Honeywell Model 700/800 Signal Processor and Viewing Head USER MANUAL • Model 700ACSP Universal 85-265 VAC powered, plus 24VDC backup. • Model 700DCSP 22-26VDC powered, plus 24VDC backup. The two Model 700 signal processors are similar, with 12 push-buttons, a two-digit numeric display, and four LED status indicators for operator interface. The only difference between the two is that one accepts AC power and the other accepts DC power. Both models also accept 24VDC backup power.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD Table 1. Available viewing head models and associated features. Model Pipe Fit Connection 0.5 in. NPTM with 50-ft (15.2 m) pigtail Connector S702 X S702HF X S702PF S802HF X S806 X 3. X X X X X X X X X X X X X X UV Detector Spec S706 & S706PF, S806: UVtron with spectral response 185nm to 260nm and a peak response at 210nm All models include Electronic self-check. Flicker Frequency filter settings available for IR sensor models.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD APPROVALS 4. S70X/S80X Viewing Heads (Connector series and Pipe fit series [PF]) CSA for CLASS I, DIV 2, GROUPS A, B, C, D & T4A FM 7610/NEMA 4X and CLASS 1, DIV 2, GROUPS A, B, C, D & T4A* SIL 3 “Fit for Use” IECEx CSA 10.0003 Ex nA IIC T4 Gc -40
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD +26VDC + AC POWER SUPPLY GND APPROVED 0-20 OR 4-20 MA + INSTRUMENTATION 360 OHMS MAX - .125 A -t° 2A .4A CHASSIS, EARTH, OR SYSTEM GND FOR INDICATOR OR TO VIEWING HEAD + GROUND M34280 Fig. 1. Model 700ACSP Signal Processor Wiring.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD +26VDC + GND .125 A LIM APPROVED 1A 1A .4A +26 PWR 0-20 OR 4-20 MA + FOR INDICATOR OR INSTRUMENTATION 360 OHMS MAX - TO VIEWING HEAD CHASSIS, EARTH, OR SYSTEM GND + DC POWER SUPPLY 250 MA + 24 V BACKUP BATTERY (OPTIONAL) M34282 Fig. 2. Model 700DCSP Signal Processor Wiring.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD Viewing Head Connector and Wiring “Accessories” on page 9 for part numbers. The use of 22g, 4conductor cable with shield and drain is recommended. The shield should be foil and braid type surrounding all conductors. The shield should be connected to GND at the processor end. The cable diameter should not exceed 0.307" in order for it to go through the hex bushing in the connector.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD VH SC GREEN LED VH SIG VH +V ORANGE LED VH GND METAL CONNECTOR RING 5-16 (8) VIEWING HEAD CONNECTOR MAX LOOKING AT PINS CONNECTOR REAR VIEW WITH NUT LOOSENED AND COVER REMOVED C330S YELLOW, 4 COND WITH FOIL/BRAID SHIELD AND DRAIN (ITC & CIC) WHITE BLACK RED SHIELD GREEN TERMINAL VH SIG VH SC VH +V VH GND M34286A Fig. 4. Model 700/800 Viewing Head Cable Connections. Cable Preparation 2.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD M35140 Fig. 6. ASSY786 Viewing Head Plug Assembly with C330S. Protecting the Viewing Head Cable (Connector Series) Viewing Head Mounting Block The S70X viewing heads are held firmly in place in their mounting blocks by two galvanized steel latches. The S80X viewing head is secured in its mounting block by a friction twist-lock. Refer to the ACCESSORIES section for part numbers.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD ACCESSORIES position has been decided. A continuous flow of air must be maintained in order to reduce the conducted heat and to keep the sight pipe and viewing head lens free of dirt and debris. Air required is about 5 SCFM (0.13 Nm3 /min) delivered at 1 in. (25mm) above the maximum pressure as measured at the “Y” or “T” section of the purge air connection for each viewing head.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD Filter Selection for IR Viewing Head Vortex coolers (M3204, M3208, M3210, M4025) - Used with air cooling canister. Contact your distributor or the factory for selection assistance. If a good count ratio between BNR-ON and BNR-OFF cannot be obtained when using an IR viewing head—particularly when monitoring oil flames—an IR viewing head with the High Frequency (HF) filter option is recommended.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD Self-Checking ring to hold it in place so that it is sandwiched tightly between the two retaining rings. The self-check circuitry guards against internal component failure. There are several tasks that require intelligent interaction between the viewing heads and the signal processor. If all of these interactions do not occur properly, the viewing head will not send pulses back to the signal processor and the flame relay will open.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD • • • • • • • • • • • To change the gain, press and hold the SET GAIN button for two seconds until the current value is displayed. Use the INCREASE and DECREASE buttons to change the setting as appropriate while the value is displayed. To store the new setting, press the STORE button until “- -” is shown, indicating the value has been accepted. INCREASE, DECREASE and STORE buttons (range of 00 to 29).
