS 1 (25) 36 (914) MINIMUM 1 (25) IF WIRED BEFORE MOUNTING. 36 INCHES (914) FOR WIRING ACCESSIBILITY 4 (102) Air Proving AP AP AIR PROVING (OR JUMPER) 1 1 AIR PROVING JUMPER COMES PRE-INSTALLED. REMOVE JUMPER IF AIR PROVING IS UTILIZED.
HM750A1000 LOCATION Steam Nozzle Location Mount on a suitable wall or vertical surface. Do not sit the unit on the floor. Allow clearances required for plumbing and electrical connections. Clearance dimensions shown are for reference only and are the minimum required for maintenance of the humidifier. Whether the humidifier is being installed directly on the air duct or remotely, the location of the distributor nozzle in the air duct should follow the subsequent rules: 1 4.
HM750A1000 Steam Line Instructions The following instructions must be followed for installation of steam lines for the HM750. Failure to use recommended material (see Table 5), or failure to follow any other steam line installation instructions will result in improper operation and could void the warranty. Table 5. Recommended Steam Line Material for HM750 Duct. Steam Output Material* Voltage 110/120V 220/240V lbs/hr (kg/hr) GPD 3.8 (1.7) 11 7.7 (3.5) 22 Steam Hose Steam Line Length 1 in. dia.
HM750A1000 Steam Line Installation Examples 12 (305) 4 (102) MINIMUM 12 (305) MINIMUM RADIUS 12 (305) MINIMUM RADIUS SUPPORT BRACKETS SUPPORT 1 BRACKETS CONNECT STEAM HOSE TO CYLINDER OBSTRUCTION HM750 Status Idle Filling Humidifying Draining Service Cylinder Fault Power Drain Fault Codes In Front Cover HM750 Status Idle Filling 12 (305) MINIMUM Humidifying Draining Service Cylinder Fault Power 12 (305) MINIMUM 4 (102) MINIMUM Drain Fault Codes In Front Cover TO DRAIN USE FULL SIZE CONDENS
HM750A1000 MOUNTING THE HUMIDIFIER The HM750 can be mounted either directly on a supply air duct or remotely mounted on a wall. When remotely mounted the steam nozzle is mounted on a duct and connected to the HM750 with a steam hose. The HM750 has a keyhole and three additional mounting holes as shown in Fig. 12. DUCT MOUNT 3. Drill a 1-3/4” hole in the duct for the steam distributor nozzle. Attach the steam hose to the distributor nozzle and the remote adapter on the humidifier.
HM750A1000 Mounting to the Supply Duct The HM750 can also be mounted directly onto the supply duct. In this case, the steam guide must be removed and replaced with the steam nozzle and baffle as follows: REMOVE THE STEAM GUIDE CAUTION Do not remove the cover when the humidifier powered. 1. 2. 3. 4. Remove the humidifier front cover. Remove the cylinder plugs and high water sensor plug from the cylinder pins by pulling vertically.
HM750A1000 PLUMBING 3/4 (19) OD 1/4 LDPE OR COPPER WATER LINE ALWAYS INSTALL A WATER SHUT-OFF VALVE. USE 1/2 IN. OD COPPER TO WITHIN 4 FT (1.2 M) OF HUMIDIFIER. M37187 Fig. 18. Water supply and drain connection. IMPORTANT — Use potable water. — All water supply and drain line connections should be installed in accordance with local plumbing codes. — Drain water is automatically cooled to 160 °F (71 °C) when HM750 cycles a drain. When an emergency drain occurs, temperature may be higher.
HM750A1000 ELECTRICAL WARNING To comply with UL product listing, the HM750 must be hardwired to a dedicated 15 amp circuit. All wiring must be done per governing electrical codes. Failure to do so will void the product warranty. The use of electric cord plugs can cause overheating and result in risk of damage to property and/or personal injury. CAUTION Wiring to be performed by a licensed electrician. Installation on a GFCI circuit is recommended. Do not remove the cover when the humidifier powered.
HM750A1000 Low-voltage Controls Requirements Humidistat or Thermostat Connection Connect a humidistat or thermostat to the HUM terminals of the humidifier. The humidifier provides a 24-VAC source to power the humidistat or thermostat if needed (5 VA max.). • 18 AWG solid wire or greater. • Low voltage wiring must be routed through the hole that is to the left of the high voltage strain relief. • Keep control wires as short as possible.
