User Guide

Honeywell • 28 COMMUNICATIONS
NOTE! Present Value Access Types: R = Read-only, W = Writeable, C = Commandable.
Commandable values support priority arrays & relinquish defaults.
6.2.2 Analogue Value Object
BV20
Quick Stop Quick Stop 0 / 1 C
BV21
Zero Ramp Stop by zero ramp 0 / 1 C
BV22
Hold Ramp Hold ramp 0 / 1 C
BV23
BusCtrl Activate Bus control 0 / 1 C
BV24
BusRef Activate Bus reference 0 / 1 C
BV25
fb_control_word Bit_10 fb_control_word bit 10 0 / 1 C
BV26
fb_control_word Bit_11 fb_control_word bit 11 0 / 1 C
BV27
fb_control_word Bit_12 fb_control_word bit 12 0 / 1 C
BV28
fb_control_word Bit_13 fb_control_word bit 13 0 / 1 C
BV29
fb_control_word Bit_14 fb_control_word bit 14 0 / 1 C
BV30
fb_control_word Bit_15 fb_control_word bit 15 0 / 1 C
Table 10.
Instance ID Object Name Description Units
Present Value
Access Type
AV0
Frequency Setpoint Frequency Setpoint Hz R
AV1
Output Frequency Output Frequency Hz R
AV2
Motor Speed Motor Speed rpm R
AV3
Load (power) Motor Shaft Power % R
AV4
Kilowatt Hours total Kilowatt Hour Counter (Total) kWh R
AV5
Motor Current Motor Current A R
AV6
DC link Voltage DC link Voltage V R
AV7
Motor Voltage Motor Voltage V R
AV8
Unit Temperature Heatsink Temperature °C R
AV9
Motor Torque In % of motor nominal Torque % R
AV10
Operating Days Operating Days (resettable) Day R
AV11
Operating Hours Operating Hours (resettable) Hour R
AV12
Kilowatt Hours Kilowatt Hours (resettable) kWh R
AV13
Torque Reference Torque Reference %
R