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD is live. Adjustments will cause the Flame Relay to de-energize immediately, ignoring FFRT settings. To exit the menu at any time without saving changes, simply press the RESET/rE button or wait four seconds. To access this setpoint, press and hold the ACCEPT RATIO/ SET GAIN button for 2 seconds until the current value is displayed. While the value is displayed, adjustments may be made via the INCREASE or DECREASE arrow buttons.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD the computed ratio, for example, “AC” and “75.” Press either the ACCEPT RATIO or RESET keys. If ACCEPT RATIO is pressed, the display responds with “- -”, the ratio is stored, and the AUTO SET LED is turned on. If RESET is pressed, the display returns to the counts, both of the AUTO SETUP LEDs are turned off, and the old setpoints are used. Table 3.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD • • • • using key sequence below at the front panel of the 700 as follows: 1. 2. 3. Press and hold BNR-OFF SEQ START/END button for 2 seconds. Press up arrow to change setting from P0 to P1. Press STORE.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD BOILER 1 ADDRESS BNR 1 11 BNR 2 12 BNR 3 13 BNR 4 14 ADDRESS BNR 1 31 BNR 2 32 BNR 3 33 BNR 4 34 BNR 5 15 BNR 6 16 BOILER 3 MODBUS MASTER CONTROL NOTES: A CONVERTER MAY BE NECESSARY FOR COMMUNICATION WITH THE MODBUS MASTER CONTROL. USE SHIELDED CABLE FOR COMMUNICATION WIRING. DRAWING IS FOR GENERAL REFERENCE ONLY.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD TROUBLESHOOTING Lockout or Faulty VH Indication cannot be energized. The signal processor can be reset by changing the RELAY ON SETPOINT to a reasonable value or by pressing LOAD FACTORY DEFAULTS. If the viewing head produces any pulses during the last one third of the self-check time, the relay will immediately deenergize, the display will show “LO” (lockout), and the FAULT LED will flash on and off rapidly. Exit lockout by pressing RESET.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD 1/2 (13) 14 NPT FOR SIGHTING PIPE 1/2 (13) 14 NPT FOR SIGHTING PIPE HEX 1-1/2 (38) ACROSS FLATS HEX 1-1/2 (38) ACROSS FLATS 1-49/64 (45) DIA MOUNTING BLOCK 1-49/64 (45) DIA MOUNTING BLOCK 1/4 (6) 18 NPT FOR PURGE AIR 1/4 (6) 18 NPT FOR PURGE AIR 7-23/32 (196) 8-19/64 (211) 6 (153) 6-13/32 (163) 13/32 (10) 1-27/64 (36) 21/64 (8) 1-31/64 (38) 1-1/8 (29) DIA M34283 M34284 Fig. 10. Models S802 and S806 Viewing Heads. Fig. 9.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD RELAY CONNECTIONS RS-422 WIRING 35MM DIN RAIL CL 5-1/2 (139) APPROVED +26 PWR DIN RAIL RELEASE 1/4 (6) 2-29/32 (74) 3-1/4 (83) M34584 Fig. 11. Model 700DCSP Signal Processor.