Dampers, Actuators and Valves control your environment with honeywell DAMPERS, valves and actuators Application And Selection Guide
How to use this guide Additional product information All pages in this literature are constructed in one of two ways: To find more detailed information on the individual products included in this document, go to: http://customer.honeywell.com and use the search text box to quickly locate product specific content. For unassembled product: As a reference, pictures will represent the valves and actuators separately; and part numbers are highlighted in blue.
Table Of Contents Section 1: DCA & Damper Selection Resilient Seat Butterfly Valves Dampers.......................................................................................8 2-Way Electrically-Actuated Control.......................................66 DCA............................................................................................12 3-Way Electrically-Actuated Control.......................................68 Fire and Smoke...........................................................
Table Of Contents Section 3: Submittal Sheets (CONT.) MP958.................................................................................104 Modutrol IV Motor Flanged Cage Valve V5051A................................................................................139 Flanged Globe Valve M4185; M8185....................................................................105 V5011A, B...........................................................................140 M6184; M6194................................
Table Of Contents Pneumatic Valve Actuator Parts and Accessories.....................196 Foot Mounted Motor Accessories.............................................198 Damper and Valve Linkage Accessories....................................200 Section 8: Competitive Cross Reference Direct Coupled Actuator............................................................202 Control Ball Valve 2-Way Valve ........................................................................
Selection GUIDE Section 1: DCA & Damper Selection Dampers.......................................................................................8 DCA............................................................................................12 Fire and Smoke...........................................................................
Damper And Actuator Sizing Use the following guidelines to determine the actuator quantity and torque requirements for your damper configuration. Determine Damper Actuator Locations Use the following configuration to determine the amount of actuator locations your damper will require. Determining Damper Actuator Torque Requirements Use the following procedure to determine the required torque for your damper. NOTE: Damper area is measured using the H and W dimensions.
DCA & Damper Selection Damper And Actuator Sizing Table 2. Approximate industry standard damper lb-in. per sq ft value. Face Velocity (fpm)/ Static Pressure (in. wc Leakage Damper Blades 500/ 1 1000/ 2 1500/ 3 2000/ 4 2500/ 5 Low Parallel 4 7 Low Opposed 3 5 10.5 12 14 7.5 8.5 10 Standard Parallel 3 Standard Opposed 2 4.5 6.5 7 8 3 4.5 5 6 Damper Sizing Dampers can be sized using two different methods; actual sizing and nominal sizing.
Damper And Actuator Sizing HVAC performance depends largely upon airflow, and Honeywell Volume Control Dampers are built for both improved airflow and heavy-duty use. Honeywell has long been the leading source for airflow control, with Volume Control Dampers that meet AMCA-certified Air Performance Standards, the highest established standards for commercial control dampers. Designed to minimize leakage, Honeywell dampers will give you efficient, trouble-free operation for years to come.
Standard Round Dampers Custom Dampers D690 and DM7600 Round Dampers. The 6” to 16” round dampers are used in zoning systems to control airflow in a round duct. These dampers come with neoprene and silicone seals for tight close off and low leakage. The DM7600 includes an actuator that is already attached to the round damper. Need a custom damper? Contact the Take-Off Service. Below is a sample list of the products we frequently quote.
Direct Coupled Actuators Direct coupled actuators quick selection guide Spring Return, Low Torque Precise, reliable performance. Lasting value. Ease of installation. Everything you look for in directcoupled actuators hinges on quality. And quality engineering is what makes Honeywell’s complete line of actuators the top performers in the industry.
spring return Running Time Order Specification Number Power Supply Control Input/Output Auxiliary Knob Approximate Spring 0/2-10 3 kOhm Feedback Area of Damper Drive Return 24 120-230 VA Rating Vdc, NTC, (0/2-10 (4.5 lb-in/sq. ft.
Fire & Smoke Actuators Honeywell’s complete line of two-position, fast-acting springreturn actuators meet all of your needs for fire and smoke control applications. All models are designed to meet the UL-555 and UL-555S high temperature requirements for fire dampers and combined fire and smoke dampers.
Section 2: Valve Selection Control Valve Applications . ........................................................17 Control Valve Selection Criteria ..................................................18 2-Way....................................................................................18 Fan Coil and Zone Valves........................................................... 22 With Tandem Linked Direct Coupled Actuators.....................46 Flanged Globe Valves 2 ½ - 3” With Dedicated Valve Actuators....
Control Valve Applications Control Valve Applications Valve Selection 17
Control Valve Selection Criteria 2-Way Unitary Attribute Specification Pipe Size VU52 VU53 Cartridge Globe V58x2 V5011N...
Control Valve Selection Criteria 2-Way Globe Control Ball Pressure-Balanced Attribute Specification Pipe Size V5862A3 VGF2xP Threaded Flanged VBN2 VBF2 1/2" [DN15] 3/4" [DN20] 1" [DN25] • • 1 1/4" [DN32] • • 1 1/2" [DN40] • 2" [DN50] 2 1/2" [DN65] Butterfly Resilient Seat VFF1 VFF2 • • • • • • • • • • • 3" [DN80] • • • 4" [DN100] • • • • 5" [DN125] • • • • 6" [DN150] • • • (maximum size) • 20" [DN500] Valve Selection Other Sweat Pipe Fitting
Control Valve Selection Criteria 3-Way Unitary Fan Coil Attribute Pipe Size Specification 1/2" [DN15] 3/4" [DN20] 1" [DN25] 1 1/4" [DN32] 1 1/2" [DN40] 2" [DN50] 2 1/2" [DN65] 3" [DN80] 4" [DN100] 5" [DN125] 6" [DN150] Other (maximum size) VU54 • • • Cartridge Cage VCzM/N • • • • Globe Cartridge Globe V58x3 V5863A3 • • • • • Sweat NPT Internal Thread Inverted Flare ANSI Flange Static Pressure ANSI 125/150 ANSI 250/300 Other 300 psi 300 psi 230 psi 230 psi Media Chilled Water Hot Water • •
Control Valve Selection Criteria 3-Way Control Ball Attribute Pipe Size Specification 1/2" [DN15] 3/4" [DN20] 1" [DN25] 1 1/4" [DN32] 1 1/2" [DN40] 2" [DN50] 2 1/2" [DN65] 3" [DN80] 4" [DN100] 5" [DN125] 6" [DN150] Other (maximum size) Butterfly Threaded Flanged VBN3 VBF3 VFF3 VFF6 • • • • • • • • • • • • • • • • • • • • • • Resilient Seat 20" [DN500] Static Pressure ANSI 125/150 ANSI 250/300 Other 360 psi Media Chilled Water Hot Water • • • • Flow Capacity, Cv Multiple ratings per p
Fan Coil and Zone Valves Honeywell Fan Coil and Zone Valves family (VU Series) have Common Features withstood the test of time as a reliable and dependable product. • Maximum static water pressure: 300 psig With a Cv range suitable for anything from radiator panels to fan • Ambient temp range: 34-104°F (at 34-200°F medium temperature) coil units and both normally open and normally closed spring • 3-way valve is diverting type return functions, it’s easy to select a model that fits your needs.
Fan Coil and Zone Valves Actuator O.S. Number Voltage Frequency Power (60 Hz) 2-Position SPST SPST Seconds @ 60 Hz, Driving Fail Safe Control Aux Switch Maximum Timing Fail Safe Action Electrical Connections Manual Override Nickel plated motors Valve Size (inches) f NPT Sweat f NPT Sweat f NPT Sweat f NPT Sweat Sweat f NPT Sweat f NPT f NPT Sweat f NPT Sweat Inverted Flare f NPT Sweat f NPT Sweat f NPT Sweat f NPT Sweat f NPT Sweat 1.0 Cv 1.0 Cv 2.5 Cv 2.5 Cv 3.5 Cv 3.5 Cv 3.5 Cv 3.5 Cv 5.0 Cv 8.0 Cv 8.
Cartridge Cage Valves Honeywell Cartridge Cage Valves family (VC Series) are highly serviceable and completely rebuildable. Select from 2-position (both low and line voltage), floating, and modulating actuators, and fail-safe actuators with configurable open/closed functionality on power failure depending on the application. Since these valves are not sensitive to flow direction; they can do both mixing and diverting without changing anything except the piping.
Cartridge Cage Valves Common Features • 2-way straight-through or 3-way mixing/diverting body configurations • Corrosion resistant, engineered plastic actuator housing • 60 psid close-off on all models • Fast acting 2-position actuator with soft close technology • Position indicator/manual override lever standard • Replaceable cartridge rebuilds valve to factory specifications without removing valve body from piping • 300 psi operating pressure • Combination position indicator/manual flush-and-fill ma
Cartridge Globe Valves For more than 50 years, Honeywell has manufactured the V58 series of premium Cartridge Globe Valves. The compact size and replacement capabilities make it a great choice for controlling modulating unitary equipment. Valves 1" and larger feature a pressure balanced design with enhanced close-off (levels). Common Features • Maximum static pressure 235 psi • Long stroke allows for a wide range of control • Leakage rate: 0.
Cartridge Globe Valves Actuator O.S. Number Power Supply Voltage Frequency Power Stem Force (lb.) Control 2-Position SPDT Floating 0(2)-10 Vdc 4-20 mA (external 500 Ohm resistor) Pneumatic Spring Range Fail Safe Action Stroke Timing Wiring Change DIP Switch Seconds @ 60 Hz (Drive) Fail Safe (Use valve dust cap) Manual Override Position Indicator Electrical Connection Cable length, in. Plenum-rated Cable Screw terminals 1/2 in.
Control Ball Valves ½- 3" 2-Way NPT NEMA 2 Honeywell's Control Ball Valve product lines Actuator Features (VBN and VBF) feature the largest Cv range in Actuator O.S. Number the industry. A patented seat design allows for Power Supply Non-fail Safe MN6105A1011 MN6105A1011 MN7505A2001 24 Vac 24 Vac 24 Vac 24 Vac 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz Power 5 VA 5 VA 5 VA 5 VA (lb.-in.
Control Ball Valves ½- 3" 2-Way NPT NEMA 2 Actuator Features Fail Safe Actuator O.S. Number Power Supply Voltage Frequency 50 / 60 Hz 50 / 60 Hz 7.5 VA 7.5 VA (lb.-in.
Control Ball Valves ½- 3" 2-Way NPT NEMA 3R Common Features Actuator Features • Max static pressure 360 psi (250°F) Non-fail Safe MN6105A1011 MN6105A1011 MN7505A2001 24 Vac 24 Vac 24 Vac 24 Vac 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz Power 5 VA 5 VA 5 VA 5 VA (lb.-in.) 44 44 44 44 (0)2-10 Vdc • • 4-20 mA (external 500 Ohm Resistor) • • Actuator O.S. Number • Medium: Water/glycol solutions up to 50%.
Control Ball Valves ½- 3" 2-Way NPT NEMA 3R Actuator Features Fail Safe Actuator O.S. Number Power Supply Voltage Frequency 50 / 60 Hz 50 / 60 Hz 7.5 VA 7.5 VA (lb.-in.
Control Ball Valves ½- 2½" 3-Way NPT NEMA 2 Common Features Actuator Features VBN3 (Three-way): Actuator O.S. Number • Equal % A to AB, linear B to AB Power Supply • Nickel-chrome plated brass ball and stem • Convert to 2-way by plugging B port (plug not provided) Non-fail Safe Voltage Frequency Actuator Torque Control MS7505A2030 24 Vac 24 Vac 24 Vac 24 Vac 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz Power 5 VA 5 VA 8 VA 7.5 VA (lb.-in.
Control Ball Valves ½- 2½" 3-Way NPT NEMA 3R Actuator Features Non-fail Safe Actuator O.S. Number Power Supply Voltage Frequency Actuator Torque Control MN7505A2001 MS8105A1030 MS7505A2030 24 Vac 24 Vac 24 Vac 24 Vac 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz Power 5 VA 5 VA 8 VA 7.5 VA (lb.-in.
Flanged Control Ball Valves 4"- 6" 2-Way Flanged NEMA 2+3R Common Features Actuator Features • Maximum static pressure 240 psi (-22°F to 250°F) • Medium: Water/glycol solutions up to 50% Non-fail Safe MN6110A1003 4 to 5 in. MN6134A1003 6 in. Actuator O.S. Number Power Supply Voltage Actuator Torque Control • ANSI class IV leakage (0.01% of Cv) 24 Vac 24 Vac 24 Vac 24 Vac 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz Power 5 / 9 VA 5 / 9 VA 30 / 40 VA 14 / 16 VA (lb.-in.
Flanged Control Ball Valves 4"- 6" 3-Way Flanged NEMA 2+3R Common Features • Mixing or diverting with the same 3-way valve Actuator Features Non-fail Safe MN6110A1003 4 to 5 in. MN6134A1003 6 in. Actuator O.S. Number • Globe valve A-B-AB flow pattern (side B port) Power Supply • Three-way: A-AB equal percentage, B-AB linear (80% of Cv on B-port) Actuator Torque Voltage Valve Only MS7510A2008 4 to 5 in. MS7520A2007 6 in.
NPT Globe Valves ½- 3" With Dedicated Valve Actuators For more than 50 years, Honeywell Globe Valves (V5011/13, VGF) have provided precise control for most applications. Power Supply ML6420A3056 Voltage 24 Vac / 28 Vdc 24 Vac / 28 Vdc 24 Vac 24 Vac 24 Vac 24 Vac 0 / 50 / 60 Hz 0 / 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz Power 12 VA 12 VA 7 VA 7 VA 6 VA 6 VA (lbs.) 160 160 135 135 135 135 •* •* Frequency Actuator Stem Force Control ML6420A3049 Actuator O.S.
NPT Globe Valves ½- 3" With Dedicated Valve Actuators Common Features • ANSI body class 150 • Close-off pressure = maximum differential pressure • Maximum steam pressure 2-way steam valves, 337°F: 100 psi 2-way water valves: 15 psi Actuator O.S. Number • Stem travel: 0.75" Power Supply Voltage • Leakage < 0.
NPT Globe Valves ½- 3" With Direct Coupled Actuators and Valve Linkage Common Features • ANSI body class 150 Q5020A1003 Required • Maximum static water pressure (250°F): 240 psi Actuator Features • Maximum steam pressure 2-way steam valves, 337°F: 100 psi 2-way water valves: 15 psi Actuator O.S. Number • Stem travel: 0.75" Power Supply Voltage Frequency • Rangeability: 50:1 • Leakage < 0.
NPT Globe Valves ½- 3" With Direct Coupled Actuators and Valve Linkage Q5020A1003 Required Power Supply Voltage Frequency Actuator Torque 24 Vac 24 Vac 24 Vac 24 Vac 24 Vac 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz 9 VA 5 VA 5 VA 6 VA 6 VA 9 VA 88 88 175 175 300 300 (lbs.
NPT Globe Valves ½- 3" With Direct Coupled Spring Return Actuators and Valve Linkage Common Features • ANSI body class 150 • Close-Off pressure = maximum differential pressure Q5020A1003 Required • Leakage < 0.05% of Cv Power Supply Voltage Frequency • Body material: Red brass, stainless steel stem (steam valve has stainless steel trim) Actuator Torque 24 Vac 24 Vac 100-250 Vac 24 Vac 24 Vac 50 / 60 Hz 50 / 60 Hz 60 Hz 50 / 60 Hz 50 / 60 Hz 30 VA Power 7.5VA 8 VA 11VA 14 VA (lb.-in.
