Product Overview

SMARTVFD HVAC
63-4520—09 2
* If 230VAC is used as control voltage from the output relays, the control
circuitry must be powered with a separate isolation transformer to limit
short circuit current and overvoltage spikes. This is to prevent welding on
the relay contacts. Refer to standard EN 60204-1, section 7.2.9.
SmartVFD BYPASS Features
The Smart VFD BYPASS is available in 5 configurations as
explained below. All configurations are available in
NEMA 1, NEMA 12 and ventilated NEMA 3R.
SmartVFD Disconnect:
Fused Disconnect with no bypass
SmartVFD 2-Contactor:
Provides an economical means of bypassing the VFD.
No Main Disconnect
Freeze/Fire/Smoke Interlock
SmartVFD 3-Contactor:
Commission, service or replace the VFD without affecting
the operation of the motor. Provide additional bypass
control capabilities with Auto-bypass and HOA options.
Fused Disconnect
Freeze/Fire/Smoke Interlock
VFD can be isolated from power with motor running in
BYPASS mode
TEST position powers the VFD without sending power
to the motor
SmartVFD 3-Contactor Options:
AUTO-BYPASS
Any VFD fault will automatically send the bypass to
BYPASS mode
A contact closure sends the bypass to BYPASS mode
Dry contacts indicate when the bypass is in BYPASS
mode, alerting the building management system.
Table 1. General.
Communication
RS485 Standard: Modbus™ RTU, BACnet, N2
Ethernet Standard: Modbus/TCP, BACnet/IP
Software features
Energy-saving
functions
Real-time clock for timed functions
Energy monitor for kWh monitoring
Sleep function to minimize downtime energy
Protections
Overload and underload protections (e.g. broken fan and dry pump)
Motor thermal protection
Missing phase detection
Automatic reset to avoid interruption of the process
Process control
2 * PID For process control
Multipump For replacing the pump controller
Flying start For tripless catching of spinning fan
Human
interfaces
Keypad Graphical display with built-in manual and wizards.
PC Tools
PC Commissioning Tool for easy commissioning, monitoring, and troubleshooting.
Energy Savings calculator to estimate cost avoidance.
Product selection tool for selecting VFD and bypass, and creating submittal
documents.
Table 2. I/O Connections.
Basic I/O Board
Terminal Signal
1 +10 Reference output
2 AI1+ Analogue input, voltage or current
3 AI1- Analogue input common (current)
4 AI2+ Analogue input, voltage or current
5 AI2- Analogue input common (current)
6 24 24 V aux. voltage
7GNDI/O ground
8 DI1 Digital input 1
9 DI2 Digital input 2
10 DI3 Digital input 3
11 CM Common A for DI1-DI6
12 24 24 V aux. voltage
13 GND I/O ground
14 DI4 Digital input 4
15 DI5 Digital input 5
16 DI6 Digital input 6
17 CM Common A for DI1-DI6
18 AO1+ Analogue signal (+output)
19 AO-
/GND
Analogue output common
30 +24 24 V auxiliary input voltage
A RS485 Differential receiver/transmitter
B RS485 Differential receiver/transmitter
Table 3. I/O Connections, Relay Board 2.
Relay Board 2
Terminal Signal
21
Relay output 1*
Switching capacity24VDC/8A
250VAC/8A
125VDC/0.4A
Min.switching load5V/10mA
22
23
24
Relay output 2*
Switching capacity24VDC/8A
250VAC/8A
125VDC/0.4A
Min.switching load5V/10mA
25
26
28
Thermistor input
Rtrip = 4.7 kΩ (PTC); Measuring
voltage 3.5V
29