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD RELAY CONNECTIONS RS-422 WIRING MODEL 700AC 35MM DIN RAIL CL 5-1/2 (139) APPROVED DIN RAIL RELEASE 1/4 (6) 2-29/32 (74) 3-1/4 (83) M34851 Fig. 12. Model 700ACSP Signal Processor.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD BURNER FRONT PLATE 1 (25) NPT NIPPLE TOE S70X VIEWING HEAD 1/4 (6) NPT PURGE CONNECTION 700-1 SWIVEL MOUNT QUICK DISCONNECT CABLE CONNECTION (SUPPLIED) M34537 Fig. 13. Viewing Head Mounting Example. BURNER FRONT PLATE OR WINDOWBOX 1/2 (13) NPTM PIPE S70X VIEWING HEAD 1/4 (6) NPT PURGE CONNECTION QUICK DISCONNECT CABLE CONNECTION (SUPPLIED) FLANGE (OPTIONAL) M34538 Fig. 14. Viewing Head Mounting Example.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD HIGH FREQUENCY FLICKER ZONE DETECTOR IN GOOD SIGHTING POSITION (PARALLEL SIGHTING) BURNER NOZZLE CENTERLINE DETECTOR IN POOR SIGHTING POSITION LOW FREQUENCY FLICKER ZONE M33285 Fig. 15. IR Viewing Head Location UV RADIATION ZONE UV VIEWING HEAD SIGHTED ON UV ZONE BURNER NOZZLE CENTERLINE M33286 Fig. 16.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD NO. 1 FLAME ENVELOPE NO. 2 FLAME ENVELOPE VIEWING HEAD VIEWING HEAD BURNER NOZZLE NO. 1 BURNER NOZZLE NO. 2 HIGH FREQUENCY IR ZONE LOW FREQUENCY ZONE (LESS THAN 36Hz) HIGH FREQUENCY IR ZONE M33287 Fig. 17.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD RESTORING DEFAULT VALUES LOAD FACTORY DEFAULTS PRESS LOAD FACTORY DEFAULTS FOR 2 SECONDS 2 SECS IS THE PANEL LOCKED? Y DISPLAY SHOWS ‘PL’, MEANING THE PANEL IS LOCKED N NORMAL OPERATION IS THE AUTO SET LIGHT LIT? Y DISPLAY SHOWS ‘CF’, MEANING CONFIRM N RESET rE PRESS RESET OR WAIT 4 SECONDS TO CANCEL CHANGING THE AUTO SET VALUES OR LOAD FACTORY DEFAULTS PRESS LOAD FACTORY DEFAULTS AGAIN TO CONFIRM YOU WANT TO CHANGE THE AUTO SET VALUE
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD AUTO SETUP BNR-ON SEQ START/END PRESS BNR-ON SEQ FOR 2 SECONDS 2 SECS IS THE PANEL LOCKED? Y DISPLAY SHOWS ‘PL’ UNTIL KEY RELEASED N IS THE AUTO SET LIGHT LIT? Y DISPLAY SHOWS ‘CF’, MEANING CONFIRM N PRESS RESET OR WAIT 4 SECONDS TO CANCEL AUTO SETUP RESET rE OR BNR-ON SEQ START/END IS THE FLAME ON LIGHT LIT? PRESS BNR-ON SEQ AGAIN TO CONFIRM YOU WANT TO BEGIN TAKING DATA FOR AUTO SETUP N DISPLAY SHOWS ‘BO’, MEANING BURNER OFF Y
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD NOTE: AUTO SETUP - PAGE 2 (CONTINUED) RESET rE PRESS RESET AT ANY TIME DURING THIS PROCEDURE TO CANCEL AUTO SETUP DISPLAY BEGINS COUNTING DOWN FROM 59 SECONDS BNR-ON SEQ START/END PRESS BNR-ON SEQ AGAIN TO END TAKING BURNER ON DATA OR WAIT UNTIL THE COUNT REACHES ZERO (30 SECONDS MINIMUM RECOMMENDED) DISPLAY RETURNS TO CURRENT FLAME SIGNAL AND AUTO SETUP OFF SEQ LIGHT FLASHES TURN BURNER OFF BNR-OFF SEQ START/END PRESS BNR-OFF SEQ TO BEGIN
