6.2.1 Binary Value Object
Out_Of_Service X X
Present_Value X X
Priority_Array X * X *
Relinquish_Default X * X *
Status_Flags X X
COV_Increment X
Units X
Instance ID Object Name Description
Inactive /
Active
Present
Value
Access
Type
BV0
Ready State
Indicates whether the drive is ready
or not
Not Ready /
Ready
R
BV1
Run/Stop State
Indicates whether the drive is running
or stopped
Stop / Run R
BV2
Fwd/Rev State
Indicates the rotation direction of the
motor
Fwd / Rev R
BV3
Fault State Indicates if a fault is active OK / Fault R
BV4
Alarm State Indicates if an alarm is active OK / Alarm R
BV5
At Setpoint Ref. Frequency reached False / True R
BV6
At Zero Speed Motor Running at zero speed False / True R
BV7
fb_ProcessdataOut_01 Bit_0 ProcessDataOut1 bit 0 0 / 1 R
BV8
fb_ProcessdataOut_01 Bit_1 ProcessDataOut1 bit 1 0 / 1 R
BV9
fb_ProcessdataOut_01 Bit_2 ProcessDataOut1 bit 2 0 / 1 R
BV10
fb_ProcessdataOut_01 Bit_3 ProcessDataOut1 bit 3 0 / 1 R
BV11
fb_ProcessdataOut_01 Bit_4 ProcessDataOut1 bit 4 0 / 1 R
BV12
fb_ProcessdataOut_01 Bit_5 ProcessDataOut1 bit 5 0 / 1 R
BV13
fb_ProcessdataOut_01 Bit_6 ProcessDataOut1 bit 6 0 / 1 R
BV14
fb_ProcessdataOut_01 Bit_7 ProcessDataOut1 bit 7 0 / 1 R
BV15
Run/Stop CMD
Command to start drive (FB control is
active)
Stop / Run C
BV16
Fwd/Rev CMD Command to run forward/reverse Fwd/Rev C
BV17
Reset Fault
Command to reset Active Fault from
drive
0 / Reset C
BV18
Stop By Coast Stop Drive by coast 0 / 1 C
BV19