NPT Globe Valves ½- 3" With Direct Coupled Spring Return Actuators and Valve Linkage Q5020A1003 Required MS8120A1007 MS8120A1205 MS4120A1001 MS4120A1209 24 Vac 24 Vac 100-250 Vac 60 Hz 50 / 60 Hz 50 / 60 Hz 60 Hz Power 45 VA 16 VA 40 VA 60 VA (lb.-in.) 88 175 175 175 (lbs.
Flanged Globe Valves 2½- 3" With Direct Coupled Actuators and Valve Linkage Common Features • ANSI body class 125 or 250 Actuator Features Non-fail Safe • Stem travel: 0.75" ML7174A2001 • Maximum steam pressure (V5011, 2-pos): 15 psi Actuator O.S.
Flanged Globe Valves 2½- 3" With Direct Coupled Actuators and Valve Linkage Q5020A1003 Required Power Supply Voltage Frequency MN6134A1003 24 Vac 24 Vac 24 Vac 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz Power 6 VA 6 VA 9 VA 9 VA (lb.-in.) 175 175 300 300 (lbs.
Flanged Globe Valves 2½- 3" With Direct Coupled Spring Return Actuators and Valve Linkage Common Features • ANSI body class 125 or 250 • Maximum static water pressure: Up to 400 psi Q5020A1003 Required • Maximum steam pressure (VGF, 2-pos or modulating): 100 psi Actuator Features • Close-off pressure = Maximum differential pressure Fail Safe MS8110A1008 MS4110A1002 • Stem travel: 0.
Flanged Globe Valves 2½- 3" With Direct Coupled Spring Return Actuators and Valve Linkage Q5020A1003 Required Fail Safe MS4120A1001 24 Vac 24 Vac 100-250 Vac 50 / 60 Hz 50 / 60 Hz 60 Hz Power 16 VA 40 VA 60 VA (lb.-in.) 175 175 175 (lbs.) 234 234 234 Actuator O.S.
Threaded and Flanged Globe Valves 2"- 3" With Tandem Direct Coupled Actuators and Valve Linkage Common Features • Stem travel: 0.
Threaded and Flanged Globe Valves 2"- 3" With Tandem Direct Coupled Actuators and Valve Linkage Q5022A1001 Required*** MS4120A1001 Voltage 24 Vac 24 Vac 100-250 Vac Frequency 60 Hz 60 Hz 60 Hz Power 16 VA 40 VA 60 VA (lb.-in.) 175 175 175 (lbs.) 655 655 655 Actuator O.S.
Flanged Globe Valves 2½- 3" With Dedicated Valve Actuators Common Features • ANSI body class 125 or 250 • Close-off pressure = Maximum differential pressure • Maximum static water pressure: Up to 400 psi • Maximum steam pressure (VGF, 2-pos or modulating): 100 psi Actuator O.S.
Flanged Globe Valves 2½- 3" With Dedicated Valve Actuators Power Supply Voltage Control ML6421A1017 24 Vac 24 Vac 24 Vac 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz Power 6 VA 6 VA 12 VA 11 VA (lb.-in.
Flanged Globe Valves 2½- 3" With Dedicated Valve Actuators Common Features • ANSI body class 125 or 250 • Close-off pressure = Maximum differential pressure • Maximum static water pressure: Up to 400 psi • Maximum steam pressure (VGF, 2-pos or modulating): 100 psi Actuator O.S. Number • Body material: Cast iron • Body trim: Stainless steel stem, brass seat (V5011/13), stainless steel (VGF) Power Supply Voltage ML6425A3022 • Rangeability: 50:1 ML7425A3013 • Stem travel: 0.
Notes & Numbers Valve Selection 51
Flanged Globe Valves 4"- 6" With Tandem Direct Coupled Actuators and Valve Linkage Common Features • Stem travel: 1.
Flanged Globe Valves 4"- 6" With Tandem Direct Coupled Actuators and Valve Linkage Q5022B1009 Required*** MS4120A1001 Voltage 24 Vac 24 Vac 100-250 Vac Frequency 60 Hz 60 Hz 60 Hz Power 16 VA 40 VA 60 VA (lb.-in.) 175 175 175 (lbs.) 325 325 325 Actuator O.S.
Flanged Globe Valves 4"- 6" With Dedicated Valve Actuators Common Features • ANSI body class 125 or 250 • Close-off pressure = Maximum differential pressure • Maximum static water pressure: Up to 400 psi • Maximum steam pressure (VGF, 2-pos or modulating): 100 psi • Maximum steam pressure (V5011, 2-pos): 15 psi • Stem travel: 1.5" Actuator Features • Rangeability: 50:1 Non-fail Safe ML7421B1023 Actuator O.S. Number • Leakage < 0.
Flanged Cage Valves 2½- 6" The V5051 series advantage lies in its ability to perform like a globe valve while achieving high closeoff pressures with a single spring return actuator. This premium valve delivers a high close-off using a single spring return actuator on all valves up to 6". It is highly suitable for medium-pressure steam applications. Common Features • Pressure balanced design for high close-off • Close-off pressure = Maximum differential pressure • ANSI body class 125 • Stem travel 1.
NPT Globe Valves ½- 3" With Pneumatic Actuators Common Features MP953D1172 MP953C1083 MP953D1131 MP953C1075 MP953D1107 MP953C1067 Direct / Reverse Acting DA / RA DA DA DA DA DA DA DA DA RA RA RA Diaphragm Size 5" 5" 5" 8" 8" 8" 13" 13" 7-1/8" 7-1/8" 7-1/8" Fail Safe Action Positioner MP953C1562 MP953C1026 • No positive positioner Actuator O.S.
NPT Globe Valves ½- 3" With Pneumatic Actuators Chart A 0 (0) 4 (30) CV .73 TO 2.9 CV 4.7 5 (35) C 7 V .3 3 (20) C V 11.7 C V 18 . 7 2 (15) 1 (10) 0 (0) 5 (35) 3 (20) 7 (50) 2 (15) 6 (40) 1 (10) 5 (35) 0 (0) 4 (30) CV .73 TO 2.9 CV 7.3 CV 11.
NPT Globe Valves ½- 3" With Pneumatic Actuators Common Features DA DA DA DA DA DA RA RA RA\ 5" 5" 8" 8" 8" 13" 13" 7-1/8" 7-1/8" 7-1/8" Positioner Stem Up Stem Up Stem Up Stem Up Stem Up Stem Up Stem Up Stem Up Stem Down Stem Down Stem Down 10psi span • 5psi span Straight Through Straight Through Mixing 3-Way Water Valves 2-Way Steam Valves 2-Way Water Valves 3psi span Valve Size (inches) Cv 1/2" 3/4" 1" 1-1/4" 1/2" 1/2" 1/2" 1/2" 1/2" 3/4" 1" 1-1/4" 1-1/2" 2" 2-1/2" 3" 1/2" 1/
NPT Globe Valves ½- 3" With Pneumatic Actuators Chart A 0 (0) 4 (30) CV .73 TO 2.9 CV 4.7 5 (35) C 7 V .3 3 (20) C V 11.7 C V 18 . 7 2 (15) 1 (10) 0 (0) 5 (35) 3 (20) 7 (50) 2 (15) 6 (40) 1 (10) 5 (35) 0 (0) 4 (30) CV .73 TO 2.9 CV 7.3 CV 11.
Flanged Globe Valves 2½- 3" With Pneumatic Actuators Common Features • Rolling diaphragm for long life and low hysteresis • Easily installation and attachment to the valve • Direct or reverse acting • No positive positioner MP953D1131 MP953D1172 DA DA DA DA RA RA RA 8" 8" 8" 13" 13" MP953C1554 DA 7-1/8" 7-1/8" 7-1/8" Stem Stem Stem Up Stem Up Stem Up Stem Up Stem Up Stem Down Down Down Fail Safe Action Positioner MP953D1107 DA / RA Diaphragm Size MP953C1562 Direct / Reverse Acting
Flanged Globe Valves 2½- 3" With Pneumatic Actuators Chart M Chart L Chart N SPRING RANGE 1 PSI (kPa) SIZE 2-1/2 IN. AND 3 IN. WITH 8 IN. D.A. PNEUMATIC ACTUATOR (NORMALLY OPEN PORTS B TO AB) 11 (76) 15 (103) 16 (110) 12 (83) 16 (110) 17 (117) 13 (90) 17 (117) 18 (124) 14 (96) 18 (124) 19 (131) 15 (103) 19 (131) 20 (138) 16 (110) 20 (138) 21 (144) 1 17 (117) 21 (144) 22 (152) USE 4-11 PSI (30-75 kPa) RANGE FOR DETERMINING CLOSEOFF OF VALVES USED WITH MP953E ACTUATORS.
Flanged Globe Valves 2½- 3" With Pneumatic Actuators Common Features • Rolling diaphragm for long life and low hysteresis • Easily installation and attachment to the valve • Direct or reverse acting • Integrated positive positioner Fail Safe Action Positioner MP953F1119 DA DA DA DA DA RA RA RA\ 8" 8" 8" 13" 13" 7-1/8" 7-1/8" 7-1/8" Stem Stem Stem Stem Up Stem Up Stem Up Stem Up Stem Up Down Down Down 10psi span • • • 5psi span 3-Way Water Valves 2-Way Water & Steam Valves 3psi span Va
Flanged Globe Valves 2½- 3" With Pneumatic Actuators Chart L Chart N SPRING RANGE 1 PSI (kPa) SIZE 2-1/2 IN. AND 3 IN. WITH 8 IN. D.A. PNEUMATIC ACTUATOR (NORMALLY OPEN PORTS B TO AB) 11 (76) 15 (103) 16 (110) 12 (83) 16 (110) 17 (117) 13 (90) 17 (117) 18 (124) 14 (96) 18 (124) 19 (131) 15 (103) 19 (131) 20 (138) 16 (110) 20 (138) 21 (144) 1 17 (117) 21 (144) 22 (152) USE 4-11 PSI (30-75 kPa) RANGE FOR DETERMINING CLOSEOFF OF VALVES USED WITH MP953E ACTUATORS.
Flanged Globe Valves 4"- 6" With Pneumatic Actuators Common Features • Rolling diaphragm for long life and low hysteresis • Easily installation and attachment to the valve • Direct or reverse acting MP953E1285 MP953E1400 MP953E1418 Diaphragm 13" 13" 8" 8" 13" 13" Action DA DA DA DA DA DA 4-11psi 4-11psi 2-7psi 4-11psi 3-15psi 4-11psi Positioner Span n/a Stroke 2-Way Water & Steam Valves 4" 5" 6" 3-Way Water Valves 4" 5" 6" Cv Valve Type 160 160 150 150 150 155 150 250 25
Flanged Globe Valves 4"- 6" With Pneumatic Actuators Chart V Chart W 17 (120) 14 (95) 18 (125) 15 (105) C v = 16 0 4-11 (30-75) 13 (90) 2-7 (15-50) 4-11 (30-75) 16 (110) AIR PRESSURE IN ACTUATOR PSI (kPa) 2-7 (15-50) 12 (85) 0 (0) 2 (15) C V = 16 0 C V = 1 (10) 0 (0) 5 (35) 10 (70) 15 20 (105) (140) 25 30 (170) (205) 35 40 (240) (275) 0 (0) 45 55 50 60 (310) (345) (380) (515) 5 (35) CLOSEOFF PRESSURE RATINGS PSI (kPa) 1 0 10 (70) Chart O 23 (159) 20 (138) 24 (165) 21 (1
Resilient Seat Butterfly Valves 2-Way Electrically-Actuated Control Honeywell Resilient Seat Butterfly Valves family (VFF) offers options in sizes 2" to 20", highlighted with an industry unique tandem mount using Honeywell direct coupled actuators on valves up to 8" size. Common Features • Honeywell direct coupled actuators up to 8" size Actuator Features Non-fail Safe Floating Modulating Actuator O.S.
Resilient Seat Butterfly Valves 2-Way Electrically-Actuated Control Actuator Features Fail Safe Actuator O.S.
Resilient Seat Butterfly Valves 3-Way Electrically-Actuated Control Common Features Actuator Features • VFF3 – A-B-AB porting, full-cut (150175 psid close-off) or under-cut disc (50 psid close-off) • Honeywell direct coupled actuators up to 6" size • Mixing or diverting control • Standard right-angle cast-iron T-pipe • A-port configured to closed position at factory • Porting pattern field-configurable with valve linkage adjustment P N.C. A AB B S N.O.
Resilient Seat Butterfly Valves 3-Way Electrically-Actuated Control Actuator Features Fail Safe Actuator O.S. Number Power Supply Voltage Frequency Power (* tandem mount) Actuator Torque lb.-in.
Resilient Seat Butterfly Valves 3-Way Electrically-Actuated Control Common Features Actuator Features • VFF6 – A-AB-B porting, full-cut (150175 psid close-off) or under-cut disc (50 psid close-off) • Honeywell direct coupled actuators up to 6" size • Mixing or diverting control • Standard right-angle cast-iron T-pipe • A-port configured to closed position at factory • Porting pattern field-configurable with valve linkage adjustment P N.C. A B AB S N.O.
Resilient Seat Butterfly Valves 3-Way Electrically-Actuated Control Actuator Features Fail Safe Actuator O.S. Number Power Supply Voltage Frequency Power (* tandem mount) Actuator Torque lb.-in.
Resilient Seat Butterfly Valves 2-Way Pneumatically-Actuated Control Common Features Honeywell offers a wide selection of pneumatic actuators: • 20 psi spring return (up to 10" size) • 80 psi spring return Actuator Features • 80 psi double acting bi-directional Actuator Configurable with accessories: Standard Power Supply Voltage Frequency Power Control Modulating Pneumatic 2-Position 4-20 mA Auxiliary Switch Add-On Manual Override Conduit Connection Waterproof Fail Safe • Positioner • Electro-pneuma
Resilient Seat Butterfly Valves 2-Way Pneumatically-Actuated Control Actuator Features Fail Safe 20 psi Actuator 8-13 spring Positioner Actuator Standard Power Supply 2-Way Normally Open 2-Way Normally Closed Valve Size (inches) Cv @ 60° Cv @ 90° 2" 2 1/2" 3" 61 107 154 144 282 461 4" 274 841 5" 428 1376 6" 567 1850 8" 1081 3316 10" 1710 5430 12" 2563 8077 14" 3384 10538 16" 4483 13966 18" 5736 17214 20" 7144 22339 Valve Size (inches) Cv @ 60° Cv @ 90° 2" 2 1/2"
Resilient Seat Butterfly Valves 3-Way Pneumatically-Actuated Control Common Features Honeywell offers a wide selection of pneumatic actuators: • VFF3 – A-B-AB porting, full-cut (150-175 psid close-off) or under-cut disc (50 psid close-off) (Figure 1 - from 63-2661-02 fig. 12) Actuator Features Actuator • VFF6 – A-AB-B porting, full-cut (150-175 psid close-off) or under-cut disc (50 psid close-off) (Figure 2 - from 63-2661-02 fig.