HM750A1000 H6062 HUMIDIPRO R C Air Proving U THERMOSTAT R Rc W Y G AP AP AIR PROVING OR JUMPER U Humidistat S 24VAC COM HUM HUM S OUTDOOR SENSOR External GT RF GF HM750 R C W Y G HVAC M37760 Fig. 24. Wiring the steam humidifier with a mechanical thermostat. NOTE: If a Prestige, VisionPRO, Round Smart (or similar) is used to control humidity, wire the two U contacts from thermostat to HUM and HUM on the HM750.
HM750A1000 START UP Installation Check 5. Before turning on power to the HM750, inspect the installation to ensure that it was carried out correctly, as per these installation instructions. 6. On/Off The HM750 is factory-configured to operate as an On/Off humidifier. It will run when 24 VAC from one HUM terminal is fed back into the other HUM terminal through an On/Off humidistat. 7. WARNING Personal Injury Hazard. Damaged or improperly installed units must not be operated.
HM750A1000 OPERATION LED Status Lights The HM750 user interface includes a series of LEDs that provide information about the humidifier status. LED will flash on and off, during which time the humidifier will continue to operate as normal. After 7 days of flashing, the LED will remain on solid, and the humidifier will not generate steam. The cylinder must be replaced. See “Cylinder Replacement Kit” on page 19.
HM750A1000 STEAM OUTLET FILL CUP HIGH WATER SENSOR CYLINDER PLUGS STEAM CYLINDER HM750 Status USER INTERFACE Idle Filling Humidifying Draining Service Cylinder POWER/DRAIN BUTTON Fault Power Drain Fault Codes In Front Cover FILL VALVE DRAIN VALVE QUICK CONNECTOR DRAIN OUTLET M37211 Fig. 26. Humidifier components. Component Function Cylinder plugs Power connectors to electrodes in cylinder. Drain outlet Connection to drain hose, used to remove water from the humidifier.
HM750A1000 MAINTENANCE AND SERVICING Required Maintenance HOSE CONNECTIONS Inspect annually, clean as necessary. The HM750 humidifier has been designed to require minimal maintenance. Regular maintenance consists of checking the humidifier to ensure it is in good condition, replacing the cylinder when the software advises that the cylinder is spent and cleaning out the drain valve whenever the cylinder is replaced. CYLINDER The cylinder LED will indicate when to replace the device cylinder (see page 16).
HM750A1000 REPLACEMENT PARTS CYLINDER REPLACEMENT KIT CAUTION Before Servicing 1. Disconnect main power source before accessing internal compartments. 2. The plumbing and electrical compartments contain high voltage components and wiring. Access should be limited to licensed HVAC professionals only. 3.
HM750A1000 Removing the Cylinder 5. 6. 7. WARNING Disconnect main power source before accessing internal compartments. The inside of the humidifier cabinet contains high voltage components and wiring. Access should be limited to authorized personnel. 1. 2. 3. 4. 8. 9. Drain the existing cylinder by pressing the Power/Drain button on the front of the humidifier for 1 second. Let the humidifier drain until no more water is flowing out to drain (usually not more than 10 minutes).
HM750A1000 Drain Valve Removal (for cleaning or replacement) Always clean the drain valve before installing a new cylinder. Scale from the spent cylinder may have fallen into the drain valve and could prevent its proper operation. To properly clean the drain valve it must be removed and disassembled. WARNING Disconnect main power source before accessing internal compartments. The inside of the humidifier cabinet contains high voltage components and wiring.
HM750A1000 Inlet Valve Strainer Cleaning Opening Electrical Compartment Depending on the water quality, periodic cleaning of the fill valve strainer may be required. This can be performed without removing the valve from humidifier. WARNING Disconnect main power source before accessing internal compartments. The inside of the humidifier cabinet contains high voltage components and wiring. Access should be limited to authorized personnel.
HM750A1000 Inlet Valve Replacement 3. SLIDE FORWARD WARNING Disconnect main power source before accessing internal compartments. The inside of the humidifier cabinet contains high voltage components and wiring. Access should be limited to authorized personnel. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. Drain the cylinder by pressing the Power/Drain button on the front of the humidifier for 1 second.
