Fault tracing Honeywell • 35
7.3 Other fault conditions
The following fault tracing diagram will help you to locate and fix some of the most usual prob-
lems. If the problem persists contact your local distributor.
Figure 9. Fault tracing diagram for Modbus RTU
Drive does not
start from the bus
Check communi-
cation status (par.
5.7.3.2.1/5.8.3.2.2)
Counter does not
run
Counter for bad
frames (see Table
3) increases
Counter OK.
No communication
Poor
communication
Is the device in
READY state?
Check the led on
keypad
Check external
interlockings (I/O)
Is fieldbus selected
as control place?
Check parameter
M1.15 or M3.2.1
Does Master give
RUN command?
Use keypad to
monitor variable
M5.7.3.2.5
Set variable AV36
to ‘1
Check fieldbus
parameters
Check other field-
bus parameters in
menu M5.8
Check selected
protocol (M5.7.1.1)
Check Masters
parameters
Check configura-
tions (Slave add-
ress, baudrate etc.)
Check termination
resistors
Check that both
ends of the fieldbus
line have termina-
tion resistors
(chapter 4.2)
Check cabling
Check cable for
cuts
Check correct place-
ment of conductors
in terminals
Other bus devices
Check other
necessary devices
(e.g. router)
Check termination
resistors
Check that both
ends of the fieldbus
line have termi-
nation resistors
(chapter 4.2)
Check parameters
Check cabling
Check distances
between cables,
see chapter 4.2.
Check cable types,
see chapter 3.
Check grounding
Check grounding,
see chapter 4. Re-
member to make
grounding for each
device!
Check connections
Check stripping of
cables and
conductors, see
chapter 4.
Check terminals for
loose connections