IPGSM-DPC Commercial Fire Communicator Installation and Setup Guide IPGSM-DPC Commercial Fire Communicator RADIO TROUBLE LOW BATT AC LOSS AC ON 800-09370 6/11 Rev.
Contents General Information .......................................................................................................................1 Package Contents .......................................................................................................................1 Compatible Fire Panels ..............................................................................................................1 Operation ...............................................................................
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide General Information The IPGSM-DPC Commercial Fire Communicator (henceforth referred to as IPGSM-DPC) includes everything you need to upgrade a commercial fire system that previously reported by POTS to a system that uses the Internet as its primary reporting path, and uses a GSM cellular reporting path as a backup.
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide Operation The IPGSM-DPC replaces the fire panel's POTS communications path. When an event occurs, the fire panel goes off-hook to dial the central station. The IPGSM-DPC detects the off-hook condition and provides the fire panel with a dial tone. When the fire panel detects the dial tone, it begins dialing the central station. The IPGSM-DPC considers the three second period after dialing as the number dialing has been completed.
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide Installation ULC Compliance To meet Canadian ULC compliance, ensure the following: IPGSM-DPC must be installed in accordance with Canadian Electrical Code, Part 1. IPGSM-DPC must be mounted in the same room and within 20 feet of the fire panel. The wiring must be routed through conduit. IPGSM-DPC, and all equipment used for the IP connection (such as the router, hub, modem, etc.
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide STEP 3 – Determine the Signal Strength and Select a Location IMPORTANT - Do Not mount this device outdoors. RF Exposure Warning – The antenna(s) used for this transmitter must be installed to provide a separation distance of at least 20 cm from all persons and must not be collocated or operating in conjunction with any other antenna or transmitter.
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide 4. Connect the LED Display board to its connector, then slide the board into the mounting rails. (Refer to the “LED Display Information” topic if a wire is detached from its connector.) 5. Carefully remove the packaging material that surrounds the PowerBoost1. 6. Mount the PowerBoost1 on the three unused standoffs.
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide ANTENNA 1451-UL9 WIRED TRANSFORMER WIRES MUST BE RUN IN CONDUIT TO 24 HR FACILITY POWER NUT, WASHER BLU BLU 120VAC, 60Hz, 850mA GND POST ANTENNA MOUNTING ADAPTER 18 VAC 72 VA TO Cabinet Ground Post GND BLU TO PowerBoost1 BLU DO NOT REMOVE these knockouts. Tin wire ends.
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide Wiring the 659EN Line Fault Monitor (if required) The IPGSM-DPC is compatible with the Honeywell brand FACP’s listed on page 1 when the model 659EN Line Fault Monitor is installed. 1. Refer to the installation guide for the 659EN. 2. Mount the 659EN on the lower left side of the IPGSM-DPC cabinet. 3. DO NOT cut the 659EN’s BLACK Output Relay Jumper or the BLUE Voltage Trip Threshold Jumper. 4.
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide STEP 5 – Program the Communications Module You must use the 7720P Programming tool to program the IPGSM-DPC. When using the 7720P Programming tool, the values given below are for most installations. Press the [#] key to accept the displayed default value (xxx) or enter the new value and press the [#] key for the next prompt. Use the [Space] key to scroll through a list of options. 1. 2. 3. 4. 5. 6. 7. 8.
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide To exit the programming mode, press [N] in response to the "Review?" prompt. Then press [Y] to the "Exit Prog Mode?" prompt. Upon exiting, the root file is updated to log the changes made. A message is displayed telling the user that this step is being executed. When complete, the message "DONE" is displayed to indicate the file was successfully uploaded.
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide Dialer Capture Module Information RED – Steady ON Messages exist in buffer. RED – Flashing No messages to be sent. Waiting for messages. GREEN – Steady ON Normal Indication. GREEN – Blinks every 2 sec. PowerBoost1 communication problem. GREEN – Blinks twice every sec. Communication Module connection is lost. GREEN – Blinks 10 times every sec. PowerBoost1 and Communications Module connection is lost.
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide PowerBoost1 Module Information LED Indicator STATUS AC (green) AC power available. ACTIVE (green) Cyclical flashing – normal communications. Repetition of 3 flashes – loss of communications. LOW BATT (yellow) Missing or low battery. TROUBLE (yellow) One or more trouble conditions exist, such as; overload, output supervision, ground fault, or charger failure.
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide iGSM Communications Module Information YEL ON – No contact with network. OFF – Normal. SLOW BLINK – Loss of communication with the Dialer Capture Module (ECP fault). FAST BLINK – No network contact AND loss of communication with the Dialer Capture Module. RED FCC:XXXXXXXXXX IC: YYYYYYYYYY RSSI TB 1 1 2 3 4 5 6 7 8 9 10 11 Tamper Switch Note: If all LEDs FAST BLINK in unison with the RSSI LEDs this indicates a Hardware Error.
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide RF Specifications Band Transmission Frequency (MHz) Transmit Power (dBm) Receive Frequency (MHz) Receive Sensitivity (dBm) Number of Channels Channel Spacing (MHz) Duplex Separation (kHz) GSM 850 824-849 33 869-894 -107 124 200 45 GSM 900 890-915 33 935-960 -107 124 200 45 GSM 1800 1710-1785 30 1805-1880 -106 374 200 95 GSM 1900 1850-1910 30 1930-1990 -105.
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide IPGSM-DPC Trouble Detection Information Telco 1 is used for the Fire Panel to output contact ID messages to the IPGSM-DPC, and Telco 2 is used by the IPGSM-DPC to report faults to the Fire Panel. If Telco 1 is not operational, the Fire Panel will use Telco 2 to report events if there are no faults in the iGSM Communications module.
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide NOTES – 15 –
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide NOTES – 16 –
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide NOTES – 17 –
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide NOTES – 18 –
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide NOTES – 19 –
IPGSM-DPC Commercial Fire Communicator – Installation and Setup Guide NOTES – 20 –
Wiring Diagram The wiring diagram below is depicted for point-to-point electrical connection checks used for troubleshooting or component replacement. It is not intended to show the physical routing of wires. When replacing a wire or component, ensure the wire is routed in the same manner as the original factory wire.
IC STATEMENT Notice: This Class A digital apparatus complies with Canadian ICES-003. Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada. IC STATEMENT This device complies with RSS 210 of IC. Operation is subject to the following two conditions: (1) This device may not cause harmful interference. (2) This device must accept any interference received, including interference that may cause undesired operation. Cet appareil est conforme à la RSS 210 des Industries Canada.