8. QUICK SETUP
Following these instructions, you can easily and fast set up your BACnet bus for use.
1
Parametrize BACnet functionality as described in Chapter 4.
2
Make these settings in the master software.
A. Set Control Word to ‘0’ (AV36 Fb_Control_Word_Lo16).
B. Set Control Word to
‘1’
(AV36 Fb_Control_Word_Lo16).
C. AC drive status is RUN.
D. Set Reference value to ‘50’ (50.00%) (AV24 Speed Reference).
E. Frequency setpoint is 25.00 Hz (if MinFreq is 0.00 Hz and MaxFreq is 50.00 Hz)
F. Set Control Word to ‘0’ (AV36 Fb_Control_Word_Lo16).
G. AC drive status is STOP.