Specification Sheet

APPENDICES
Table 1. Troubleshooting Guide.
Symptom Cause Solution
Poor airflow Plugged outside hood 1/4 in. (6 mm) mesh.• Clean exterior hoods or vents•
Filters plugged.• Remove and clean filter.•
Core obstructed.• Remove and clean core.•
House grilles closed or blocked.• Check and open grilles.•
Dampers (if installed) are closed.• Open and adjust dampers•
Poor power supply at site.• Have electrician check supply voltage at house.•
Ductwork is restricting airflow.• Check duct installation.•
Improper speed control setting.• Increase speed of ventilator.•
Ventilator airflow improperly balanced.• Have contractor balance ventilator airflow.•
Supply air
feels cold
Poor location of supply grilles, airflow can •
irritate the occupant.
Locate grilles high on walls or under baseboard •
heaters; install ceiling-mounted diffuser or
grilles to avoid blowing directly on occupants
(example: over a sofa).
Outdoor temperature extremely cold.• Turn down ventilator supply speed.•
Use a small duct heater (1 kW) to temper the •
supply air.
Placement of furniture or closed doors is •
restricting movement of air in the home.
If supply air is ducted in furnace return, run •
furnace fan continuously to distribute ventilation
air comfortably.
Ventilator airflow can be incorrectly balanced.• Have a contractor balance ventilator airflow.•
Dehumidistat
is not
operating
Incorrect connection to external 24-volt control.•
Staple/nail is shorting out external low voltage.•
Check that correct wires were used.•
Check external wiring for a short.•
Check dehumidistat setting; it could be at Off.• Set dehumidistat at the desired setting.•
Dehumidistat is disabled when the outdoor •
temperature is above 60F for 24 hours.
Check the LED on the terminal block for long •
flash followed by a short flash.
TROUBLESHOOTING
HR150, 200; ER150, 200 Perfect Window™ Fresh Air Ventilation Systems 68-0171—12
18