Resilient Seat Butterfly Valves 3-Way Pneumatically-Actuated Control Actuator Features Fail Safe 20 psi Actuator 8-13 spring Positioner Actuator Standard Power Supply 3-Way Mixing / Diverting Globe Valve Porting 3-Way Mixing / Diverting Center Common Port Valve Size (inches) Cv @ 60° Cv @ 90° 2" 2 1/2" 3" 61 107 154 144 282 461 4" 274 841 5" 428 1376 6" 567 1850 8" 1081 3316 10" 1710 5430 12" 2563 8077 14" 3384 10538 16" 4483 13966 18" 5736 17214 20" 7144 22339 Val
Section 3: Submittal Sheets Unitary Valve Actuator VU443; VU444; VU843; VU844...........................................115 VC Series Two-position........................................................116 VC Series Proportional.........................................................117 VC Series Fail Safe Proportional...........................................118 M6410; M7410....................................................................119 M6435; M7435................................................
Rectangular Volume Control Dampers D1 D1Series Series The D1 series is an extremely low leakage damper with rugged steel airfoil blades designed to meet the highest standards established. It is intended for application in medium to high pressure and velocity ratings. Performance Data D1 Pressure and Velocity Limits. Damper Size in in. 12 x 12 24 x 24 36 x 36 48 x 48 60 x 60 Maximum System Pressure 8.0 in. wg 8.0 in. wg 6.3 in. wg 4.7 in. wg 2.0 in.
Rectangular Volume Control Dampers D2 D2and andD3 D3Series Series Honeywell International, Inc. certifies that the models D2, and D3 shown herein are licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Programs. The AMCA Certified Ratings Seal applies to air performance ratings only. March 2008.
Round Volume Control Dampers D690 D690 The D690 Round Damper is used in conventional air handling systems to control airflow in a round duct. The damper is designed for use with Honeywell ML6161 and ML7161 Direct Coupled Actuators. SPECIFICATIONS FEATURES • Neoprene seal for tight closing and low leakage • Oilite™ bearings for long life • 90 degree damper travel for a variety of applications DIMENSIONS DIAGRAM Application .........................................
Round Volume Control Dampers DM7600 DM7600 The DM7600 Commercial Zone Damper is used in zoning systems to control airflow in a round duct. A Honeywell ML6161 or ML7161 Direct Coupled Actuator is factory mounted to the damper to simplify field installation.
Spring Return Direct Coupled Actuator S03 MS7503;MS8103) MS8103) S03Series Series (MS4103; (MS4103; MS7403; MS7403; MS7503; MS4103, MS7403, MS7503, MS8103 Spring Return Direct Coupled Actuators (DCA) are used within heating, ventilating, and airconditioning (HVAC) systems. They can drive a variety of quarter-turn, final control elements requiring spring return fail-safe operation. SPECIFICATIONS Actuator Type ....................................... Damper, Valve Rotational Stroke ..........................
Spring Return Direct Coupled Actuator S05S05 Series (MS4105; MS7105; MS7405; Series (MS4105; MS7105; MS7405;MS7505; MS7505;MS8105) MS8105) MS4105, MS7405, MS7505, MS8105 Spring Return Direct Coupled Actuators (DCA) are used within heating, ventilating, and airconditioning (HVAC) systems. They can drive a variety of quarter-turn, final control elements requiring spring return fail-safe operation.
Spring Return Direct Coupled Actuator S10 MS8110) S10Series Series (MS4110; (MS4110; MS7510; MS7510; MS8110) MS4110, MS7510, MS8110 S10 Series Spring Return Direct Coupled Actuators (DCA) are used within heating, ventilating, and airconditioning (HVAC) systems. They can drive a variety of quarter-turn, final control elements requiring spring return fail-safe operation. SPECIFICATIONS Actuator Type ....................................... Damper, Valve Rotational Stroke ..................................
Spring Return Direct Coupled Actuator S20 Series S20 Series(MS4120; (MS4120;MS7520; MS7520;MS8120) MS8120) MS4120, MS7520, MS8120 Spring Return Direct Coupled Actuators (DCA) are used within heating, ventilating, and air-conditioning (HVAC) systems. They can drive a variety of quarter-turn, final control elements requiring spring return fail-safe operation. SPECIFICATIONS DIMENSIONS DIAGRAMS 3-15/16 (100) 1-9/16 (40) submittal Sheets Actuator Type .......................................
Spring Return Direct Coupled Actuator ML4125; ML4125; ML8125 ML8125 The ML8125 Fast-Acting, TwoPosition Actuators are spring return direct coupled actuators (DCA) with an integral junction box for on/off damper control. SPECIFICATIONS Actuator Type ....................................... Damper Rotational Stroke .................................. 95 ±3 degrees Fail Safe Mode ..................................... Spring Return Rated Torque ........................................ 100 lb-in. (11.
Spring Return Direct Coupled Actuator ML4135; ML4135;ML8135 ML8135 The ML8135 Fast-Acting, TwoPosition Actuators are spring return direct coupled actuators (DCA) with an integral junction box for on/ off damper control. SPECIFICATIONS DIMENSIONS DIAGRAMS 2 (51) 1 (25) 5/8 (17) 1 6 3/8 (161) 7 1/2 (192) 4 (102) 2 (51) submittal Sheets Actuator Type ....................................... Damper Rotational Stroke .................................. 95 ±3 degrees Fail Safe Mode ........................
Non-Spring Return Direct Coupled Actuator ML6161; ML6161; ML7161 ML7161 Used to control dampers in applications such as variable air volume (VAV) terminal units and for mounting on ball valves; suitable for use with SPDT or floating thermostats or building automation controls. SPECIFICATIONS Actuator Type ....................................... Damper Rotational Stroke .................................. 90 degrees Fail Safe Mode ..................................... Non-Spring Return Rated Torque .........
Non-Spring Return Direct Coupled Actuator ML6174; ML6174;ML7174 ML7174 Used to control dampers in applications such as variable air volume (VAV) terminal units and for mounting on ball valves; suitable for use with SPDT or floating thermostats or building automation controls.
Non-Spring Return Direct Coupled Actuator N05 MN7505) N05Series Series (MN6105; (MN6105; MN7505) This non-spring return directcoupled damper actuator provides modulating and floating/2-position control for: air dampers, VAV units, air handlers, ventilation flaps, louvers, and reliable control for air damper applications with up to 10 sq. ft./ 44lb.-in. (5 Nm) and 20 sq. ft./88 lb.-in. (10 Nm) (sealless damper blades; air frictiondependent). SPECIFICATIONS Actuator Type .....................................
Non-Spring Return Direct Coupled Actuator N10 Series N10 Series(MN6110; (MN6110;MN7510) MN7510) This non-spring return directcoupled damper actuator provides modulating and floating/2-position control for air dampers, VAV units, air handlers, ventilation flaps, louvers, and reliable control for air damper applications with up to 20 sq ft/88 lb-in. (10 Nm) (seal-less damper blades; air frictiondependent).
Non-Spring Return Direct Coupled Actuator N20 MN7220) N20Series Series (MN6120; (MN6120; MN7220) SPECIFICATIONS Actuator Type ....................................... Damper; Valve Rotational Stroke .................................. 95 ±3 degrees Fail Safe Mode ..................................... Non-Spring Return Rated Torque ........................................ 175 lb-in. (20 Nm) External Auxiliary Switches Available .. Yes, SW2-US Electrical Connections .........................
Non-Spring Return Direct Coupled Actuator N34 Series N34 Series(MN6134; (MN6134;MN7234) MN7234) SPECIFICATIONS DIMENSIONS DIAGRAMS SHAFT ADAPTER 3-15/16 (100) SHAFT ADAPTER (REVERSED) 95° 1-3/16 (20.6) 8-25/32 (223) 3-5/8 (92) MIN 2-3/8 (60) submittal Sheets Actuator Type ....................................... Damper; Valve Rotational Stroke .................................. 95 ±3 degrees Fail Safe Mode ..................................... Non-Spring Return Rated Torque ........................
Fire And Smoke Actuator ML4115; ML4115; ML8115 ML8115 Spring return direct coupled actuators (DCA) for on/off damper control with an integral junction box. The actuator accepts an on/off signal from a single-pole, singlethrow (SPST) controller. They are designed to operate reliably in smoke control systems requiring Underwriter's Laboratories Inc. UL555S ratings up to 350 F. SPECIFICATIONS Actuator Type ....................................... Damper Rotational Stroke ..................................
Fire And Smoke Actuator MS4209F; MS4309F; MS4709F; MS4809F; MS4209F; MS4309F; MS4709F; MS4809F;MS8209F; MS8209F;MS8309F MS8309F Spring return direct coupled actuators (DCA) for on/off damper control with an integral junction box. The actuator accepts an on/off signal from a single-pole, single-throw (SPST) controller. They are designed to operate reliably in smoke control systems requiring Underwriter's Laboratories Inc. UL555S ratings up to 350 F. APPROVALS CE .............................................
Fire And Smoke Actuator MS4120F; MS8120F MS4120F; MS4620F; MS4620F; MS8120F Spring return direct coupled actuators (DCA) for on/off damper control with an integral junction box. The actuator accepts an on/off signal from a single-pole, singlethrow (SPST) controller. They are designed to operate reliably in smoke control systems requiring Underwriter's Laboratories Inc. UL555S ratings up to 350 F. SPECIFICATIONS Actuator Type ....................................... Damper Rotational Stroke .................
Pneumatic Damper Actuator MP909D MP909D Used for pneumatic proportional control of variable volume terminal units and small dampers. Available in various operating ranges for either individual or sequence operation with other actuators. Replacement devices are available for Johnson, Powers, Robertshaw, and older Honeywell actuator models. SPECIFICATIONS Actuator Type ....................................... Damper Actuator Force ...................................... Low Fail Safe Mode .....................
Pneumatic Damper Actuator MP909E,H MP909E,H These actuators are used for proportional control of variable volume terminal units, mixing boxes, and small to medium sized dampers. They are available in various operating ranges for either independent operation or sequence operation with other actuators. The MP909E has an optional adjustable stroke feature. The MP909H includes a positive positioner.
Pneumatic Damper Actuator MP913 MP913 Provides proportional control of variable volume dampers in small high velocity mixing boxes. Replacement devices are available for Johnson and Robertshaw devices. Suitable for direct replacement only, do not attempt to replace larger damper actuators with this unit. FEATURES • Compact in size. • Neoprene rolling diaphragm. • The MP913 Operator can be used with or without a crankarm. SPECIFICATIONS Actuator Type .......................................
Pneumatic Damper Actuator MP918A,B MP918A,B Used for proportional control of medium- to large-size dampers in HVAC systems. The MP918A,B are rolling diaphragm, piston-type actuators. The MP918A has a positive positioner. Replacement devices are available for Johnson, Powers, Robertshaw, BarberColman, and older Honeywell actuator models. SPECIFICATIONS Actuator Type ....................................... Damper Actuator Force ..................................... High Fail Safe Mode .......................
Pneumatic Damper Actuator MP920 MP920 Provides proportional control of large dampers in HVAC systems or inlet vanes on a VAV fan. Positive positioner available separately. Replacement devices are available for Robertshaw actuator models. SPECIFICATIONS FEATURES • Rolling diaphragm operated. • Fail safe on over pressure. • Actuator can be swivel mounted from either end to pipe, floor, or wall surface. • Optional positive positioner provides accurate positioning under varying load conditions.
Pneumatic Valve Actuator MP953C,D MP953C,D Pneumatic actuators provide proportional control of steam or hot or cold liquids in HVAC systems by operating V5011, V5013, and VGF valve assemblies. Replacement devices are available for older Honeywell actuators. SPECIFICATIONS Actuator Type ....................................... Valve Action ................................................... Direct Acting Actuator Force ..................................... Medium Fail Safe Mode ..............................
Pneumatic Valve Actuator MP953E,F MP953E,F Pneumatic actuators provide proportional control of steam or hot or cold liquids in HVAC systems by operating V5011, V5013, and VGF valve assemblies. Replacement devices are available for older Honeywell actuators. SPECIFICATIONS Actuator Type ....................................... Valve Action ................................................... Direct Acting Actuator Force ...................................... Low Fail Safe Mode ................................
Pneumatic Valve Actuator MP958 MP958 The MP958 Pneumatic Valve Actuator is direct-acting and used only with Honeywell V5852A2xx, V5862A2xx, V5853A2xx, and V5863A2xx Terminal Unit Valves to control hot and/or chilled water. SPECIFICATIONS Actuator Type ....................................... Valve Action ................................................... Direct Acting Actuator Force ..................................... Low Fail Safe Mode .....................................
Modutrol IV Motor M4185; M4185;M8185 M8185 Series 41 and Series 81 Modutrol IV motors are 2-position (line- and low-voltage per motor control) spring-return motors. They are used to operate dampers or valves in applications where it is necessary or desirable to have the controlled element return to the starting position in the event of power failure or interruption.
Modutrol IV Motor M6184; M6184; M6194 M6194 Series 61 Modutrol IV™ Motors non-spring return floating control motors used with controllers that provide a switched SPDT or floating output to operate dampers or valves. SPECIFICATIONS Application Type .................................. Damper; Valve Fail Safe Mode ..................................... Non-Spring Return Control Signal ....................................... Floating Torque/Force ........................................ 75 lb-in. (8.
Modutrol IV Motor M6285 for for slaving applications M6285 slaving applications Series 62 Modutrol IV™ Motors are spring return floating control motors used with controllers that provide a switched SPDT or floating output to operate dampers or valves. These motors also have an internal electrically isolated feedback potentiometer that provides indication of the motor shaft position and can be used for slaving Series 90 motors or rebalancing an external control circuit.
Modutrol IV Motor M6284; slavingapplications applications M6284; M6294 M6294 for for slaving These Series 62 Modutrol IV™ Motors non-spring return floating control motors are used with controllers that provide a switched SPDT or floating output to operate dampers or valves. These motors also have an internal electrically isolated feedback potentiometer that provides indication of the motor shaft position. Some models can be used for slaving Series 90 Motors. SPECIFICATIONS Application Type ................
Modutrol IV Motor M6274; M6284; M6285; M6294 Motors with Linear 10K M6274; M6284; M6285; M6294 Motors with Linear 10KFeedback Feedback Series 62 Modutrol IV™ Motors spring return and non-spring return floating control motors used with controllers that provide a switched SPDT or floating output to operate dampers or valves. These motors also have an internal electrically isolated feedback potentiometer that provides indication of the motor shaft position.
Modutrol IV Motor M7164 M7164 Series 71 Modutrol IV™ Motors non-spring return motors used to control dampers and valves. These motors accept a voltage signal from an electronic controller to position a damper or valve at any point between open and closed. FEATURES • Integral junction box provides NEMA 3 weather protection if motor is mounted in the upright position. • Motor and circuitry operate from 24 Vac. • Quick-connect terminals are standard--screw terminal adapter is available.
Modutrol IV Motor M7274; M7284; M7285; M7274; M7284; M7285;M7286; M7286;M7294 M7294 The Series 72 Modutrol IV Motors spring return and non-spring return motors are used to control dampers and valves. The motors accept a current or voltage signal from an electronic controller to position a damper or valve at any point between open and closed.
Modutrol IV Motor M9164; M9182; M9184; M9184;M9194 M9194 M9164; M9174; M9174; M9182; Series 90 Modutrol IV™ Motors non-spring return modulating proportional control motors used with controllers that provide a Series 90 output to operate dampers or valves. SPECIFICATIONS Application Type .................................. Damper Fail Safe Mode ..................................... Non-Spring Return Control Signal ....................................... Proportional, 135 ohm Torque/Force ....................