HM750A1000 TROUBLESHOOTING CAUTION High Voltage Hazard. Be aware, when troubleshooting, that the humidifier is powered by high voltage and familiarity with both good practices and wiring of the humidifier is recommended. Any troubleshooting that requires opening the cabinet should be done by qualified personnel. CAUTION Burn and Scalding Hazard. Hot water or steam with a temperature above 120 °F (49 °C) can cause burns from scalding.
HM750A1000 HM750 Faults Clearing a Fault The self-diagnostic system built into the HM750 is continually monitoring the operation of the humidifier. When an abnormal condition occurs that cannot be selfcorrected by the software, the HM750 will turn off power to the cylinder, drain the cylinder, and annunciate the fault using the yellow Service LEDs. • Check the flash sequence against the list of fault messages and take any necessary actions to correct the cause(s) as outlined in the below table.
HM750A1000 Service LED Symptom Cause Corrective Action(s) Fault 3 flashes Cylinder plugs installed incorrectly Check that cylinder plugs are completely seated Insufficient on cylinder. Current Fill valve activated Fill valve inlet filter clogged Check fill valve inlet filter and clean if required. for long time, but high water level not reached. Fill should be faster than 1 in. per minute. Fault 4 flashes PCB Error The control board detects current draw when the humidifier is in standby mode.
HM750A1000 ORANGE BLACK BLACK ELECTRODES TO CARTRIDGE MAIN SUPPLY L1 L2/N GND STEAM CARTRIDGE GND J10 AIR PROVING J14 FUSE T2A 250V AIR PROVING SW HUMIDISTAT 24VAC COM HUMIDISTAT VOLTAGE SELECTION 120VAC EXTERNAL GT RF GF 240VAC IDLE LED FILLING LED HUMIDIFYING LED DRAINING LED TRANSFORMER BLACK BLUE CYLINDER LED FILL VALVE FAULT LED RED YELLOW DRAIN VALVE ON/OFF/DRAIN/FAULT RESET BUTTON FAULT CODES NUMBER OF FLASHES INDICATES FAULTS TO CLEAR FAULTS, PRESS AND HOLD POWER BUTTON FOR FIVE SEC
HM750A1000 5-YEAR LIMITED WARRANTY Resideo warrants this product, excluding battery, to be free from defects in workmanship or materials, under normal use and service, for a period of five (5) years from the date of first purchase by the original purchaser. If at any time during the warranty period the product is determined to be defective due to workmanship or materials, Resideo shall repair or replace it (at Resideo’s option).
IMPORTANT Lisez et conservez ces instructions. Ce guide doit être conservé par l’installateur. HM750A1000 HUMIDIFICATEUR À VAPEUR À ÉLECTRODES ÉVOLUÉ INSTRUCTIONS D’INSTALLATION Outils nécessaires — — — — — — Tournevis à tête plate Tournevis cruciforme Clé Tuyau en cuivre (facultatif) Niveau à bulle Scie à trous Configuration de l’humidificateur Le HM750 est configuré en usine pour fonctionner dans la plupart des conditions sans qu’il soit nécessaire de modifier sa configuration.
HM750A1000 Tableau 1. Spécifications. Volts Sortie de vapeur en gal./jour (Litres/jour) kW 110/120 11 (41,6) 1,5 220/240 22 (83,3) 3,0 Fusible ext. max. (A) Phase A 12 1 15 Cylindre standard HM750ACYL Poids net/brut en lb (kg) Dimensions LxHxP 10,5 / 18,5 10 x 18 x 7 in. (4,8 / 8,4) 254 x 457 x 178 mm MISE EN GARDE S/N DATECODE 110-120 12 220-240 12 S/N 22 1.5 3.0 AMP KW S/N 110-120 12 11 1.5 Country Pays of origin: d’origine Canada : Canada 220-240 12 22 3.
HM750A1000 Pièces et accessoires Les pièces et accessoires suivants sont disponibles et peuvent être inclus avec votre humidificateur HM750. Le cylindre est le seul élément qui doit être remplacé régulièrement pour maintenir le bon fonctionnement de l’humidificateur. Tableau 2. Pièces et accessoires.
HM750A1000 DIMENSIONNEMENT IMPORTANT Valider les dimensions du volume à couvrir avant d'installer le HM750. N’utilisez pas la mesure de la surface lorsque vous dimensionnez l’installation d’un humidificateur. Utilisez plutôt des pieds cubes, car l’humidité remplit un volume d’espace (largeur x longueur x hauteur). Tenez également compte de l’« étanchéité » d’une maison.
