User Guide
Table Of Contents
- 1. Safety
- 2. Receipt of delivery
- 3. Technical data
- 4. Installation
- 5. Commissioning
- 6. Fault tracing
- 7. SmartVFD Compact Application Interface
- 8. Control panel
- 9. General purpose application parameters
- 9.1 Quick setup parameters (Virtual menu, shows when par. 13.1 = 1)
- 9.2 Motor settings (Control panel: Menu PAR -> P1)
- 9.3 Start/stop setup (Control panel: Menu PAR -> P2)
- 9.4 Frequency references (Control panel: Menu PAR -> P3)
- 9.5 Ramps and brakes setup (Control panel: Menu PAR -> P4)
- 9.6 Digital inputs (Control panel: Menu PAR -> P5)
- 9.7 Analogue inputs (Control panel: Menu PAR -> P6)
- 9.8 Digital and analogue outputs (Control panel: Menu PAR - > P7)
- 9.9 Protections (Control panel: Menu PAR -> P9)
- 9.10 Autorestart parameters (Control panel: Menu PAR -> P10 )
- 9.11 PI control parameters (Control panel: Menu PAR -> P12 )
- 9.12 Easy usage menu (Control panel: Menu PAR -> P0 )
- 9.13 System parameters
- 10. Parameter descriptions
- 10.1 Motor settings (Control panel: Menu PAR -> P1)
- 10.2 Start/Stop setup (Control panel: Menu PAR -> P2)
- 10.3 Frequency references (Control panel: Menu PAR -> P3)
- 10.4 Ramps & brakes setup (Control panel: Menu PAR -> P4)
- 10.5 Digital inputs (Control panel: Menu PAR -> P5)
- 10.6 Analoque inputs (Control panel: Menu PAR -> P6)
- 10.7 Digital and analoque outputs (Control panel: Menu PAR -> P7)
- 10.8 Motor thermal protection (parameters 9.7 - 9.10)
- 10.9 Autorestart parameters (Control panel: Menu PAR -> P10)
- 10.10 PI control parameters (Control panel: Menu PAR -> P12)
- 10.11 Easy usage menu (Control panel: Menu PAR -> P9)
- 10.12 Fieldbus parameters (Control panel: Menu PAR -> S2 )
46 Parameters Honeywell
9
9.2 MOTOR SETTINGS (CONTROL PANEL: MENU PAR -> P1)
NOTE! These parameters are shown, when P13.1 = 0.
Code Parameter Min Max Unit Default ID Note
P1.1
Motor nominal volt-
age
180 500 V
230
400
110
Check rating plate on
the motor
P1.2
Motor nominal fre-
quency
30 320 Hz 50.00 111
Check rating plate on
the motor
P1.3
Motor nominal
speed
300
2000
0
rpm 1440 112
Default applies for a 4-
pole motor.
P1.4
Motor nominal cur-
rent
0.2 x
I
Nunit
1.5 x
I
Nunit
A
I
Nunit
113
Check rating plate on
the motor
P1.5
Motor cos
0.30 1.00 0.85 120
Check rating plate on
the motor
P1.7 Current limit
0.2 x
I
Nunit
2 x
I
Nunit
A
1.5 x
I
Nunit
107
P1.8 Motor control mode 0 1 0 600
0 = Frequency control
1 = Speed control
P1.9 U/f ratio selection 0 2 0 108
0 = Linear
1 = Squared
2 = Programmable
P1.10
Field weakening
point
30.0
0
320 Hz 50.00 602
P1.11
Voltage at field
weakening point
10.0
0
200 % 100.00 603
% of Nominal voltage of
the motor
P1.12
U/f curve midpoint
frequency
0.00 P1.10 Hz 25.00 604
P1.13
U/f curve midpoint
voltage
0.00 P1.11 % 50.00 605
% of Nominal voltage of
the motor
P1.14
Output voltage at
zero frequency
0.00 40.00 % 0.00 606
% of Nominal voltage of
the motor
P1.15 Torque boost 0 1 0 109
0 = Not used
1 = Used
P1.16
Switching fre-
quency
1.5 16.0 kHz 6.0 601
P1.17 Brake chopper 0 2 0 504
0=Disabled
1=Used in Run state
2=Used in Run and Stop
state
Table 9.2: Motor settings
ϕ