User's Manual

56
NPT Globe Valves ½- 3"
With Pneumatic Actuators
Common Features
Rolling diaphragm for long life and
low hysteresis
Easily installation and attachment
to the valve
Direct or reverse acting
No positive positioner
Actuator Features Without Positive Positioner
Actuator O.S. Number
MP953C1000
MP953C1018
MP953C1026
MP953C1067
MP953C1075
MP953C1083
MP953C1554
MP953C1562
MP953D1107
MP953D1131
MP953D1172
Direct / Reverse Acting DA / RA DA DA DA DA DA DA DA DA RA RA RA
Diaphragm Size
5" 5" 5" 8" 8" 8" 13" 13" 7-1/8" 7-1/8" 7-1/8"
Fail Safe Action
Stem Up Stem Up Stem Up Stem Up Stem Up Stem Up Stem Up Stem Up Stem Down Stem Down Stem Down
Positioner 10psi span
N/A5psi span
3psi span
Valve Size
(inches)
Cv
Flow
Characteristic
Valve
Action
Valve OS
Number
Close-off Pressure - See Charts On Page 51
2-Way
Water Valves
Straight Through
2.9
Equal %
Stem up to
close
V5011N3004
A-NC A-NC A-NC B-NC B-NC B-NC
N/A
C-NO C-NO C-NO
1/2" 4.7
V5011N3012
A-NC A-NC A-NC B-NC B-NC B-NC C-NO C-NO C-NO
3/4" 7.3
V5011N3020
A-NC A-NC A-NC B-NC B-NC B-NC C-NO C-NO C-NO
1" 11.7
V5011N3038
A-NC A-NC A-NC B-NC B-NC B-NC C-NO C-NO C-NO
1-1/4" 18.7
V5011N3046
A-NC A-NC A-NC B-NC B-NC B-NC C-NO C-NO C-NO
1/2" 0.73
Stem down
to close
V5011N1008
F-NO F-NO F-NO E-NO E-NO E-NO D-NC D-NC D-NC
1/2" 1.16
V5011N1016
F-NO F-NO F-NO E-NO E-NO E-NO D-NC D-NC D-NC
1/2" 1.85
V5011N1024
F-NO F-NO F-NO E-NO E-NO E-NO D-NC D-NC D-NC
1/2" 2.9
V5011N1032
F-NO F-NO F-NO E-NO E-NO E-NO D-NC D-NC D-NC
1/2" 4.7
V5011N1040
F-NO F-NO F-NO E-NO E-NO E-NO D-NC D-NC D-NC
3/4" 7.3
V5011N1057
F-NO F-NO F-NO E-NO E-NO E-NO D-NC D-NC D-NC
1" 11.7
V5011N1065
F-NO F-NO F-NO E-NO E-NO E-NO D-NC D-NC D-NC
1-1/4" 18.7
V5011N1073
F-NO F-NO F-NO E-NO E-NO E-NO D-NC D-NC D-NC
1-1/2" 29.3
V5011N1081
F-NO F-NO F-NO E-NO E-NO E-NO D-NC D-NC D-NC
2" 46.8
V5011N1099
F-NO F-NO F-NO E-NO E-NO E-NO D-NC D-NC D-NC
2-1/2" 63
V5011F1105
L-NO L-NO L-NO L-NO L-NO L-NO G-NC G-NC G-NC
3" 100
V5011F1113
L-NO L-NO L-NO L-NO L-NO L-NO
G-NC G-NC G-NC
2-Way
Steam Valves
Straight Through
1/2" 0.73
Linear
Stem down
to close
V5011N2006
F*-NO F*-NO F*-NO E*-NO E*-NO E*-NO
N/A
D*-NC D*-NC D*-NC
1/2" 1.16
V5011N2014
F*-NO F*-NO F*-NO E*-NO E*-NO E*-NO D*-NC D*-NC D*-NC