HM750A1000 MONTAGE 12 (305) 4 (102) DISTRIBUTION DE VAPEUR 4 (102) 1 (25) 1 (25) SI L’APPAREIL EST CÂBLÉ AVANT LE MONTAGE. 36 (914) POUR PERMETTRE L’ACCÈS AU CÂBLAGE. DISPOSITIF DE 1 VÉRIFICATION DE AP PRÉSENCE D'AIR AP (OU CAVALIER) 1 UN CAVALIER EST PRÉINSTALLÉ À LA PLACE D'UN DISPOSITIF DE VÉRIFICATION DE PRÉSENCE D'AIR. RETIREZ LE CAVALIER SI VOUS UTILISEZ UN DISPOSITIF DE VÉRIFICATION DE PRÉSENCE D'AIR. Humidistat COMMANDES 24 V c.a. COM HUM HUM DIAM. EXT.
HM750A1000 EMPLACEMENT Installez l’appareil sur un mur ou une surface verticale adéquat. Ne laissez pas l’unité reposer sur le sol. Laissez les dégagements requis pour les raccordements électriques et de plomberie. Les dimensions des dégagements indiquées ici sont fournies à titre de référence uniquement et constituent le minimum requis pour l’entretien de l’humidificateur.
HM750A1000 LARGEUR D’1/2 CONDUIT ÉCOULEMENT D’AIR MF37233 Fig. 6.
HM750A1000 Instructions pour les lignes de vapeur Veuillez suivre les instructions ci-dessous pour l’installation des lignes de vapeur du HM750. La non-utilisation du matériel recommandé (voir le Table 5) ou le non-respect de toute autre instruction d’installation des lignes de vapeur se traduira par un fonctionnement incorrect et pourrait annuler la garantie. Tableau 5. Matériel recommandé pour les lignes de vapeur du HM750.
HM750A1000 Exemples d’installation de la ligne de vapeur 12 (305) 4 (102) MINIMUM RAYON MINIMUM DE 12 (305) RAYON MINIMUM DE 305 (12) SUPPORTS DE MONTAGE SUPPORTS 1 DE MONTAGE CONNEXION DU TUYAU DE VAPEUR AU CYLINDRE OBSTRUCTION HM750 Status Idle Filling Humidifying Draining Service Cylinder Fault Power Drain Fault Codes In Front Cover HM750 Status 12 (305) MINIMUM Idle Filling Humidifying Draining Service Cylinder 12 (305) MINIMUM 4 (102) MINIMUM Fault Power Drain Fault Codes In Front Cove
HM750A1000 MONTAGE DE L’HUMIDIFICATEUR Le HM750 peut être monté soit directement sur le conduit d’alimentation en air soit à distance sur un mur. En cas de montage à distance, la buse de distribution est montée sur un conduit et reliée au HM750 par un tuyau de vapeur. Le HM750 présente un trou de serrure et trois orifices de montage supplémentaires, comme représenté sur la Fig. 12. MONTAGE SUR CONDUIT 1. 2. 3. TROU DE SERRURE Retirez le couvercle de l’humidificateur et sortez le cylindre.
HM750A1000 Montage sur le conduit d’alimentation Le HM750 peut également être monté directement sur le conduit d’alimentation. Dans ce cas, vous devez retirer le guide de vapeur et le remplacer par la buse de vapeur et le déflecteur comme suit : RETIREZ LE GUIDE DE VAPEUR MISE EN GARDE Ne retirez pas le couvercle lorsque l’humidificateur est sous tension. 1. 2. Retirez le couvercle avant de l’humidificateur.
HM750A1000 PLOMBERIE DIAM. EXT. 19 MM (0,75 PO) LIGNE D’EAU EN CUIVRE OU LDPE 6,35 MM (1/4 PO) INSTALLEZ TOUJOURS UN ROBINET D’ARRÊT D’EAU. UTILISEZ UN TUYAU EN CUIVRE DE DIAM. EXT. DE 12,7 MM (1/2 PO) DANS UN RAYON DE 1,2 M (4 PI) DE L’HUMIDIFICATEUR. MF37187 Fig. 18. Raccordement de l’alimentation en eau et de la vidange. IMPORTANT — Utilisez de l’eau potable. — Tous les raccordements des lignes d’alimentation en eau et de vidange doivent être installés conformément aux codes de plomberie locaux.