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD NOTE: AUTO SETUP - PAGE 3 (CONTINUED) RESET rE Y IS THE AUTO SETUP RATIO MARGINAL? 71% < RATIO < 81% PRESS RESET AT ANY TIME DURING THIS PROCEDURE TO CANCEL AUTO SETUP RATIO MAY BE ACCEPTABLE N DISPLAY ALTERNATES SHOWING ‘AC’ AND THE NEW RATIO SETTING ACCEPT RATIO SET GAIN PRESS ACCEPT RATIO / SET GAIN TO ACCEPT THE RATIO DISPLAYED DISPLAY SHOWS ‘_ _’ FOR ONE SECOND AND NEW VALUES ARE SAVED NORMAL OPERATION IS THE AUTO SETUP RATIO UNACCE
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD SETTING RELAY ON VALUE RELAY ON SET POINT PRESS RELAY ON SET POINT FOR 2 SECONDS DISPLAY SHOWS CURRENT RELAY SETTING 2 SECS INCREASE USE INCREASE OR DECREASE KEYS TO ADJUST SETTING DECREASE IS THE PANEL LOCKED? Y DISPLAY SHOWS ‘PL’ UNTIL KEY RELEASED N IS THE AUTO SET LIGHT LIT? Y DISPLAY SHOWS ‘CF’, MEANING CONFIRM N PRESS RESET OR WAIT 4 SECONDS TO CANCEL CHANGING THE AUTO SETTING RESET rE OR RELAY ON SET POINT PRESS RELAY ON SET
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD SETTING RATIO PERCENTAGE RATIO (%) RATIO OFF RATIO ON PRESS, RATIO (%), FOR 2 SECONDS DISPLAY SHOWS CURRENT RATIO SETTING IN PERCENT 2 SECS INCREASE DECREASE IS THE PANEL LOCKED? Y USE INCREASE OR DECREASE KEYS TO ADJUST SETTING DISPLAY SHOWS ‘PL’, UNTIL KEY RELEASED N IS THE AUTO SET LIGHT LIT? Y DISPLAY SHOWS ‘CF’, MEANING CONFIRM N PRESS RESET OR WAIT 4 SECONDS TO CANCEL CHANGING THE AUTO RATIO RESET rE OR RATIO (%) PRESS RATIO
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD SETTING FLAME FAILURE RESPONSE TIME (FFRT) FFRT 1/2/3 SEC OPTION PRESS, FFRT, FOR 2 SECONDS DISPLAY SHOWS CURRENT SETTING IN SECONDS 2 SECS INCREASE DECREASE IS THE PANEL LOCKED? Y USE INCREASE OR DECREASE KEYS TO ADJUST SETTING DISPLAY SHOWS ‘PL’, UNTIL KEY RELEASED N STORE INCREASE USE INCREASE OR DECREASE KEYS TO ADJUST SETTING PRESS STORE TO SAVE THE NEW SETTING OR DECREASE RESET rE PRESS RESET OR WAIT 4 SECONDS TO RESTORE OLD SE
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD SETTING ANALOG OUTPUT LEVELS (0-20/4-20 mA) 0-20 mA 4-20 mA OPTION DISPLAY SHOWS: PRESS, 0-20 / 4-20 mA OPTION, FOR 2 SECONDS ‘02’ FOR 0-20 mA ‘42’ FOR 4-20 mA 2 SECS INCREASE USE INCREASE OR DECREASE KEYS TO ADJUST SETTING DECREASE IS THE PANEL LOCKED? Y DISPLAY SHOWS ‘PL’, UNTIL KEY RELEASED N STORE INCREASE USE INCREASE OR DECREASE KEYS TO ADJUST SETTING PRESS STORE TO SAVE THE NEW SETTING OR DECREASE RESET rE PRESS RESET OR WAIT 4
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD SETTING VIEWING HEAD GAIN ACCEPT RATIO SET GAIN PRESS ACCEPT RATIO / SET GAIN FOR 2 SECONDS DISPLAY SHOWS CURRENT GAIN SETTING 2 SECS INCREASE DECREASE IS THE PANEL LOCKED? Y USE INCREASE OR DECREASE KEYS TO ADJUST SETTING DISPLAY SHOWS ‘PL’ UNTIL KEY RELEASED N STORE PRESS STORE TO SAVE THE NEW SETTING OR RESET rE PRESS RESET OR WAIT 4 SECONDS TO RESTORE OLD SETTING NORMAL OPERATION Fig. 26. Flow Chart 9: Viewing Head Gain Setting.