User Guide

ANNEX - PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT Honeywell • 39
Data Link Layer Options:
MS/TP master (Clause 9), baud rate(s): 9600,19200,34800, 76800 (supports autobaud detec-
tion)
BACnet IP, (Annex J), Foreign Device
Device Address Binding:
Is static device binding supported? (This is currently necessary for two-way communication
with MS/TP slaves and certain other devices.)
Yes No
Networking Options:
Router, Clause 6 - List all
routing configurations
, e.g.,
ARCNET-Ethernet
, Ethernet-MS/TP, etc.
Annex H, BACnet Tunneling Router over IP
BACnet/IP Broadcast Management Device (BBMD)
Character Sets Supported:
Indicating support for multiple character sets does not imply that they can all be supported si-
multaneously.
_ ISO 10646 (UTF-8) IBM
TM
/Microsoft
TM
DBCS ISO 8859-1
ISO 10646 (UCS-2) ISO 10646 (UCS-4) JIS X 0208
relinquish-default x x
Binary Value Object - writable when out-of-service is set true
Object property Readable Writable
object-identifier x
object-name x
object-type x
present-value x
* x Normally ‘read only’ but
becomes writable when out-of-
service set to true
status-flags x
event-state x
out-of-service x x
priority-array x
relinquish-default x x
Binary Value Object - Commandable
Object property Readable Writable Commandable