HM750A1000 ÉLECTRICITÉ MISE EN GARDE Le câblage doit être effectué par un électricien certifié. Il est recommandé d’effectuer l’installation sur un circuit à disjoncteur de fuite de terre. Ne retirez pas le couvercle lorsque l’humidificateur est sous tension.
HM750A1000 Commandes à basse tension Exigences • Utilisez un fil solide d’un calibre d’au moins 18 AWG. • Le câblage basse tension doit être acheminé à travers l’orifice situé sur la gauche du connecteur serre-câble. • Maintenez les fils de contrôle les plus courts possible. Procédure de câblage L’humidificateur peut être relié aux trois appareils suivants (Fig. 23) : 1. Humidistat ou thermostat 2. Dispositif de contrôle de la présence d’air (recommandé) 3.
HM750A1000 HUMIDIPRO H6062 R C DISPOSITIF DE VÉRIFICATION DE PRÉSENCE D'AIR (OU CAVALIER) U THERMOSTAT R Rc W Y G U S Air Proving AP AP Humidistat 24 Vca COM HUM HUM S CAPTEUR EXTÉRIEUR External GT RF GF HM750 R C W Y G CVCA MF37760 Fig. 24. Câblage de l’humidificateur de vapeur à l’aide d’un thermostat mécanique.
HM750A1000 DÉMARRAGE Vérification de l’installation 5. Avant de mettre le HM750 sous tension, inspectez l’installation pour vérifier qu’elle a été effectuée correctement, conformément aux présentes instructions d’installation. Marche/arrêt Le HM750 est configuré en usine pour fonctionner en tant qu’humidificateur avec commande de marche/arrêt. Il se met en route lorsqu’une tension de 24 V c.a.
HM750A1000 FONCTIONNEMENT Voyants DEL d’état L’interface utilisateur du HM750 comprend une série de voyants DEL qui fournissent des informations sur l’état de l’humidificateur. HM750 Status Idle Filling Humidifying Draining L’humidificateur continue de fonctionner normalement tandis que ce voyant clignote. Après 7 jours de clignotement, le voyant DEL devient fixe et l’humidificateur ne génère plus de vapeur. Vous devez remplacer le cylindre.
HM750A1000 SORTIE DE VAPEUR GODET DE REMPLISSAGE CAPTEUR DE NIVEAU D’EAU ÉLEVÉ CONNECTEURS HAUTE TENSION DU CYLINDRE CYLINDRE DE VAPEUR HM750 INTERFACE UTILISATEUR Status Idle Filling Humidifying Draining Service Cylinder BOUTON ALIMENTATION/VIDANGE Fault Power Drain Fault Codes In Front Cover SOUPAPE DE REMPLISSAGE SOUPAPE DE VIDANGE RACCORD RAPIDE SORTIE DE PURGE MF37211 Fig. 26. Composants de l’humidificateur.
HM750A1000 ENTRETIEN ET RÉVISION Entretien requis RACCORDEMENTS DES TUYAUX Inspectez-les annuellement et nettoyez-les si nécessaire. L’humidificateur HM750 a été conçu pour nécessiter un minimum d’entretien. L’entretien périodique consiste à vérifier que l’humidificateur est en bon état, à remplacer le cylindre lorsque le logiciel signale qu’il est en fin de vie et à nettoyer la soupape de vidange chaque fois que le cylindre est remplacé.
HM750A1000 PIÈCES DE RECHANGE MISE EN GARDE Avant l’entretien 1. Débranchez la source d’alimentation principale avant d’accéder aux compartiments internes. 2. Les compartiments électriques et de la plomberie contiennent des composants et des câblages à haute tension. L’accès doit être limité au seul personnel autorisé. 3.
HM750A1000 Retrait du cylindre 5. 6. AVERTISSEMENT 7. Débranchez la source d’alimentation principale avant d’accéder aux compartiments internes. L’intérieur du boîtier de l’humidificateur contient des composants et des câblages à haute tension. L’accès doit être limité au seul personnel autorisé. 8. 9. 1. 2. 3. 4. Vidangez le cylindre actuel en appuyant sur le bouton Alimentation/Vidange sur l’avant de l’humidificateur pendant 1 seconde.