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD SAFETY MANUAL: 700 SIGNAL PROCESSOR 700ACSP, 700DCSP Product Declaration FIT FOR USE IN A LOW DEMAND SAFETY APPLICATION. Models: 700ACSP & 700DCSP Models SIL HFT SFF PFD λs λdd λdu 10-6 10-9 8.20 x 10-9 8.53 x 10-9 8.20 x 10-9 700AC 3 0 >99% 1.79 x 10 1.93 x 700DC 3 0 >99% 1.79 x 10-4 1.36 x 10-6 -4 System Architecture 8.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD signal. Each relay must be driven by an alternating signal of the proper frequency and duty cycle from the processor. As an added safety feature, the coil of the Flame Relay is wired in series with a second pole of contacts on a Self Check Relay. The Self Check Relay is designed to be closed during normal operation of the signal processor and open during detection of a fault or power down.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD 700AC or 700DC Signal Processor Proof Test Procedure Equipment 3. • Powered 700AC or 700DC correctly connected to a compatible viewing head. • Multimeter able to take voltage and resistance measurements. • For 700AC signal processors, an 85V AC to 265V AC power source. • For 700DC signal processors, a 22V DC to 26V DC power supply. • Light source* capable of generating a flame on condition. 4. 5.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD SAFETY MANUAL: S70X & 80X VIEWING HEAD S702, S706, S802, AND S806 Product Declaration FIT FOR USE IN A LOW DEMAND SAFETY APPLICATION. Models: S702, S702-PF, S702-HF, S702-HF-PF, S706, S706-PF, S802, S802-HF, S806 Models SIL HFT SFF PFD λs λdd λdu S702 and S802 3 0 >99% 1.81 x 10-10 1.70 x 10-7 2.27 x 10-11 0 S706 and S806 3 0 >99% 1.51 x 10-5 1.02 x 10-5 2.27 x 10-11 6.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD Safety Function of the S702, S706, S802, and S806 S70X and S80X Viewing Head Proof Test Interval The S702, S706, S802, and S806 viewing heads do not have a safety function. They are used to provide flame intensity information via cables to Signal Processor Models 531AC, 531DC, 532AC, 532DC, 700AC, 700DC, and 800 which use Flame Relays to provide a safety function. The proof test must be conducted every 1 to 5 years.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD 5. Product Decommissioning a. Increase the gain and store the setting. Ensure the flamecount increased. b. Decrease the gain and store the setting. Ensure the flamecount decreased. Restore all original settings as recorded in Setup and reconnect the signal processor to the safety system. 66-2069—02 When required, decommissioning of the S70X and S80X viewing heads should be performed in accordance with requirements of the overall safety system.
HONEYWELL MODEL 700/800 SIGNAL PROCESSOR AND VIEWING HEAD 39 66-2069—02