Modutrol IV Motor M9175; M9175;M9185; M9185;M9186 M9186 Series 90 Modutrol™ IV Motors spring return modulating proportional control motors used with controllers that provide a Series 90 output to operate dampers or valves. SPECIFICATIONS DIMENSIONS DIAGRAM TOP VIEW 4-7/8 (124) 5-1/2 (140) 13/16 (20) 1/4 (7) 2 3 APPROVALS 4-1/16 (103) 13/16 (20) 1-1/2 (37) 4-1/16 (103) 1-1/2 (37) Canadian Standards Association ......... Certified: File No. LR1620, Guide No. 400-E Underwriters Laboratories, Inc. .
Modutrol IV Motor Q7130; Q7130;Q7230; Q7230; Q7330 Q7330 For converting Series 90 Modutrol IV motors to Series 70 (electronic) control. SPECIFICATIONS Application Type .................................. Damper Dimensions, Approximate .................... Fits inside wiring junction box of Modutrol IV Motor Control Signal ....................................... Provides selectable voltage ranges: 4 to 7, 6 to 9, or 10.5 to 13.5 Vdc. Adapts M91XX to function as M71XX model Electrical Connections ............
Unitary Valve Actuator VU443, VU444; VU843; VU844 VU443, VU444; VU843; VU844 The VU844 Fan Coil Valve Actuators are used in conjunction with the VU52, VU53 and VU54 valves for controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectors. These valves are humidity resistant and are suitable for use in condensing, noncorrosive environments. FEATURES • Compact construction for easy installation.
Unitary Valve Actuator VC Actuators VCSeries Series Two-position Two-position Actuators Control central heating and/or cooling systems, fan coil systems, radiators and convectors. Depending on the model selected, it can be controlled by either a low or line voltage SPST controller such as a room thermostat. SPECIFICATIONS Actuator Type ....................................... Valve Control Signal ....................................... 24 Vac, 100-130 Vac, or 200-240 Vac Fail Safe Mode .....................
Unitary Valve Actuator VC VC Series Proportional Actuators Series Proportional Actuators Control central heating and/or cooling systems, fan coil systems, radiators and convectors. Depending on the model selected, it can be controlled by either a low or line voltage SPST or SPDT or floating controller such as a room thermostat, Aquastat control, flow switch or a 0/2 to 10 Vdc controller. FEATURES • Use with two-way or three-way valves. • Minimal actuator power consumption. • Double insulated actuator.
Unitary Valve Actuator VC ProportionalActuators Actuators VCSeries SeriesFail Fail Safe Safe Proportional Control central heating and/or cooling systems, fan coil systems, radiators and convectors. Depending on the model selected, it can be controlled by either a low or line voltage SPST or SPDT or floating or modulating controller such as a room thermostat, Aquastat control, flow switch or a 0/ 2 to 10 Vdc controller. SPECIFICATIONS Actuator Type .......................................
Unitary Valve Actuator M6410; M6410;M7410 M7410 Cartridge Globe Valve Actuator are small electric actuators for individual room control that provide floating or modulating control of V5852, V5862 two-way or V5853, V5863 three-way valves. SPECIFICATIONS DIMENSIONS DIAGRAM 2-5/16 (58) 3-15/16 (100) 1/2 (13) 1-15/16 (49) 2-3/8 (61) M8225A submittal Sheets Actuator Type ....................................... Valve Control Signal .......................................
Unitary Valve Actuator M6435; M6435; M7435 M7435 Cartridge Globe Valve Spring Return Actuators are small electric actuators for individual room control that provide floating or modulating control of 1/2 and 3/4 in. V5852, V5862 two-way or V5853, V5863 three-way valves. SPECIFICATIONS Actuator Type ....................................... Valve Control Signal ....................................... Floating; 0-10 Vdc or 2-10 Vdc modulating Fail Safe Mode .....................................
Direct Coupled Valve Actuator ML6420; ML6420;ML7420 ML7420 Direct Coupled Globe Valve Actuators provide floating or modulating control of chilled water, hot water, or steam, and mount directly on VGF series, V5011, and V5013 globe valves from 1/2 to 3 in. SPECIFICATIONS DIMENSIONS DIAGRAM 5-5/15 6-5/16 x (135) (161) 12-11/16 (322) MINIMUM CLEARANCE 2-11/16 (67) 9-3/16 (233) 9-9/16 (242) 1/2 (13) FPT submittal Sheets Actuator Type ....................................... Valve Control Signal ..........
Direct Coupled Valve Actuator ML6421; ML7421 ML6421; ML7421 Direct Coupled Globe Valve Actuators provide floating or modulating control of chilled water, hot water, or steam, and mount directly on VGF series, V5011, and V5013 valves. These Non-Spring Return Actuators will operate 1/2 to 6 in. valves. SPECIFICATIONS Actuator Type ....................................... Valve Control Signal ....................................... Floating; 0-10 Vdc or 2-10 Vdc modulating Fail Safe Mode .....................
Direct Coupled Valve Actuator ML6425; ML6425;ML7425 ML7425 Direct Coupled Globe Valve Actuators provide floating and modulating control of chilled water, hot water, and steam, and mount directly on VGF series, V5011, and V5013 globe valves. These Spring Return Actuators will operate 1/2 to 3 in. valves. SPECIFICATIONS DIMENSIONS DIAGRAM 5-5/15 6-5/16 x (135) (161) 14-5/16 (364) MINIMUM CLEARANCE 2-11/16 (67) 11-1/4 (284) 1/2 (13) FPT submittal Sheets Actuator Type ...................................
Direct Coupled Valve Actuator ML6984 ML6984 The ML6984 is a self-contained, self-adjusting, motorized linkage that mounts directly onto V5011 two-way or V5013 three-way valves and provides up to 25 mm (1 in.) of linear travel (stem lift). For use with low voltage 3-wire SPDT Series 20 (on-off); Series 60 (floating) electromechanical (dry contacts); or electronic (triac output) controllers. SPECIFICATIONS Actuator Type ....................................... Valve Control Signal .............................
Direct Coupled Valve Actuator ML7984 ML7984 The ML7984 is a self-contained, selfadjusting, motorized linkage that mounts directly onto V5011 two-way or V5013 three-way valves and provides up to 25 mm (1 in.) of linear stem travel. For use with Series 70 2-10Vdc, 4-20mA; Series 90 135 ohm; and Electronic (Super Mod) modulating signals controllers.
Unitary Valve VU52; VU52;VU53 VU53 Two-way Fan Coil Valves, the VU53 high pressure zone valves are used to control the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectors. FEATURES • Compact construction for easy installation. • Fits under the cover of most baseboard convectors with actuator fitted to valve body. • VU52 and VU53 provide 2-way, straight-through control of water.
Unitary Valve VU54 VU54 Three-way Fan Coil Valve, the VU54 high pressure zone valves are used to control the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectors. FEATURES • Compact construction for easy installation. • Fits under the cover of most baseboard convectors with actuator fitted to valve body. • VU54 provides three-way diverting control of water. • 300 psi (2,000 kPa, PN20) operating pressure rating.
Unitary Valve VCZA; VCZA;VCZB VCZB Two-way Cartridge Cage Valves are intended for hydronic applications in a normal indoor environment to control the flow of hot water or chilled water glycol solution to 60% concentration. These valves are designed for zone control of heating/cooling systems, or to control individual fan coil, baseboard radiator or convector applications.
Unitary Valve VCZM; VCZM;VCZN VCZN Three-way Cartridge Cage Valves are intended for hydronic applications in a normal indoor environment to control the flow of hot water or chilled water glycol solution to 60% concentration. These valves are designed for zone control of heating/cooling systems, or to control individual fan coil, baseboard radiator or convector applications.
Unitary Valve V5852; V5852;V5862 V5862 Two-way Cartridge Globe Valves control hot and/or chilled water for VAV terminal units, fan coil units, small reheaters and recoolers in electric/electronic temperature control systems. Used with the M6410 3-position floating NonSpring Return Valve Actuator and the M7410 selectable 0 to 10 Vdc or 2 to 10 Vdc Non-Spring Return Actuator. The 1/2 and 3/4 in.
Unitary Valve V5853; V5853;V5863 V5863 Three-way Cartridge Globe Valves control hot and/or chilled water for VAV terminal units, fan coil units, small reheaters and recoolers in electric/ electronic temperature control systems. Used with the M6410 3-position floating NonSpring Return Valve Actuator and the M7410 selectable 0 to 10 Vdc or 2 to 10 Vdc Non-Spring Return Actuator. The 1/2 in. and 3/4 in.
Control Ball Valve VBN2 VBN2 The VBN2 Two-Way Control Ball Valves control hot and chilled water with glycol solutions up to 50% in heating, ventilating, and air conditioning (HVAC) systems to provide two-position or modulating functions. These valve assemblies can be ordered with or without factory-mounted non-spring return or spring return direct-coupled actuators (DCA). SPECIFICATIONS Valve Type ............................................ Control Ball Valve Body Pattern .................................
Control Ball Valve VBN3 VBN3 The VBN3 Three-Way Control Ball Valves control hot and chilled water with glycol solutions up to 50% in heating, ventilating, and air conditioning (HVAC) systems to provide two-position or modulating functions. These valve assemblies can be ordered with or without factory-mounted non-spring return or spring return direct-coupled actuators (DCA). SPECIFICATIONS Valve Type ............................................ Control Ball Valve Body Pattern ...............................
Control Ball Valve VBF2 VBF2 The VBF2 Two-Way Ball Valve Assemblies, with and without actuators, control hot and chilled water with glycol solutions up to 50% in heating, ventilating, and air conditioning (HVAC) systems to provide two-position or modulating functions. These valve assemblies can be ordered with or without factory-mounted non-spring return or spring return direct-coupled actuators (DCA). SPECIFICATIONS Valve Type ............................................ Control Ball Valve Body Pattern ..
Control Ball Valve VBF3 VBF3 The VBF3 Three-Way Ball Valve Assemblies, with and without actuators, control hot and chilled water with glycol solutions up to 50% in heating, ventilating, and air conditioning (HVAC) systems to provide two-position or modulating functions. These valve assemblies can be ordered with or without factory-mounted non-spring return or spring return direct-coupled actuators (DCA). SPECIFICATIONS DIMENSIONS DIAGRAM AB PORT submittal Sheets Valve Type .............................
NPT Globe Valve V5011F,G V5011F,G Used for two-position or modulating control of steam and water and glycol solutions (to 50 percent concentration) in heating or cooling systems. SPECIFICATIONS Valve Type ............................................ Globe Valve Body Pattern ........................................ Two-way Valve Action ......................................... Stem down to close Connection Type .................................. NPT Female Controlled Medium ...............................
NPT Globe Valve V5011N V5011N Used for two-position or modulating control of steam and water and glycol solutions (to 50 percent concentration) in heating or cooling systems. SPECIFICATIONS DIMENSIONS DIAGRAM Y1 Y1,2 Y2 B submittal Sheets Valve Type ............................................ Globe Valve Body Pattern ........................................ Two-way Connection Type .................................. NPT Female Controlled Medium ...............................
NPT Globe Valve V5013N V5013N The V5013N is a three-way threaded globe valve that controls hot water, cold water, and glycol solutions (up to 50 percent concentration) in heating or cooling HVAC applications. The valves are used for mixing service to direct flow from one or two inlets to a common outlet in two-position or modulating control systems. FEATURES • Red brass body with NPT-threaded connections. • Stainless steel stem and brass plug. • Low seat leakage rating, < 0.05%.
Flanged Cage Valve V5051A V5051A Single-Seated Cage Valves control steam, air, liquids, or noncombustible gases in two-position, proportional, or floating control systems where line isolation is not required. SPECIFICATIONS Valve Type ............................................ Cage Valves Body Pattern ........................................ Two-way, Straight-through Connection Type .................................. Flanged Controlled Medium ...............................
Flanged Globe Valve V5011A,B V5011A,B Used for proportional control of hot or chilled water and glycol solutions (to 50 percent concentration) and for two-position control of low pressure steam. SPECIFICATIONS Valve Type ............................................ Globe Valve Body Pattern ........................................ Two-way Flow Characteristic .............................. Equal Percentage Connection Type .................................. Flanged Controlled Medium ..........................
Flanged Globe Valve V5013B,C V5013B,C The V5013B are three-way mixing valves. The V5013C are three-way diverting valves. These valves provide proportional or two-position control of hot or chilled water in heating or cooling systems. These valves are offered in sizes 2 1/2 in. through 6 in. SPECIFICATIONS FEATURES • Not suitable for combustible gases. • Valves utilize direct mounting valve actuators, Q5020/ Q5022 linkages with Direct Coupled Actuators, or Pneumatic Valve Actuators to operate the valve.
Flanged Globe Valve VGF2 VGF2 VGF Flanged Globe Valves are used for 2-position or modulating control of steam, hot water, or chilled water-glycol solutions up to 50 percent concentration in heating, ventilation and air conditioning (HVAC) systems. They can be operated by ML6984/7984, ML6420/6425, ML6421/7421 Electric Linear Actuators, MP953 Pneumatic Actuators, Modutrol™ Motors with Q5001 valve linkage, or MN/MS Series Direct Coupled Actuators with Q5020 valve linkage.
Flanged Globe Valve VGF2 Pressure VGF2 PressureBalanced Balanced VGF Flanged Globe Valves are used for 2-position or modulating control of steam, hot water, or chilled water-glycol solutions up to 50 percent concentration in heating, ventilation and air conditioning (HVAC) systems. They can be operated by ML6984/7984, ML6420/6425, ML6421/7421 Electric Linear Actuators, MP953 Pneumatic Actuators, Modutrol™ Motors with Q5001 valve linkage, or MN/MS Series Direct Coupled Actuators with Q5020 valve linkage.
Flanged Globe Valve VGF3 VGF3 VGF Flanged Globe Valves are used for 2-position or modulating control of hot water or chilled waterglycol solutions up to 50 percent concentration in heating, ventilation and air conditioning (HVAC) systems. They can be operated by ML6984/7984, ML6420/6425, ML6421/7421 Electric Linear Actuators, MP953 Pneumatic Actuators, Modutrol™ Motors with Q5001 valve linkage, or MN/MS Series Direct Coupled Actuators with Q5020/Q5022 valve linkages.
Resilient Seat Butterfly Valves VFF1 VFF1 Resilient seat in two-way valves, provide control for HVAC system applications including chilled water, hot water, cooling tower water, thermal storage systems, and steam. SPECIFICATIONS DIMENSIONS DIAGRAM L2 L1 H G* F D L2 L1 R T PIPE SIZE IN.
Resilient Seat Butterfly Valves VFF2 VFF2 Resilient seat two-way valves provide control for HVAC system applications including chilled water, hot water, cooling tower water, thermal storage systems, and steam. SPECIFICATIONS Body Pattern ........................................ 2 way (NC, NC/NO; NSR) Valve Action ......................................... Normally Closed, convertible to Normally Open with Spring Return DCA Connection Type .................................. Lugged Controlled Medium .........
Resilient Seat Butterfly Valves VFF3 VFF3 Resilient seat three-way valves provide control for HVAC system applications including chilled water, hot water, cooling tower water, thermal storage systems, and steam. SPECIFICATIONS APPROVALS CE ......................................................... Compliant Underwriters Laboratories, Inc. ............
Resilient Seat Butterfly Valves VFF6 VFF6 Resilient seat three-way valves provide control for HVAC system applications including chilled water, hot water, cooling tower water, thermal storage systems, and steam. SPECIFICATIONS Body Pattern ........................................ 3 way (A-AB-B) Valve Action ......................................... Normally Closed Connection Type .................................. Lugged Controlled Medium ...............................
