User Guide

Communications Honeywell • 25
Control word bits
The Control word is composed of 32 bits. Meanings of bits are described below. Unused bits
have to be set to zero.
Table 18. Control Word bits
2004
2055 = High data
2056 = Low data
FB Process Data In 1 See chapter 9
2005
2057 = High data
2058 = Low data
FB Process Data In 2 See chapter 9
2006
2059 = High data
2060 = Low data
FB Process Data In 3 See chapter 9
2007
2061 = High data
2062 = Low data
FB Process Data In 4 See chapter 9
2008
2063 = High data
2064 = Low data
FB Process Data In 5 See chapter 9
2009
2065 = High data
2066 = Low data
FB Process Data In 6 See chapter 9
2010
2067 = High data
2068 = Low data
FB Process Data In 7 See chapter 9
2011
2069 = High data
2070 = Low data
FB Process Data In 8 See chapter 9
* . In drive, the Control Word and the Status Word are formed of 32 bits.
Only the initial 16 bits can be read in the 16-bit area.
Bit Name Value = 1 Value = 0 Description
B0 Start/Stop Start request Stop request
Start/Stop command to
application
B1 Direction Reverse Forward
Command to change
rotational direction
B2 Fault reset Reset faults No action Command to reset fault
B3-B31 Not used
Address
Name Range/Type
16-bit
*
32-bit
Table 17. Fieldbus Process Data IN