1/2" 1.85
V5011N2022
F*-NO F*-NO F*-NO E*-NO E*-NO E*-NO D*-NC D*-NC D*-NC
1/2" 2.9
V5011N2030
F*-NO F*-NO F*-NO E*-NO E*-NO E*-NO D*-NC D*-NC D*-NC
1/2" 4.7
V5011N2048
F*-NO F*-NO F*-NO E*-NO E*-NO E*-NO D*-NC D*-NC D*-NC
3/4" 7.3
V5011N2055
F*-NO F*-NO F*-NO E*-NO E*-NO E*-NO D*-NC D*-NC D*-NC
1" 11.7
V5011N2063
F*-NO F*-NO F*-NO E*-NO E*-NO E*-NO D*-NC D*-NC D*-NC
1-1/4" 18.7
V5011N2071
F*-NO F*-NO F*-NO E*-NO E*-NO E*-NO D*-NC D*-NC D*-NC
1-1/2" 29.3
V5011N2089
F*-NO F*-NO F*-NO E*-NO E*-NO E*-NO D*-NC D*-NC
D*-NC
2" 46.8
V5011N2097
F*-NO F*-NO F*-NO E*-NO E*-NO E*-NO D*-NC D*-NC D*-NC
2-1/2" 63
V5011G1111
L*-NO L*-NO L*-NO L*-NO L*-NO L*-NO G*-NC G*-NC G*-NC
3" 100
V5011G1129
L*-NO L*-NO L*-NO L*-NO L*-NO L*-NO G*-NC G*-NC G*-NC
3-Way
Water Valves
Mixing
1/2" 2.9
Linear B-AB /
Equal % A-AB
Stem up
closes A-AB
V5013N1030
H-NC H-NC H-NC J-NC J-NC J-NC
N/A
K-NC K-NC K-NC
1/2" 4.7
V5013N1048
H-NC H-NC H-NC J-NC J-NC J-NC K-NC K-NC K-NC
3/4" 7.3
V5013N1055
H-NC H-NC H-NC J-NC J-NC J-NC K-NC K-NC K-NC
1" 11.7
V5013N1063
H-NC H-NC H-NC J-NC J-NC J-NC K-NC K-NC K-NC
1-1/4" 18.7
V5013N1071
H-NC H-NC H-NC J-NC J-NC J-NC K-NC K-NC K-NC
1-1/2" 29.3
V5013N1089
H-NC H-NC H-NC J-NC J-NC J-NC K-NC K-NC K-NC
2" 46.8
V5013N1097
H-NC H-NC H-NC J-NC J-NC J-NC K-NC K-NC K-NC
*The close-off pressure not to exceed rated pressure of steam valve
NC = Normally Closed
NO = Normally Open
SPRING RANGE PSI (kPa)
L - LOWER SEAT
U - UPPER SEAT
ACTUATOR AIR PRESSURE IN PSI (kPa)
4-11
(30-75)
11
(75)
12
(85)
13
(90)
14
(95)
15
(105)
16
(110)
17
(115)
18
(125)
4
(30)
3
(20)
2
(15)
1
(5)
0
(0)
LU
V5013N: 1/2-INCH TO 2-INCH VALVE BODIES WITH
5-INCH DIRECT ACTING PNEUMATIC ACTUATOR
5
(35)
10
(70)
15
(105)
20
(140)
25
(170)
30
(205)
35
(240)
40
(275)
CLOSEOFF PRESSURE RATING - PSI (kPa)
2-7
(15-50)
7
(50)
8
(55)
9
(60)
10
(70)
11
(75)
12
(85)
13
(90)
14
(95)
2
(15)
1
(5)
0
(0)
LU
MIXING
1
1
USE 4-11 PSI (30-75 kPa) RANGE FOR DETERMINING CLOSEOFF OF VALVES WITH
MP953E ACTUATORS.
M12909
8-12
(55-85)
12
(85)
13
(90)
14
(95)
15
(105)
16
(110)
17
(115)
18
(125)
1
(5)
8
(55)
7
(50)
6
(40)
LU
5
(35)
4
(30)
3
(20)
2
(15)
45
(310)
55
(380)
65
(450)
50
(345)
60
(415)
70
(485)
Cv 2.9
Cv 4.7
Cv7.3
Cv 11.7
Cv18.7
Cv 29.3
Cv 46.8
Chart H