Damper Linkage Q605 Q605 Use the Q605 linkage kit to connect Modutrol® motor to standard damper or set of dampers to provide control of duct airflow. FEATURES • Adjustable to any degree of damper opening. Include ball joints, motor crank arm and damper arm for 1/2 in. (13 mm) diameter shaft. • 27520 pushrod must be ordered separately. SPECIFICATIONS Linkage Type ........................................ Damper Mounting ..............................................
Valve Linkage Q5001 Q5001 The Q5001 Valve Linkage connects a Modutrol® Motor to a 2- or 3-way valve. It is used primarily on V5011 or V5013 steam and water valves. SPECIFICATIONS Linkage Type ........................................ Valve Mounting .............................................. Linkage mounts directly to the valve bonnet; motor mounts on linkage bracket. Used with Actuator ............................... Modutrol Motor Stem Force Rating ...............................
Globe Valve Linkage Q5020 Q5020 The Q5020 Globe Valve Linkages connect a Honeywell direct coupled actuator (DCA) to a steam or water globe valve. The Q5020 Linkages are compatible with two-way and threeway globe valves up to 3 in. (DN80). SPECIFICATIONS Linkage Type ........................................ Valve Mounting .............................................. Linkage mounts directly to the valve bonnet; motor mounts on linkage Used with Actuator ...............................
Globe Valve Linkage Q5022 Q5022 The Q5022A,B Globe Valve Linkages connect one or two Honeywell direct coupled rotary actuators (DCA) to a globe valve for control of chilled water, hot water, or steam. The Q5022A,B Linkages are compatible with 2 and 3-way globe valves up to 6 in. (DN150) pipe size. Q5022A is used to provide enhanced close-off ratings with Honeywell globe valves up to 3 in. with 1-3/8 in. diameter bonnet and 3/4 in. stem stroke. Q5022B is used with Honeywell globe valves 4 to 6 in.
Direct Coupled Actuators - Spring Return Models Override to full open Wiring for (0)2-10 Vdc proportioning controller operating multiple actuators ACTUATOR ACTUATOR 1 24 VAC 4 – V 2 3 0/2 TO 10 VDC PROPORTIONING CONTROLLER 4 90°-0° 5 FEEDBACK 2-10 VDC 10-2 VDC 0-10 VDC 10-0 VDC Fltg, fwd Fltg, rev 3 ACTUATOR 1 3 2 – + SPDT FEEDBACK 2-10 VDC 10-2 VDC 0-10 VDC 10-0 VDC Fltg, fwd Fltg, rev 3 3 SET SWITCH TO MODULATING. 4 ENSURE PROPER GROUNDING OF ACTUATOR CASE.
Actuator Wiring Diagrams Direct Coupled Actuators - Spring Return Models Direct Coupled Actuators - Spring Return Models S03 Series (MS4103, MS7403, MS7503, MS8103) and S05 Series (MS4105, MS7105, MS7405, MS7505, MS8105) Wiring for low-voltage two-position control Wiring for floating control ACTUATOR 1 24 VAC 2 1 SPST 3 V 2 24 VAC 1 1 2 4 V 2 0°-90° 3 ACTUATOR 1 LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 24 VDC SUPPLY ACCEPTABLE.
Actuator Wiring Diagrams Direct Coupled Actuators - Spring Return Models Direct Coupled Actuators - Spring Return Models Override to full open Wiring for (0)2-10 Vdc proportioning controller operating multiple actuators ACTUATOR ACTUATOR 1 24 VAC 4 0/2 TO 10 VDC PROPORTIONING CONTROLLER – V 2 3 4 90°-0° 5 FEEDBACK 2-10 VDC 10-2 VDC 0-10 VDC 10-0 VDC Fltg, fwd Fltg, rev 3 ACTUATOR 1 1 LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
Actuator Wiring Diagrams Direct Coupled Actuators - Spring Return Models Direct Coupled Actuators - Spring Return Models S10 Series (MS4110, MS7510, MS8110) and S20 Series (MS4120, MS7520, MS8120) Wiring for On/Off Control 1 24 VAC 1 SPST 2 Wiring for Proportioning controllers (Modulating mode setting) 3 V 2 ACTUATOR ACTUATOR 1 2 2 – 3 ENSURE PROPER GROUNDING OF ACTUATOR CASE. 3 OR + OR N/A 5 FEEDBACK 1 2 3 FEEDBACK V 4 + 2 24 VDC SUPPLY ACCEPTABLE.
Actuator Wiring Diagrams Direct Coupled Actuators - Spring Return Models Direct Coupled Actuators - Spring Return Models Override to full open (Modulating mode setting) ACTUATOR 24 VAC 1 2 0/2 TO 10 VDC PROPORTIONING CONTROLLER – + SPDT FEEDBACK 1 V 2 24 VAC ACTUATOR 2 3 OR + 4 OR N/A 5 FEEDBACK 2-10 VDC 10-2 VDC 0-10 VDC 10-0 VDC Fltg, fwd Fltg, rev 3 1 1 V 2 24 VAC 0/2 TO 10 VDC PROPORTIONING CONTROLLER 3 OR + 4 OR N/A 5 FEEDBACK 2-10 VDC 10-2 VDC 0-10 VDC 10-0 VDC Fltg, fwd
Actuator Wiring Diagrams Direct Coupled Actuators - Spring Return Models Direct Coupled Actuators - Spring Return Models ML4125, ML8125, ML4135, and ML8135 Typical 24 Vac wiring Typical 230 Vac Wiring L1 ( ) RED 24 VAC BLACK M17585A M17588A Typical 120 Vac Wiring 120 VAC L2 ( ) M17589A 158 230 VAC L2 ( ) L2 ( ) L1 ( ) L1 ( ) BLACK WHITE BROWN BLUE
Actuator Wiring Diagrams Direct Coupled Actuators - Non-Spring Return Models Direct Coupled Actuators - Non-Spring Return Models ML6161 and ML7161 ML6174 and ML7174 ML7161 used with 4-20 mA control L1 (HOT) ML7174 used with 4-20 mA control ML7161, ML7174 1 L1 (HOT) T1 L2 ML7161, ML7174 1 T1 L2 T2 T2 – – – – + + mA + + mA +V +V 4-20 mA CONTROLLER 1 4-20 mA CONTROLLER POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 1 M18071 POWER SUPPLY.
Actuator Wiring Diagrams Direct Coupled Actuators - Non-Spring Return Models Direct Coupled Actuators - Non-Spring Return Models N05 Series (MN6105, MN7505) and N10 Series (MN6110, MN7510) Wiring for Floating Control Wiring for Voltage Control MN7505, MN7510 MODULATING: 0[2]... 10 V, 10... 0[2] V MN6105, MN6110 FLOATING: DIR ACTUATOR 1 1 24 VAC 2 2 ACTUATOR 1 V 1 3 2 0[2]... 10 V 4 5 1 2 LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
Actuator Wiring Diagrams Direct Coupled Actuators - Non-Spring Return Models Direct Coupled Actuators - Non-Spring Return Models N20 Series (MN6120, MN7220) and N34 Series (MN6134, MN7234) Used for On/Off Control Wiring for Floating Control FLOATING ACTUATOR FLOATING ACTUATOR Direct Service/Off Reverse Direct Service/Off Reverse 2 3 CONTROLLER 4 2 3 FLOATING CONTROLLER 4 2 1 1 24 VAC 24 VAC 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
Actuator Wiring Diagrams Direct Coupled Actuators - Fire and Smoke Actuators Direct Coupled Actuators - Smoke and Fire Actuators ML4115, ML8115, MS4209F, MS4309F, MS4709F, MS4809F, MS8209F, and MS8309F Typical 24 Vac wiring L1 ( ) RED 24 VAC BLACK Typical 230 Vac Wiring L1 ( ) BROWN 230 VAC BLUE L2 ( ) L2 ( ) M17585A M17588A Typical 120 Vac wiring L1 ( ) BLACK 120 VAC WHITE L2 ( ) M17589A MS4120F, MS4620F, and MS8120F Wiring for 24V Control Wiring for 120V Control MS4120F MS8120F L2 ( )
Actuator Wiring Diagrams Foot Mounted Motors Foot Mounted Motors M4185 and M8185 Typical connections for Series 41 motors MOTOR THERMOSTAT Typical connections for Series 81 motors MOTOR LIMIT CONTROL THERMOSTAT LIMIT CONTROL TRANSFORMER 1 1 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS M806A AND OVERLOAD PROTECTION AS REQUIRED. 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
Actuator Wiring Diagrams Foot Mounted Motors Foot Mounted Motors M6274, M6284, M6285, and M6294 Motors with Linear 10K Feedback Typical wiring for Series 62 motors SERIES 62 MOTOR SERIES 60 CONTROLLER R R 1 B 3 2 W 4 T G Y 2 1 3 L1 (HOT) L2 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 TRANSFORMER MAY BE INTERNAL OR EXTERNAL TO MOTOR. 3 FEEDBACK POTENTIOMETER.
Actuator Wiring Diagrams Foot Mounted Motors Foot Mounted Motors M9161, M9164, M9171, M9172, M9174, M9175, M9181, M9182, M9184, M9185, M9186, and M9194 Typical wiring for Series 90 motors SERIES 90 CONTROLLER Wiring for Potentiometer Control 135 OHM POTENTIOMETER MOTOR R R W W B B MOTOR W W T1 R R T2 B B L2 L2 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
Actuator Wiring Diagrams Actuators with Butterfly Valves Actuators with Butterfly Valves VFF2, VFF3, and VFF6 Typical Non-Spring Return Floating Control Actuator wiring Typical Spring Return Floating/Modulating control wiring FLOATING ACTUATOR ACTUATOR Direct Service/Off Reverse 1 24 VAC 1 2 4 V 2 3 0/2 TO 10 VDC PROPORTIONING CONTROLLER – OR + 4 OR N/A 5 FEEDBACK 2-10 VDC 10-2 VDC 0-10 VDC 10-0 VDC Fltg, fwd Fltg, rev + 2 3 CONTROLLER 4 3 FEEDBACK 2 1 LINE VOLTAGE POWER SUPPLY.
Actuator Wiring Diagrams Actuators with Butterfly Valves Actuators with Butterfly Valves Typical Non-Spring Return 120 Vac Floating control wiring FIELD WIRING AUXILIARY SWITCHES N.O. COM N.C. ACTUATOR COM A N.O. B N.C. C COM D N.O. E N.C. F AUX SPDT SWITCH/LS3 (VOLTAGE FREE) AUX SPDT SWITCH/LS4 (VOLTAGE FREE) LS3 CAM LS4 CAM TORQUE SWITCHES (OPTIONAL) N.C. COM N.O. N.C. N.O. C 0 MOTOR SINGLE PHASE POWER SUPPLY N.C. N.O. L 1 3 4 5 6 7 OPEN CLOSE FOR HEATER OPTION ONLY N.C. N.O.
GUIDE Specifications Section 5: Guide Specifications Guide Specifications ...............................................................
Guide Specifications Threaded Globe Valves 23 00 00 HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC) 23 09 00 Instrumentation and Control for HVAC 23 09 13 Instrumentation and Control Devices for HVAC 23 09 13.33 Control Valves Threaded Globe Valves Mounting 1. Two-way threaded globe valves shall be red brass with female national pipe thread fittings in sizes from ½ up to 3 inches (DN15 to DN80). Three-way valves shall be up to 2 inches (DN50). 2.
Pressure-Balanced Flanged Globe Valves 23 00 00 HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC) 23 09 00 Instrumentation and Control for HVAC 23 09 13 Instrumentation and Control Devices for HVAC 23 09 13.33 Control Valves Pressure-Balanced Flanged Globe Valves Mounting 1. Flanged globe valves shall be cast iron with ANSI/ASME 125 flanges in sizes from 2 ½ up to 6 inches (DN65 to DN150), maximum temperature 353°F (178 C). 2. Valve dimensions will conform to ANSI/ISA S75.03. 3.
Guide Specifications Flanged Globe Valves 23 00 00 HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC) 23 09 00 Instrumentation and Control for HVAC 23 09 13 Instrumentation and Control Devices for HVAC 23 09 13.33 Control Valves Flanged Globe Valves Mounting 1. Flanged globe valves shall be cast iron with ANSI/ASME 125 and ANSI/ASME250 flanges in sizes from 2 ½ up to 6 inches (DN65 to DN150), maximum temperature 353°F (178 C). 2. Valve dimensions will conform to ANSI/ISA S75.03. 3.
Threaded Control Ball Valves and Actuators 23 00 00 HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC) 23 09 00 Instrumentation and Control for HVAC 23 09 13 Instrumentation and Control Devices for HVAC 23 09 13.33 Control Valves Threaded Control Ball Valves and Actuators Mounting and Wiring 1. Valves shall be forged brass with female national pipe thread pipe fittings from ½ to 2 ½ inches (DN15 to DN65), and 3 inches (DN80) in two-way. 2.
Guide Specifications Control Ball Valves and Actuators 23 00 00 HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC) 23 09 00 Instrumentation and Control for HVAC 23 09 13 Instrumentation and Control Devices for HVAC 23 09 13.33 Control Valves Control Ball Valves and Actuators Mounting and Wiring 1. Valves shall be cast iron with ANSI/ASME 125 flange fittings from 4 to 6 inches (DN100 to DN150). 2. Valves shall provide equal percentage flow control characteristics.
Flanged Butterfly Valves and Actuators 23 00 00 HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC) 23 09 00 Instrumentation and Control for HVAC 23 09 13 Instrumentation and Control Devices for HVAC 23 09 13.33 Control Valves Flanged Butterfly Valves and Actuators Mounting and Wiring 1. Valves shall be cast iron with ANSI/ASME 125 flange fittings from 2 to 20 inches (DN50 to DN500). Valve body shall be coated with polymer resin for corrosion protection. 2.
Guide Specifications Fan Coil Zone Valves and Dedicated Actuators 23 00 00 HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC) 23 09 00 Instrumentation and Control for HVAC 23 09 13 Instrumentation and Control Devices for HVAC 23 09 13.33 Control Valves Fan Coil Zone Valves and Dedicated Actuators Mounting and Wiring 1. Valves shall be forged brass with sweat or female national pipe thread pipe fittings in sizes from ½ up to 1 inches (DN15 to DN25).
Cartridge Cage Valves and Dedicated Actuators 23 00 00 HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC) 23 09 00 Instrumentation and Control for HVAC 23 09 13 Instrumentation and Control Devices for HVAC 23 09 13.33 Control Valves Cartridge Cage Valves and Dedicated Actuators Mounting and Wiring 1. Valves shall be cast bronze with sweat or female national pipe thread pipe fittings in sizes from ½ up to 1 ¼ inches (DN15 to DN32).
Guide Specifications Cartridge Globe Valves and Dedicated Actuators 23 00 00 HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC) 23 09 00 Instrumentation and Control for HVAC 23 09 13 Instrumentation and Control Devices for HVAC 23 09 13.33 Control Valves Cartridge Globe Valves and Dedicated Actuators Mounting and Wiring 1. Valves shall be brass with female national pipe thread fittings in sizes from ½ up to 1 ¼ inches (DN15 to DN32) and sweat fittings from ½ to ¾ inches (DN15-20). 2.