HM750A1000 Retrait de la soupape de vidange (pour nettoyage ou remplacement) (brosse à dents) ou d’un chiffon humide. N’utilisez PAS de brosse métallique ou d’agents de nettoyage chimiques car la pièce risquerait d’être endommagée. Nettoyez toujours la soupape de vidange avant d’installer un nouveau cylindre. Du calcaire présent sur le cylindre usagé peut tomber sur la soupape de vidange et empêcher son bon fonctionnement.
HM750A1000 Nettoyage du filtre de la soupape d’arrivée Ouverture du compartiment électrique En fonction de la qualité de l’eau, un nettoyage régulier du filtre de la soupape de remplissage peut se révéler nécessaire. Cette opération peut être réalisée sans retirer la soupape de l’humidificateur. AVERTISSEMENT Débranchez la source d’alimentation principale avant d’accéder aux compartiments internes. L’intérieur du boîtier de l’humidificateur contient des composants et des câblages à haute tension.
HM750A1000 4. 5. 6. 7. 8. Après avoir vérifié que la rondelle en plastique est insérée entre la tête de la vis et le panneau de commande, resserrez la vis de retenue du panneau de commande. Remettez en place le couvercle du compartiment électrique. Remettez en place le couvercle avant de l’humidificateur et tournez la vis de verrouillage de 90° dans le sens horaire pour la verrouiller. Activez l’alimentation du secteur de l’humidificateur au niveau de l’interrupteur externe.
HM750A1000 DÉPANNAGE MISE EN GARDE Risque de haute tension Lors des opérations de dépannage, gardez à l’esprit que l’humidificateur est alimenté par une haute tension et qu’il est recommandé de maîtriser les bonnes pratiques et le câblage de l’humidificateur. Toute opération de dépannage nécessitant d’ouvrir le boîtier doit être effectuée par du personnel qualifié. MISE EN GARDE Risque de brûlure L’eau ou la vapeur chaude d’une température supérieure à 49 °C (120 °F) peut provoquer des brûlures.
HM750A1000 Erreurs du HM750 Le système d’autodiagnostic intégré au HM750 surveille en continu le fonctionnement de l’humidificateur. Lorsqu’une condition anormale survient et qu’elle ne peut pas être corrigée automatiquement par le logiciel, le HM750 coupe l’alimentation du cylindre, vidange celui-ci et annonce l’erreur à l’aide des voyants DEL Service jaunes.
HM750A1000 Voyant DEL Service Symptôme Cause Mesure(s) corrective(s) Fault (Défaut) Courant 3 insuffisant clignotements Soupape de remplissage activée depuis un long moment, mais niveau d’eau élevé non atteint. La vitesse de remplissage doit être supérieure à 25 mm par minute. Conncteurs du cylindre installés Vérifiez que les connecteurs haute tension sont incorrectement insérés à fond sur le cylindre.
HM750A1000 ORANGE NOIR NOIR ÉLECTRODES VERS LA CARTOUCHE ALIMENTATION PRINCIPALE L1 L2/N GND CARTOUCHE DE VAPEUR GND J10 AIR PROVING DISPOSITIF DE VÉRIFICATION DE PRÉSENCE D'AIR J14 FUSIBLE T2A 250 V HUMIDISTAT 24 Vca COM HUMIDISTAT SÉLECTION DE LA TENSION 120 Vca EXTERNAL GT RF GF 240 Vca DEL VEILLE DEL REMPLISSAGE DEL HUMIDIFICATION DEL VIDANGE TRANSFORMATEUR NOIR BLEU DEL CYLINDRE SOUPAPE DE REMPLISSAGE DEL DÉFAUT ROUGE JAUNE SOUPAPE DE VIDANGE BOUTON MARCHE/ARRÊT/VIDANGE/ DE RÉINITIALI
HM750A1000 GARANTIE LIMITÉE DE 5 ANS Resideo garantit ce produit, à l’exception des piles, contre tout défaut de pièce ou de main-d’œuvre, durant une période pour cinq (5) ans à partir de la date d’achat par le consommateur d’origine si le produit est utilisé et entretenu convenablement. En cas de défaillance ou de mauvais fonctionnement pendant la période de garantie, Resideo remplacera ou réparera le produit, à sa discrétion.
HM750A1000 33-00289EF—03 30
HM750A1000 31 33-00289EF—03