User Guide

COMMUNICATIONS Honeywell • 29
1) ANSI/IEEE-754 floating point. Binary coding can be done only if the value has no decimals.
2) Map only analog data to these objects. If binary coded data is mapped into these objects, the
data may be invalid because of ANSI/IEEE-754 floating point to 32bit integer conversion.
NOTE! Present Value Access Types: R = Read-only, W = Writeable, C = Commandable.
Commandable values support priority arrays & relinquish defaults.
AV14
Temperature Rise
Calculated motor tempera-
ture 100.0% = nominal tem-
perature of motor
%R
AV15
fb_ProcessdataOut_01
Application specific
2)
R
AV16
fb_ProcessdataOut_02
Application specific
2)
R
AV17
fb_ProcessdataOut_03
Application specific
2)
R
AV18
fb_ProcessdataOut_04
Application specific
2)
R
AV19
fb_ProcessdataOut_05
Application specific
2)
R
AV20
fb_ProcessdataOut_06
Application specific
2)
R
AV21
fb_ProcessdataOut_07
Application specific
2)
R
AV22
fb_ProcessdataOut_08
Application specific
2)
R
AV23
Active Fault Code Active Fault Code - R
AV24
Speed Reference
Speed Reference, percent-
age of nominal speed
%C
AV25
Current Limit Current Limit A W
AV26
Min Frequency Minimum Frequency Hz W
AV27
Maximum Frequency Maximum Frequency Hz W
AV28
Accel Time Acceleration Time s W
AV29
Decel Time Deceleration Time s W
AV30
fb_ProcessdataIn_01
Application specific
2)
C
AV31
fb_ProcessdataIn_02
Application specific
2)
C
AV32
fb_ProcessdataIn_03
Application specific
2)
C
AV33
fb_ProcessdataIn_04
Application specific
2)
C
AV34
AnyParam ID
ID number that is used in
AV35
0 to 65535
resolution 1
W
AV35
AnyParam Value Value of ID defined by AV34 32 bits Value W
AV36
1)
Fb_Control_Word Lo16
Fixed Control Word First 16
bits 0-15
range 65535 -
0
C
AV37
1)
Fb_Control_Word Hi16
Fixed Control Word Last 16
bits 16-31
range 65535 -
0
C
AV38
Fb_Status_Word Lo16
Fixed Status Word First 16
bits 0-15
range 65535 -
0
R
AV39
Fb_Status_Word Hi16
Fixed Status Word Last 16
bits 16-31
range 65535 -
0
R
Table 10.