Electric Large Linear Globe Valve Actuators 23 00 00 HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC) 23 09 00 Instrumentation and Control for HVAC 23 09 13 Instrumentation and Control Devices for HVAC 23 09 13.13 Actuators and Operators Electric Large Linear Globe Valve Actuators Mounting and Wiring 1. Actuators shall be direct coupled type requiring neither crank-arm nor linkage and be capable of direct mounting to a globe valve. 2.
Guide Specifications Direct-Coupled Electronic Globe Valve Actuators 23 00 00 HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC) 23 09 00 Instrumentation and Control for HVAC 23 09 13 Instrumentation and Control Devices for HVAC 23 09 13.13 Actuators and Operators Direct-Coupled Electronic Digital Globe Valve Actuators Mounting and Wiring 1.
Direct-Coupled Rotary Actuator Globe Valve Linkage 23 00 00 HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC) 23 09 00 Instrumentation and Control for HVAC 23 09 13 Instrumentation and Control Devices for HVAC 23 09 13.13 Actuators and Operators Direct-Coupled Rotary Actuator Globe Valve Linkage Mounting and Wiring 1.
Guide Specifications Tandem Direct-Coupled Rotary Actuator Globe Valve Linkage 23 00 00 HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC) 23 09 00 Instrumentation and Control for HVAC 23 09 13 Instrumentation and Control Devices for HVAC 23 09 13.13 Actuators and Operators Tandem Direct-Coupled Rotary Actuator Globe Valve Linkage Mounting and Wiring 1.
Footmount Globe Valve Actuators 23 00 00 HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC) 23 09 00 Instrumentation and Control for HVAC 23 09 13 Instrumentation and Control Devices for HVAC 23 09 13.13 Actuators and Operators Footmount Globe Valve Actuators Mounting and Wiring 1. Actuators shall be direct coupled type requiring a Q5001 linkage and be capable of direct mounting to a Honeywell globe valve from ½ to 6 inches in size (DN15 to DN80). 2.
Guide Specifications Footmount Globe Valve Actuators 23 00 00 HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC) 23 09 00 Instrumentation and Control for HVAC 23 09 13 Instrumentation and Control Devices for HVAC 23 09 13.13 Actuators and Operators Footmount Globe Valve Actuators Mounting and Wiring 1. Actuators shall be direct coupled type requiring a Q5001 linkage and be capable of direct mounting to a Honeywell globe valve from ½ to 6 inches in size (DN15 to DN80). 2.
Section 6: Accessories ACCESSORIES Ball Joints, Push Rod Accessories............................................186 Control, Positioning, Feedback Accessories.............................186 Mounting Accessories...............................................................187 Rotational Limiters, Position Indicators......................................188 Crankarms................................................................................189 Shaft Adaptor Accessories.................................
Damper And Actuator Accessories Ball Joints, Push Rod Accessories Product Number Description Used With 103598 Ball Joint (1/4 in.) Used With: All Actuators and Dampers All Actuators and Dampers 27518 Crankarm balljoint with 1/4 - 28 UNF male threads, fits 5-16 inch diameter push rods All Actuators and Dampers 27518 Crankarm balljoint with 1/4 - 28 UNF male threads, fits 5-16 inch diameter push rods All Actuators and Dampers 27520A Push Rod (5/16 in. dia., 5 in.
Damper And Actuator Accessories Control, Positioning, Feedback Accessories (cont.
Damper And Actuator Accessories Mounting Accessories (cont.) Product Number Description Used With 32007205-004 Retaining Clip, Damper External Drive Pin Used With: Damper with External Actuator Mounting (i.e., 32007205-005 Kit) Damper with External Actuator Mounting (i.e., 32007205-005 Kit) 32007205-005 Damper External Drive Pin Kit Used With: Damper with External Actuator Mounting (i.e., 32007205-005 Kit) Damper with External Actuator Mounting (i.e.
Damper And Actuator Accessories Crankarms Product Number Description Used With 205830A Rotary-to-Linear Kit Used With: 35 and 70 lb-in NSR and 25, 44, 53, and 88 lb-in SR Actuators 35 and 70 lb-in.NSR 26026G Damper Crank Arm, 1/2 in. damper shaft All Actuators and Damper Product Number Description Used With 205843B Hub Insert, 1 in. (25mm) Round Used With: 300 lb-in NSR Actuators (ML Series) 300 lb-in.NSR Actuators (ML Series) 32003167-001 3/8 in.
Damper And Actuator Accessories Enclosure Accessories Product Number Description Used With 32003036-001 Weather Enclosure Used With: All Actuators All Actuators 50005859-001 NEMA 4 Enclosure for Direct Coupled Actuator 142 lb-in. Spring Return Actuators; ML6161, ML6174, ML7161, ML7174; N20 Actuators; N34 Actuators; 150 lb-in. NSR Actuators (ML Series); 25 and 53 lb-in.SR Actuators (ML Series); 300 lb-in.
Damper And Actuator Accessories Accessories for Obsolete Actuators Description Used With 205617 Hub Insert, 3/4 in. (19mm) Used With: 150 lb-in NSR Actuators (ML Series) 150 lb-in. NSR Actuators (ML Series) 205685 Crank Arm Kit Used With: 150 lb-in NSR Actuators (ML Series) 150 lb-in. NSR Actuators (ML Series) 205753 Hub Insert, 3/8 in. (10mm) Used With: 150 lb-in NSR and 25 and 53 lb-in Actuators (ML Series) 150 lb-in.NSR and 25 and 53 lb-in.Actuators (ML Series) 205755 Hub Insert, 1/2 in.
Valve Accessories Valve Actuator Accessories Product Number Description Used With 114191A Auxiliary Switch Assembly — 127834A Switch (made) — 272629A Adapter Kit for mounting ML6984/ ML7984 to V5045 and VGF standard 2-way valves.
Pneumatic Damper Accessories Pneumatic Damper Actuator Parts and Accessories Description Used With 14001213-001 MP904A and B Diaphragm MP904A,B 14002061-001 Damper Linkage Kit w/ Template MP909E,F 14002850-001 Angle Bracket 5 3/8 in, 137 mm, long, 5 in, 127 mm, wide MP909D,E 14003640-001 Angle Bracket 3 in. (76 mm) long, 3 3/4 in. (95 mm) wide, 2 3/4 in. (70 mm) high MP913; MP909D 14004062-001 External Trunnion Mounting Bracket MP918A,B; MP909E,H 14004062-002 Internal N.C.
Pneumatic Damper Accessories Pneumatic Damper Actuator Parts and Accessories (cont.
Pneumatic Damper Accessories Pneumatic Damper Actuator Parts and Accessories (cont.) Description Used With 314440A MP909 - Clevis, Clevis Pin and Cotter Pin Assembly MP909 314503 MP909C Replacement Diaphragm MP909C 315321 Crankarm Balljoint (with 1/4 in male MP516; MP909D,E,H; MP913 threads), fits 5/16 in. diameter pushrod 315321G Crankarm and Linkage MP909A,D 315439/0062 Clevis MP909D 315781 Motor shaft balljoint with 3/8 - 16 UNC female threads, fits 5/16 inch diameter pushrods.
Pneumatic Valve Accessories Pneumatic Valve Actuator Parts and Accessories 196 Product Number Description Used With 14002039-001 MP953D Diaphragm Sleeve MP953B,D,F 14002040-002 MP953D Diaphragm MP953B,D,F 14003124-002 MP953B,D,F Diaphragm Repair Kit (includes 14002039-001 and 14002040-002) MP953B,D,F 14004138-001 MP953B,F (Reverse Acting) Positive Positioner Retrofit Kit MP953B,F 14004139-001 MP953A,E (Direct Acting, 8 in. and 13 in. diameter, 3/4 in.
Pneumatic Valve Accessories Pneumatic Valve Actuator Parts and Accessories (cont.) Description Used With 311851/0062 Stem extension for 8 in. dia. 3/4 in. stroke MP953A,C,E MP953A,C,E (8 in.) 311852 Brown Spring for MP953A,C 3/4 inch stroke (8 inch diameter), 2-7 psi range MP953A,C (8 in., 2-7 psi) 311855 Gray spring for MP953C (8 inch diameter), 8-12 psi range MP953C 311863 Stem Retainer for the MP953C,E (8 in. diameter) MP953C,E 312099 1-1/2 in. stroke Spider for 13 in.
Foot Mounted Motor Accessories Foot Mounted Motor Accessories 198 Product Number Description Used With 203709D2 Screw Terminal Adapter With Zero and Span Adjustment for Series 2 and Series 3 Modutrol IV Motors Series 2 and Series 3 Modutrol IV™ Motor 220738A Adapter Bracket.
Foot Mounted Motor Accessories Foot Mounted Motor Accessories (cont.) Description Used With 221508A2 Resistor Board Assembly for Series 2 Modutrol IV Motors Series 2 Modutrol IV Motors 4074ERU Weatherproofing kit. Protects motor from driving rain when mounted in any position Fits all Modutrol IV motors 7617DM Coupling- Must be used with ES-650-117 explosion-proof housing ES-650-117 ES-650-117 Explosion-Proof Housing encloses motor for use in explosive atmospheres.
Damper And Valve Accessories Damper and Valve Linkage Accessories 200 Product Number Description Used With 102546 Ball Joint, 5/16 in. Damper Linkages 101662A/0021 Motor Mounting Bracket Assembly for Q605 Q605 102931/0021 Adapter arm for less that 90 degree rotation for the Q605 Q605 104643A Adapter for driving 2 dampers from 1 crank arm Modutrol IV Motors 220828AA Valve bracket assembly, Q5001 Q5001 220845/0767 Retainer button for Q5001 Q5001 220848A Q5001 Cam with 1/2 in.
Section 8: Competitive Cross Reference Direct Coupled Actuator............................................................202 Control Ball Valve 2-Way Valve ........................................................................220 2-Way Valve + Non-Spring Return Floating Actuator............221 2-Way Valve + Non-Spring Return Modulating Actuator......222 2-Way Valve + Spring Return, 2-Position Actuator...............223 2-Way Valve + Spring Return Floating Actuator....................
Competitive Cross Reference Direct Coupled Actuator Belimo Model Torque (lb-in.) Control Signal Power Feedback Switches Timing (sec) LMB24-3-P5-T 45 lb-in. (5 Nm) On/Off, Floating 24 Vac/Vdc 0-5 kOhm — 95 Honeywell Actuator Torque (lb-in.) Control Signala Power ML6174A2002 + 200976A ML6174A2002 + 200976C ML6174A2002 + 200976A ML6174A2002 + 200976C 70 lb-in.
Competitive Cross Reference Direct Coupled Actuator Torque (lb-in.) Control Signal Power Feedback Switches Timing (sec) Honeywell Actuator Torque (lb-in.) Control Signala NMCB24-3-T 90 lb-in. (10 Nm) On/Off, Floating 24 Vac/Vdc — — 45 MN6110A1003 88 lb-in. (10 Nm) On/Off, Floating NMX24-3-T 90 lb-in. (10 Nm) On/Off, Floating 24 Vac/Vdc — — MN6110A1003 88 lb-in. (10 Nm) On/Off, Floating NMX120-3 90 lb-in.
Competitive Cross Reference Direct Coupled Actuator Belimo Model Torque (lb-in.) Control Signal Power Feedback Switches AMX24-MFT 180 lb-in. (20 Nm) MFT 24 Vac/Vdc Variable (0-10 Vdc) — AMX24-MFT95 180 lb-in. (20 Nm) 0-135 Ohm 24 Vac/Vdc Variable (010 Vdc) — AMX24-PC 180 lb-in. (20 Nm) 0-20 Vdc Phase Cut 24 Vac/Vdc 2-10 Vdc — GMB24-3 360 lb-in. (40 Nm) On/Off, Floating 24 Vac/Vdc — GMX24-3 360 lb-in. (40 Nm) On/Off, Floating 24 Vac/Vdc GMX120-3 360 lb-in.
Competitive Cross Reference Direct Coupled Actuator Belimo Model Torque (lb-in.) Control Signal Honeywell Actuator Torque (lb-in.) Control Signala Power Feedbacka LF24-ECONR03 US 35 lb-in. (5 Nm) 0-3 kOhm, type 10 thermistor 95 MS7405A2030 44 lb-in. (5 Nm) On/Off, Floating, (0) 2-10 Vdc, Economizer (3kOhm, 3-Position) 24 Vac/Vdc 2-10 Vdc — 24 Vac (±20%), 24 Vdc (0) 2-10 Vdc LF24-ECONR10 US 35 lb-in.
Competitive Cross Reference Direct Coupled Actuator Belimo Model Torque (lb-in.) Control Signal Power Feedback Switches Timing (sec) Honeywell Actuator Torque (lb-in.) Control Signala TF24 US 18 lb-in. (2 Nm) On/Off 24 Vac/Vdc — — <75 MS8103A1030 27 lb-in. (3 Nm) On/Off TF24-S US 18 lb-in. (2 Nm) On/Off 24 Vac/Vdc — 1 (adj 0-95) <75 MS8103A1130 27 lb-in.
Competitive Cross Reference Direct Coupled Actuator Johnson Model Torque (lb-in.) Control Signal M9106-GGC-2 53 lb-in. (6 Nm) (0) 2-10 Vdc, (0) 4 to 20 mA M9108-AGA-2 70 lb-in. (8 Nm) On/Off, Floating 20 to 30 Vac at 50/60 Hz — — M9108-AGC-2 70 lb-in. (8 Nm) On/Off, Floating 20 to 30 Vac at 50/60 Hz — 2 M9108-AGD-2 70 lb-in. (8 Nm) On/Off, Floating 20 to 30 Vac at 50/60 Hz 0-135 Ohm — M9108-AGE-2 70 lb-in.
Competitive Cross Reference Direct Coupled Actuator Johnson Model Torque (lb-in.) Control Signal M9109-GGC-2 80 lb-in. (9 Nm) M9116-AGA-2 140 lb-in. (16 Nm) On/Off, Floating 20 to 30 Vac at 50/60 Hz — — M9116-AGC-2 140 lb-in. (16 Nm) On/Off, Floating 20 to 30 Vac at 50/60 Hz — 2 M9116-AGD-2 140 lb-in. (16 Nm) On/Off, Floating 20 to 30 Vac at 50/60 Hz 0-135 Ohm — M9116-AGE-2 140 lb-in.
Competitive Cross Reference Direct Coupled Actuator Torque (lb-in.) Control Signal M9124-AGD-2 210 lb-in. (24 Nm) On/Off, Floating 20 to 30 Vac 0-1 35 Ohm at 50/60 Hz — M9124-AGE-2 210 lb-in. (24 Nm) On/Off, Floating 20 to 30 Vac at 50/60 Hz — M9124-GGA-2 210 lb-in. (24 Nm) & 420 lb- in. (48 Nm) M9124-GGC-2 210 lb-in. (24 Nm) & 420 lb- in. (48 Nm) M9124-HGA-2 210 lb-in. (24 Nm) & 420 lb- in. (48 Nm) M9206-BGA-2S 53 lb-in.
Competitive Cross Reference Direct Coupled Actuator Johnson Model Torque (lb-in.) M9124-HGC-2 210 lb-in. (24 Nm) & 420 lb- in. (48 Nm) M9124-JGA-2 210 lb-in. (24 Nm) 100-10 kOhms, Reversible 20 to 30 Vac at 50/60 Hz 0-10 Vdc for 90 (1 mA at 10 Vdc) — M9124-JGC-2 210 lb-in. (24 Nm) 100-10 kOhms, Reversible 20 to 30 Vac at 50/60 Hz 0-10 Vdc for 90 (1 mA at 10 Vdc) 2 M9132-AGA-2 280 lb-in. (32 Nm) On/Off, Floating 20 to 30 Vac at 50/60 Hz — — M9132-AGC-2 280 lb-in.
