PROGRAMMING Honeywell • 17
4.4.2 BACnet IP settings
P5.9.3.1.1 I
NSTANCE NUMBER
Similar to BACnet MS/TP device object instance number (see Chapter 4.3.1).
P5.9.3.1.2 BAC
NET PORT NUMBER
The UDP port for the BACnet IP communication.
P5.9.3.1.3 C
OMMUNICATION TIME-OUT
Defines the number of seconds after a timeout is indicated after a communication break or dis-
connected ethernet link. Value 0 disables communication and link supervision.
NOTE! The Application parameter P3.9.1.6 (ID 733) can be used to define the action for com-
munication timeout.
P5.9.3.1.4 P
ROTOCOL IN USE
BACnet/IP protocol can be enabled and disabled with this parameter. When the parameter val-
ue is set to "1" the BACnet/IP protocol is enabled and disabled when set to "0".
P5.9.3.1.5 F
OREIGNDEVICE
The foreign device settings are located under this submenu. The foreign device feature is used
when the device is located in a different network than the BBMD. A normal router does not send
broadcast messages between different networks. The 'Foreign device' feature solves this
problem by establishing a connection to the BBMD with unicast messages. All broadcast mes-
sages are forwarded to a BBMD device that takes care of receiving and transmitting broadcast
messages in both directions for all foreign devices.
P5.9.3.1.5.1 F
OREIGNDEVICE
If this parameter is set to value 'Yes', the foreign device registration becomes active.
P5.9.3.1.5.2 BBMD IP
The IP address of the BACnet IP Broadcast Management Device.
P5.9.3.1.5.3 BBMD P
ORT
The BBMD Port number.
P5.9.3.1.5.4 R
EGISTRATIONINTERVAL
The registration interval to keep a live connection to the BBMD. Unit is seconds.
NOTE! The Registration TTL is twice as long as this time.