User Guide

Communications Honeywell • 29
6.3.3.6 Resettable operation day counter
Reset the counter by writing “1” for parameter ID2311.
6.3.3.7
Energy counter
The last number of the Format field indicates the decimal point place in the Energy field. If the
number is bigger than 0, move the decimal point to the left by the number indicated. For exam-
ple, Energy = 1200, Format = 52. Unit = 1. Energy = 12.00kWh.
6.3.3.8
Resettable energy counter
Reset the counter by writing “1” for parameter ID2312.
Address Register Purpose
40101 440101 Years
40102 440102 Days
40103 440103 Hours
40104 440104 Minutes
40105 440105 Seconds
Table 26. Resettable operation day counter
Address Register Purpose
40201 440201 Energy
40202 440202 Format
40203 440203
Unit
1 = kWh
2 = MWh
3 = GWh
4 = TWh
Table 27. Energy counter
Address Register Purpose
40301 440301 Energy
40302 440302 Format
40303 440303
Unit
1 = kWh
2 = MWh
3 = GWh
4 = TWh
Table 28. Resettable energy counter