Competitive Cross Reference Direct Coupled Actuator Johnson Model M9216-BAA-2 M9216-BAC-2 Torque (lb-in.) 140 lb-in. (16 Nm) & 280 lb-in. (32 Nm) 140 lb-in. (16 Nm) & 280 lb-in. (32 Nm) Power Feedback Switches Timing (sec) Honeywell Actuator Torque (lb-in.) Control Signala Power Feedbacka Switches Timing (sec) On/Off 120 Vac — — — MS4120A1001 175 lb-in. (20 Nm) On/Off 100-250 Vac — — 45 On/Off 120 Vac — 2 — MS4120A1209 175 lb-in.
Competitive Cross Reference Direct Coupled Actuator Johnson Model Torque (lb-in.) M9216-HGA-2 140 lb-in. (16 Nm) & 280 lb-in. (32 Nm) M9216-HGC-2 140 lb-in. (16 Nm) & 280 lb-in. (32 Nm) M9216-JGA-2 140 lb-in. (16 Nm) M9216-JGC-2 140 lb-in. (16 Nm) Invensys Model Torque (lb-in.) Control Signal MA40-7043 35 lb-in. (4 Nm) On/Off MA40-7043-501 35 lb-in. (4 Nm) On/Off MF40-7043 35 lb-in. (4 Nm) Floating MF40-7043-501 35 lb-in. (4 Nm) Floating MS40-7043 35 lb-in.
Competitive Cross Reference Direct Coupled Actuator Invensys Model Torque (lb-in.) Control Signal MA41-7153 133 lb-in. (15 Nm) On/Off MA41-7153-502 133 lb-in. (15 Nm) On/Off MF41-7153 133 lb-in. (15 Nm) Floating MF41-7153-502 133 lb-in. (15 Nm) Floating MS41-7153 133 lb-in. (15 Nm) 2-10 Vdc MS41-7153-502 133 lb-in. (15 Nm) 2-10 Vdc MA40-7170 150 lb-in.
Competitive Cross Reference Direct Coupled Actuator Invensys Model Torque (lb-in.) Control Signal Power Feedback Switches Timing (sec) Honeywell Actuator Torque (lb-in.) Control Signala Power Feedbacka Switches Timing (sec) MF41-6043 30 lb-in. (3.4 Nm) Floating 24 Vac 0.05 — — < 90 MN6105A1011 44 lb-in. (5 Nm) On/Off, Floating 24 Vac/ Vdc (+20 / -15%) — — 95 MF41-6043-510 30 lb-in. (3.4 Nm) Floating 24 Vac 0.
Competitive Cross Reference Direct Coupled Actuator Torque (lb-in.) MS4D-6083-160 70 lb-in. (8 Nm) MF4E-60430-100 35 lb-in. (4 Nm) MF4E-60830-100 70 lb-in. (8 Nm) MS50-H2301 300 lb-in. (34 Nm) MS50-H2001 300 lb-in. (34 Nm) MS50-H2101 300 lb-in. (34 Nm) — — Siemens Model Torque (lb-in.) Control Signal Power Feedback Switches Timing (sec) Honeywell Actuator Torque (lb-in.) Control Signala — — — — — — — MN7505A2209 44 lb-in.
Competitive Cross Reference Direct Coupled Actuator Siemens Model GEB161.1U GEB132.1U GEB136.1U GEB164.1U GBB171.1U Torque (lb-in.) 132 lb-in. (15 Nm) 132 lb-in. (15 Nm) 132 lb-in. (15 Nm) 132 lb-in. (15 Nm) 177 lb-in. (20 Nm) Control Signal Power Feedback Switches Timing (sec) Honeywell Actuator Torque (lb-in.
Competitive Cross Reference Direct Coupled Actuator Siemens Model Torque (lb-in.) Control Signal Power Feedback Switches Timing (sec) Honeywell Actuator Torque (lb-in.) Control Signala GIB175.1P 310 lb-in. (35 Nm) On/Off, Floating 24 Vac 0-1kOhm — 150 — — GIB166.1U GIB166.1P GIB156.1U GIB156.1P GIB161.1P/MAS GIB164.1P/MAS GIB161.1P/SLA — 310 lb-in. (35 Nm) 310 lb-in. (35 Nm) 310 lb-in. (35 Nm) 310 lb-in. (35 Nm) 310 lb-in. (35 Nm) 310 lb-in. (35 Nm) 310 lb-in.
Competitive Cross Reference Direct Coupled Actuator Siemens Model GMA166.1U GMA166.1P GCA121.1U GCA121.1P GCA221.1U GCA131.1U GCA131.1P GCA132.1U GCA132.1P GCA136.1U GCA136.1P GCA161.1U GCA161.1P GCA163.1U GCA163.1P GCA164.1U GCA164.1P GCA151.1U GCA151.1P GCA126.1U GCA126.1P GCA226.1U GCA135.1U GCA135.1P GCA166.1U GCA166.1P GCA156.1U 218 Torque (lb-in.) 62 lb-in. (7 Nm) 62 lb-in. (7 Nm) 142 lb-in. (16 Nm) 142 lb-in. (16 Nm) 142 lb-in. (16 Nm) 142 lb-in. (16 Nm) 142 lb-in. (16 Nm) 142 lb-in.
Notes & Numbers Cross Reference 219
Control Ball Valve Cross Reference 2-Way Valve Pipe Size 1/2 in. Cv Siemens 0.4 0.63 1.6 Cv Invensys 599-10203 599-10204 599-10205 0.38 0.68 1.3 VB-2213-500-9-01 VB-2213-500-9-02 VB-2213-500-9-03 2.5 4 599-10206 599-10207 10 599-10208 2.6 4.7 8 11.7 0.31 0.63 1.2 2.5 4.
Control Ball Valve Cross Reference 2-Way Valve + Non-Spring Return Floating Actuator Pipe Size Cv Siemens 2.5 4 171A-10206 171A-10207 10 171A-10208 10 171A-10209 4.7 7.4 10 B217+LRB24-3 B218+LRB24-3 B219+LRB24-3 25 171A-10210 10 16 25 171A-10211 171A-10213 171A-10212 24 7.
Control Ball Valve Cross Reference 2-Way Valve + Non-Spring Return Modulating Actuator Pipe Size Cv Siemens 171C-10203 171C-10204 171C-10205 2.5 4 171C-10206 171C-10207 10 171C-10208 10 171C-10209 4.7 7.4 10 B217+LRB24-SR B218+LRB24-SR B219+LRB24-SR 25 171C-10210 10 16 25 171C-10211 171C-10213 171C-10212 24 7.
Control Ball Valve Cross Reference 2-Way Valve + Spring Return, 2-Position Actuator Pipe Size Cv Siemens 2.5 4 171E-10206 171E-10207 10 171E-10208 10 171E-10209 4.7 7.4 10 B217+TFX24 US B218+TFX24 US B219+TFX24 US 25 171E-10210 10 16 25 171E-10211 171E-10213 171E-10212 24 7.
Control Ball Valve Cross Reference 2-Way Valve + Spring Return Floating Actuator Pipe Size Cv Siemens Belimo B207+TF24-3 US B208+TF24-3 US B209+TF24-3 US B210+TF24-3 US B211+TF24-3 US B212+TF24-3 US B213+TF24-3 US B214+TF24-3 US B215+TF24-3 US Cv Invensys 0.38 0.68 1.3 VF-2213-536-9-01 VF-2213-536-9-02 VF-2213-536-9-03 2.6 4.7 8 11.7 0.31 0.63 1.2 2.5 4.
Control Ball Valve Cross Reference 2-Way Valve + Spring Return Modulating Actuator Pipe Size Cv Siemens 0.4 0.63 1.6 171G-10203 171G-10204 171G-10205 2.5 4 171G-10206 171G-10207 10 171G-10208 1/2 in. 3/4 in. 1 in. 171G-10209 25 171G-10210 10 16 25 171G-10211 171G-10213 171G-10212 63 171G-10214 16 171G-10215 40 100 25 171G-10216 171G-10217 171G-10218 40 63 160 171G-10220 171G-10219 171G-10221 40 63 171G-10222 171G-10224 100 171G-10223 1-1/4 in. 1-1/2 in. 2 in. 250 2-1/2 in.
Globe Valve Cross Reference Threaded Globe Valves Reverse-Acting 2-Way Valves Direct-Acting, SS Trim 2-Way Valves Direct-Acting, Brass Trim 2-Way Valves Pipe Size 3-Way Valves Siemens Model Cv Belimo Model Cv Invensys Cv Johnson Controls Cv Honeywell Model 1 599-03162 0.4 G212 0.4 VB-7213-0-4-01 0.73 VG7241CT 0.73 V5011N1008 1.6 599-03163 1.3 G213 1.3 VB-7213-0-4-02 1.16 V5011N1016 2.2 G214 2.2 VB-7213-0-4-03 1.85 V5011N1024 2.5 599-03164 2.9 V5011N1032 1/2" 1.
Globe Valve Cross Reference Diverting, ANSI 125 3-Way Valves Mixing, ANSI 125 3-Way Valves Bronze Trim, ANSI 125 2-Way Valves Flanged Globe Valves Pipe Size Cv Johnson Controls Cv Belimo Model Cv Invensys Cv Honeywell Model 2 1/2" 51 VB-3752-19 65 G665 56 VB-9213-0-5-12 63 V3351A2008 3" 83 VB-3752-22 90 G680 85 VB-9213-0-5-13 100 V3351A3006 4" 150 VB-3752-25 170 G6100 145 VB-9213-0-5-14 160 V3351A4004 5" 240 VB-3752-28 263 G6125 235 VB-9213-0-5-15 250 V3351A5
Pneumatics Cross Reference MANUFACTURER REPLACEMENT ITEM 2567-009 ROBERTSHAW V5011H1022 with FUNCTIONAL MP953C1000 MP920B1002 with FUNCTIONAL 14004345-001 2567-011 ROBERTSHAW V5011H1022 with FUNCTIONAL MP953C1018 ROBERTSHAW MP920B1002 FUNCTIONAL 2567-012 ROBERTSHAW ROBERTSHAW MP909D1201 FUNCTIONAL V5011H1022 with FUNCTIONAL MP953E1327 2472-030 ROBERTSHAW MP909D1227 FUNCTIONAL 2567-013 ROBERTSHAW 2472-040 ROBERTSHAW MP909D1219 FUNCTIONAL V5011H1022 with FUNCTIONAL MP953C1000 2472
Pneumatics Cross Reference ITEM NUMBER 2568-034 2568-035 MANUFACTURER REPLACEMENT ITEM TYPE OF REPLACEMENT ROBERTSHAW V5011F1089 with FUNCTIONAL MP953C1000 ROBERTSHAW V5011F1089 with FUNCTIONAL MP953E1327 REMARKS 2568-038 ROBERTSHAW V5011F1097 with FUNCTIONAL MP953C1018 Internal normally close only, 3 psi positioner span 2568-039 ROBERTSHAW V5011F1097 with FUNCTIONAL MP953C1000 Internal normally close only, 5 psi positioner span Internal normally close only, 10 psi positioner span ITEM NUMB
Pneumatics Cross Reference ITEM NUMBER MP909A1645 MP909A1652 MP909A1660 MANUFACTURER REPLACEMENT ITEM HONEYWELL MP909D1227 with 14002850001 with 312867H with 14002061-001 MIRCOSWITCH MIRCOSWITCH MP909D1219 with 14002850001 with 312867H FUNCTIONAL MP909E1232 FUNCTIONAL HONEYWELL MP918B1063 REMARKS FUNCTIONAL MP909D1201 with 14002850001 with 312867H MP909A1744 MP909C1021 TYPE OF REPLACEMENT FUNCTIONAL FUNCTIONAL For unitary applications, consult technical support.
