User Guide

PROGRAMMING Honeywell • 9
4. PROGRAMMING
You will find basic information on how to use the control keypad in the Application Manual of
your SmartVFD HVAC/SmartDrive HVAC AC drive.
Below you will find some examples of navigation paths to the fieldbus parameters.
1. First ensure that the right fieldbus protocol is selected.
Activating BACnet MSTP (P5.8.1.1)
Main Menu > I/O and Hardware > RS-485 > Common settings > Protocol >
BACnet MSTP <
Activating BACnet IP (P5.9.3.1.4)
Main Menu > I/O and Hardware > Ethernet > Bacnet IP > Settings > Protocol
in use > Yes <
2. Select ‘Fieldbus control’ as the Remote Control Place.
Control Place (P3.2.1)
Main Menu > Parameters > Start/Stop Setup > Rem Control Place >
FieldbusCTRL <
3. Activate Remote control.
Local/Remote (P3.2.2)
Main Menu > Parameters > Start/Stop Setup > Local/Remote > Remote <
4. Select controlling fieldbus
Controlling Fieldbus (P5.13.1)
Main Menu > I/O and Hardware > Fieldbus General > Controlling Fieldbus >
Automatic/BACnet IP/RS-485 <
5. Set up Protocol Parameters.
BACnet MS/TP parameters see Chapter 4.1
BACnet IP parameters see Chapter 4.2