Modutrol IV Motor Cross Reference ITEM NUMBER REPL TYPE REPL ITEM 2005377 FUNCTIONAL M934A1334/U 612804451 FUNCTIONAL M945D1006/U 203762E/U FUNCTIONAL M8185D1006/U 2061-1 FUNCTIONAL 3402-7 FUNCTIONAL 3402A-7 MULTI REPL REPL SEQ Channel (busi group) MFG NAME TRADE SINGER CO 1 TRADE HARTZELL PROP 1 TRADE M835A1051/U 1 TRADE WHITE RODGERS M8415A1004/U 1 TRADE WHITE RODGERS FUNCTIONAL M8415A1004/U 1 TRADE WHITE RODGERS 3403-4 FUNCTIONAL M8405A1006/U 1 TRADE WHITE RO
Modutrol IV Motor Cross Reference ITEM NUMBER REPL TYPE REPL ITEM MULTI REPL REPL SEQ Channel (busi group) MFG NAME M140GGA-1 FUNCTIONAL M9174D1007/U WITH 1 TRADE JOHNSON CONTROLS M140JAA-1 FUNCTIONAL M9174D1007/U WITH 1 TRADE JOHNSON CONTROLS M140JGA-1 FUNCTIONAL M9174D1007/U 1 TRADE JOHNSON CONTROLS M150AGA-1 FUNCTIONAL M6184D1035/U 1 TRADE JOHNSON CONTROLS M150AGB-1 FUNCTIONAL M6184D1035/U 1 TRADE JOHNSON CONTROLS M150AGB-1 FUNCTIONAL M6184F1017/u 3 TRADE JOHNS
Modutrol IV Motor Cross Reference ITEM NUMBER REPL TYPE REPL ITEM MULTI REPL WITH REPL SEQ Channel (busi group) MFG NAME M6181F1017/U DIRECT M6184D1035/U M6181F1017/U FUNCTIONAL M6184F1014/U M6182F1016/U FUNCTIONAL M6285A1005-S/U M6184A1007/U TRADE EQUIV M6184D1035/U M6184A1049/U DIRECT M6184D1035/U M6184A1049/U FUNCTIONAL M6184A1023/U M6184B1005/U FUNCTIONAL M6184D1035/U M6184B1013/P DIRECT M6184B1013/U M6184B1021/U DIRECT M6184D1035/U M6184B1021/U FUNCTIONAL M6184F1014/
Modutrol IV Motor Cross Reference ITEM NUMBER REPL TYPE REPL ITEM MULTI REPL REPL SEQ Channel (busi group) MFG NAME M6294D1008/U FUNCTIONAL M6294D1008-S/U 1 ALL M6294F1009/U FUNCTIONAL M6294F1009-F/U 1 ALL M6294F1017/U FUNCTIONAL M6294F1017-F/U 1 ALL M640A1006/U FUNCTIONAL M640A1121/U 1 TRADE HONEYWELL M640B1021/U FUNCTIONAL M640B1062/U 1 TRADE HONEYWELL M6410A1003/U DIRECT M6410A1029/U 1 TRADE HONEYWELL M6410A1011/U DIRECT M6410A1029/U 1 TRADE HONEYWELL M644A10
Modutrol IV Motor Cross Reference ITEM NUMBER REPL TYPE REPL ITEM MULTI REPL M734D1012/U DIRECT M9164D1009/U WITH M734D1038/U DIRECT M9164D1009/U M734H1000/U DIRECT M9164D1009/U WITH M734H1018/U DIRECT M9164D1009/U M734H1026/U FUNCTIONAL M734J1015/U REPL SEQ Channel (busi group) MFG NAME TRADE HONEYWELL 0 ALL HONEYWELL 1 TRADE HONEYWELL WITH 1 TRADE HONEYWELL M9164D1009/U WITH 1 TRADE HONEYWELL FUNCTIONAL M9164D1009/U WITH 1 TRADE HONEYWELL M734J1023/U DIRECT
Modutrol IV Motor Cross Reference ITEM NUMBER REPL TYPE REPL ITEM MULTI REPL REPL SEQ Channel (busi group) MFG NAME M80FAA-2 FUNCTIONAL M9184A1019/U 2 TRADE JOHNSON CONTROLS M80FCA-2 FUNCTIONAL M9185D1004/U 1 TRADE JOHNSON CONTROLS M80FDA-1 FUNCTIONAL M9185D1004/U 1 TRADE JOHNSON CONTROLS M80FEA-1 FUNCTIONAL M9185D1004/U 1 TRADE JOHNSON CONTROLS M80FEA-1 FUNCTIONAL M9185A1018/U 2 TRADE JOHNSON CONTROLS M80FFA-1 FUNCTIONAL M9185D1004/U 1 TRADE JOHNSON CONTROLS M80FF
Modutrol IV Motor Cross Reference ITEM NUMBER REPL TYPE REPL ITEM M845C1009/U FUNCTIONAL M8185D1006/U M845D1024/U FUNCTIONAL M8185D1006/U M845E1007/U DIRECT M8185D1006/U M845E1007/U FUNCTIONAL M4185B1009/u M847A1031 FUNCTIONAL M847A1080 M847A1031/U DIRECT M847A1080/U M847A1049/U FUNCTIONAL M847D1004/B MULTI REPL OR REPL SEQ Channel (busi group) MFG NAME 1 TRADE HONEYWELL 1 TRADE HONEYWELL 1 TRADE HONEYWELL 4 TRADE HONEYWELL TRADE HONEYWELL 1 ALL HONEYWELL M847A10
Modutrol IV Motor Cross Reference ITEM NUMBER REPL TYPE REPL ITEM MULTI REPL M9182C1017/U FUNCTIONAL M9185D1004/U WITH M9182D1015/U FUNCTIONAL M9185D1004/U M9182D1031/U FUNCTIONAL M9185D1004/U M9182D4001/U DIRECT M9185D4008/U M9182D4001/U FUNCTIONAL M9185D1004/U M9182W1002/U FUNCTIONAL M9185D1004/U WITH M9183G1009/U DIRECT M9185D1004/U OR M9183G1009/U FUNCTIONAL M9184A1001/U REPL SEQ Channel (busi group) MFG NAME 1 ALL HONEYWELL 1 ALL HONEYWELL 1 ALL HONEYWELL 1 T
Modutrol IV Motor Cross Reference ITEM NUMBER REPL TYPE REPL ITEM MULTI REPL REPL SEQ Channel (busi group) MFG NAME FUNCTIONAL M9484D1010/U 1 TRADE HONEYWELL M941A1032/U FUNCTIONAL M9484D1010/U 1 TRADE HONEYWELL M941A1057/U FUNCTIONAL M9484D1010/U 1 TRADE HONEYWELL M941B1007/U FUNCTIONAL M6284F1013/U 2 TRADE HONEYWELL M941C1006/U FUNCTIONAL M9484E1009/U 1 TRADE HONEYWELL M941C1014/U FUNCTIONAL M9484E1017/U 1 TRADE HONEYWELL M941C1022/U FUNCTIONAL M9484E1033/u 1
Modutrol IV Motor Cross Reference ITEM NUMBER REPL TYPE REPL ITEM MULTI REPL REPL SEQ Channel (busi group) MFG NAME M955C4000/U FUNCTIONAL M9185D1004/U WITH 1 TRADE HONEYWELL M955D1005/U FUNCTIONAL M9185D1004/U OR 1 TRADE HONEYWELL M965A1007/U FUNCTIONAL M9185D1004/U 1 TRADE HONEYWELL M975A1006/U FUNCTIONAL M9185D1004/U 1 TRADE HONEYWELL M975A1089/U FUNCTIONAL M9185D1004/U 1 TRADE HONEYWELL M975A1097/U FUNCTIONAL M9185D1004/U 1 TRADE HONEYWELL M975A1097/U DIRECT
Modutrol IV Motor Cross Reference ITEM NUMBER REPL TYPE REPL ITEM SQS65 FUNCTIONAL M7410E1036/U SQS82 FUNCTIONAL M6410A1003/U SQS82 FUNCTIONAL M6410A1011/U SSC61U FUNCTIONAL SSC81U MULTI REPL REPL SEQ Channel (busi group) MFG NAME 2 TRADE POWERS/LANDIS & GYR 1 TRADE BARBER COLMAN 2 TRADE BARBER COLMAN M7410F1000/U 1 ALL SIEMENS FUNCTIONAL M6410A1029/U 1 ALL SIEMENS V70DB-6 FUNCTIONAL M945D1006/U 1 TRADE JOHNSON CONTROLS VA-7450-10011 FUNCTIONAL M6410A1029/U 1 A
Section 8: APPENDIX A: Valve Selection & Sizing............................................................244 APPENDIX B: NEMA Standard Classification Code for Enclosures ................263 APPENDIX C: Best Practices for Low Power Control Signal Wiring.................264 Notes........................................................................................265 Warranty...................................................................................
Appendix A: Valve Selection and Sizing Appendix A: Valve Selection and Sizing Introduction This section provides information on valve selection and sizing. Valves must be selected for ability to meet temperature, pressure, flow control characteristic, and piping connection requirements of the hydronic system. Valve sizing is critical to ensure support for heating and cooling loads with adequate valve capacity, yet able to control system flow to provide stable building conditions efficiently.
Appendix A: Valve Selection and Sizing Valve Flow Terms Rangeability: The ratio of maximum flow to minimum controllable flow. Approximate rangeability ratios are 50 to 1 for V-port globe valves and 30 to 1 for contoured plug valves. EXAMPLE: A valve with a total flow capacity of 100 gpm full open and a rangeability of 30 to 1, can accurately controls flow accurately as low as 3 gpm.
Appendix A: Valve Selection and Sizing Close-off rating of three-way valves: The maximum pressure difference between either of the two inlet ports and the outlet port for mixing valves, or the pressure difference between the inlet port and either of the two outlet ports for diverting valves. Pressure drop (critical): The flow of a gaseous controlled fluid through the valve increases as the pressures drop increases until reaching a critical point. This is the critical pressure drop.
Appendix A: Valve Selection and Sizing Valve Types Ball valve:A ball valve has a precision ball between two seats with a body (Fig. 3). Ball valves have several port sizes for a give body size and go from closed to open with a 90 degree turn of the stem. They are available in both two-way and three-way configurations. For HVAC applications, ball valve construction includes brass and cast iron bodies; stainless steel, chrome plated brass, and cast iron balls; resilient seats with various temperature ratings.
Appendix A: Valve Selection and Sizing Single-seated valve: A valve with one seat, plug, and disc. Single-seated valves are suitable for applications requiring tight shut-off. Since a single-seated valve has nothing to balance the force of the fluid pressure exerted on the plug, it requires more closing force than a double-seated valve of the same size and therefore requires more actuator force than a double-seated valve. Petroleum products from sources such as cutting oils, solder flux, etc.
Appendix A: Valve Selection and Sizing Valve Selection Proper valve selection matches a valve to the control and hydronic system physical requirements. First consider the application requirements and then consider the valve characteristics necessary to meet those requirements. The following questions provide a guide to correct valve selection. — What is the piping arrangement and size? The piping arrangement indicates whether a two-way or three-way mixing or diverting valve is needed.
Appendix A: Valve Selection and Sizing Ball Valve Ball valves are available for two-position applications either manual (hand) or power operated or for modulating applications with direct coupled electric actuators. Ball valves are relatively low cost, provide tight close off, and are available in two-way and three-way configurations. As with all other valves, ball valves must be properly sized to provide good flow control.
Appendix A: Valve Selection and Sizing Linear Valve NONLINEAR SYSTEM RESPONSE PERCENTAGE OF FULL COOLING 100% A linear valve may include a V-port plug or a contoured plug. This type of valve is used for proportional control of steam or chilled water, or in applications that do not have wide load variations. Typically in steam or chilled water applications, changes in flow through the load (e.g., heat exchanger, coil) cause proportional changes in heat output.
Appendix A: Valve Selection and Sizing EXAMPLE: When a valve with the stem at 30 percent of its total lift and existing flow of 3.9 gpm (Table 2) opens an additional 10 percent of its full travel, the flow measures 6.2 gpm or increases 60 percent. If the valve opens an additional 10 percent so the stem is at 50 percent of its full travel, the flow increases another 60 percent and is 9.9 gpm. Table 2. Stem Position vs. Flow for Equal Percentage Valve.
Appendix A: Valve Selection and Sizing DIVERTING VALVE THREE-WAY MIXING VALVE HOT WATER SUPPLY LOAD BYPASS HOT WATER RETURN A. LOAD BYPASS IN MIXING VALVE APPLICATION THREE-WAY DIVERTING VALVE SUPPLY LOAD RETURN BYPASS B. LOAD BYPASS IN DIVERTING VALVE APPLICATION C2335A Fig. 13. Three-Way Valve Applications. MIXING VALVE A mixing valve provides two inlet ports and one common outlet port.
Appendix A: Valve Selection and Sizing Water Valves Determine the capacity index (Cv) for a valve used in a water application, using the formula: REPRINTED BY PERMISSION FROM ASHRAE HANDBOOK— 1996 HVAC SYSTEMS AND EQUIPMENT Fig. 14. Pressure Drop Correction for Ethylene Glycol Solutions Q G C V = ------------h G h Flow of fluid in gallons per minute required to pass through the valve. Specific gravity of the fluid (water = 1). Pressure drop in psi.
Appendix A: Valve Selection and Sizing 2. For hot water coil valves: cfm × 1.08 × TD a Q = --------------------------------------------K × TD w Where: cfm = Airflow through the coil. 1.08 = A scaling constant. See Note. TDa = Temperature difference of air entering and K = TDw = leaving the coil. Value from Table 3; based on temperature of water entering the coil (pounds per gallon x 60 minutes per hour). Temperature difference of water entering and leaving the coil. NOTE: The scaling constant 1.
Appendix A: Valve Selection and Sizing c. A manual balancing valve may be installed in the boiler bypass to equalize the boiler drop and the bypass drop. WATER VALVE SIZING EXAMPLES EXAMPLE 1: A two-way linear valve is needed to control flow of 45F chilled water to a cooling coil. The coil manufacturer has specified an eight-row coil having a water flow pressure drop of 3.16 psi. Further, specifications say that the coil will produce 55F leaving air with a water flow of 14.6 gpm.
Appendix A: Valve Selection and Sizing 4 PD 3.2 36 40.4 32 37.2 SUPPLY CHILLER 12 PD 9.6 HEAT/ COOL COIL 1 DP SETPOINT = 34' DP V1 V5 PUMP 180 GPM PER AHU COIL HEAT/ COOL COIL 4 V3 V2 V4 48 50 B1 0 HEAT/ COOL COIL 3 HEAT/ COOL COIL 2 4 PD 3.2 ZERO REFERENCE B3 B2 B4 RETURN SYSTEM STRAINER 4 3.2 NUMBERS IN CIRCLES PUMP INLET TOP NUMBERS BOTTOM NUMBER PD = = = = = GAGE PRESSURES ZERO FOR SIMPLICITY FULL FLOW 90% FLOW M10605 PRESSURE DROP Fig. 16. Chiller Bypass Application.
Appendix A: Valve Selection and Sizing ( 1 + 0.00075s )Q V C v = -------------------------------------------------63.5 h Use the water valve Cv formula to determine capacity index for Valve V1 as follows: Where: Q = Q G C v = ------------h Where: Q = G h = = Flow of fluid in gallons per minute required to pass through the valve is 70 gpm. Specific gravity of water is 1. Pressure drop across the valve. Plans of the heating system indicate three-inch supply and return mains.
Appendix A: Valve Selection and Sizing NOTE: The scaling constant 1.08 is derived as follows: 0.24BTU 60min 1lbair 1.08 = ----------------------- × ---------------- × -------------------lbairF 1hr 3 13.35ft Where: 1lbair -------------------3 13.35ft = the specific volume of air at standard conditions of temperature and atmospheric pressure. Simplifying the equation: 14.40Btumin 1.08 = ---------------------------------3 Fhr13.
Appendix A: Valve Selection and Sizing 2. Determine the critical pressure drop: hcritical = 50% x Pma Where: Pma = psia = Pressure in supply main in psia (absolute pressure) psig + 14.7 Use the smaller value h or hcritical when calculating Cv. Substituting this data in the formula: Q = 808.5 pounds per hour h = The pressure drop across a valve in a modulating application is: h = 85% x (Pm-Pr) Where: Pm = Pr = Two-Position Applications Use line sized valves whenever possible.
Appendix A: Valve Selection and Sizing Select a linear valve providing close control with a capacity index of 4 and meeting the required pressure and temperature ratings. NOTE: For steam valves downstream from pressure reducing stations, the steam will be superheated in most cases and must be considered. EXAMPLE 2: In Figure 19, a linear valve (V1) is needed for accurate flow control of a steam coil that requires 750 pounds per hour of steam.
Appendix Valve Selection This larger valve (2A: psi drop) has a steeper curve that is fur- and Sizing Boiling ther away from the desired linear valve characteristic. See LINEAR VALVE under VALVE SELECTION for more information. VALVE OPENING/ STEAM FLOW 100% 0% Cv = 25 Cv = 41 LINEAR VALVE CHARACTERISTIC STEM TRAVEL 100% C2337 Fig. 20. Effect of Pressure Drop in Steam Valve Sizing. Table 5. Properties of Saturated Steam. Boiling Point or Steam V Specific Temperature Volume (V), (For valve cu.
Appendix B: NEMA Standard Classification Code for Enclosures Appendix B: NEMA Standard Classification Code for Enclosures NEMA 1—General purpose. for indoor protection, where conditions are not unusually severe. NEMA 6—Submersible. For submerged operation under specified pressures and time. NEMA 2—Drip tight. Designed to exclude falling moisture or dirt. Particularly applicable to cooling rooms, laundries, etc., where condensation is prevalent. For indoor use.
Appendix C: Best Practices for Low Power Control Signal Wiring Appendix C: Best Practices for Low Power Control Signal Wiring Low power analog signals are commonly used for proportional control signal wiring in HVAC applications. Following are a series of best practices for the prevention of corruption of these signals due to electro-magnetic interference (“EMI”). EMI is typically caused by coupling of the electro-magnetic field that surrounds all wires carrying current.
Notes & Numbers APPENDIX 265
Notes & Numbers 266
AUTOMATION AND CONTROL PRODUCTS WARRANTY POLICY Honeywell warrants the products in this catalog (except those parts designated on Honeywell's price lists as not covered by this warranty) to be free from defects due to workmanship or materials, under normal use and service, for the following warranty periods.
Automation and Control Solutions In the US: Honeywell 1985 Douglas Drive North Golden Valley, MN 55422-3992 In Canada: Honeywell Limited 35 Dynamic Drive Toronto, Ontario M1V 4Z9 customer.honeywell.com 4 63-9271 PR March 2009 © 2009 Honeywell International Inc.