® INTELLIKNIGHT 5820XL Addressable Fire System Installation and Operations Manual Part Number 151209 Rev R ECN 09- 570 08/27/09
Installation Procedure Adherence to the following will aid in problem-free installation with long-term reliability: Installation Precautions - Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing.
Installation Manual FACP operation and reliability depend upon proper installation. While installing a fire alarm system may make lower insurance rates possible, it is not a substitute for fire insurance! An automatic fire alarm system - typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification capability - can provide early warning of a developing fire.
Contents Section 1 Introduction .............................................................................................................................................. 1-1 1.1 Overview of Basic System ....................................................................................................................... 1-1 1.1.1 Hardware Features ............................................................................................................................ 1-1 1.1.2 Software Features ..
IntelliKnight 5820XL Installation Manual Section 4 Control Panel Installation ...................................................................................................... 4-1 4.1 Mounting the Control Panel Cabinet ....................................................................................................... 4-1 4.1.1 Preventing Water Damage ................................................................................................................ 4-1 4.1.
Contents 4.13.5 Auxiliary Power Installation ........................................................................................................... 4-39 4.13.5.1 Door Holder Power .............................................................................................................. 4-39 4.13.5.2 Constant Power .................................................................................................................... 4-39 4.13.5.3 Resettable Power ......................................
IntelliKnight 5820XL Installation Manual 6.4.1 Entering & Exiting the Program Menu ........................................................................................... 6-11 6.4.1.1 Moving through the Menus .................................................................................................. 6-11 6.4.1.2 Selecting Options and Entering Data ................................................................................... 6-12 6.4.1.3 Editing Keys ........................................
Contents 7.6.3.1 Assigning a Name to Points ................................................................................................. 7-27 System Options ...................................................................................................................................... 7-27 7.7.1 Reporting Account .......................................................................................................................... 7-28 7.7.1.1 Edit Accounts ...................................
IntelliKnight 5820XL Installation Manual 7.10 Access Codes ......................................................................................................................................... 7-47 7.10.1 Profile Edit Menu ............................................................................................................................ 7-48 7.10.1.1 Edit Name ............................................................................................................................ 7-48 7.10.
Contents 8.7.2 Double Interlock Zone Releasing ................................................................................................... 8-16 Conditions Required for a Pre-Alert Output Activation ...................................................... 8-16 Conditions Required for a General Alarm Output Activation ............................................. 8-16 Conditions Required for a Release Output Activation ......................................................... 8-16 8.
IntelliKnight 5820XL Installation Manual 8 151209
Section 1 Introduction The IntelliKnight 5820XL Fire Alarm Control/Communicator is an addressable fire control system that meets the requirements of UL 864. 1.1 Overview of Basic System The IntelliKnight 5820XL base system is packaged as an assembled stack of 3 circuit boards mounted to an aluminum housing. 1.1.1 • • • • • • • • • • • • • • Hardware Features The IntelliKnight 5820XL panel has one signaling line circuit (SLC).
IntelliKnight 5820XL Installation Manual 1.1.2 Software Features • 125 software zones, 250 output groups. • Advanced smoke detector features: Automatic drift compensation Maintenance alert region Point status eliminates calibrated smoke test requirements for NFPA 72 • “JumpStart” feature for easy programming • Non-volatile event history stores 1000 events • A choice of output patterns available for notification outputs, including ANSI 3.
Introduction 1.3 Compatible Products Table 1-2 lists the products available from Silent Knight for use with the IntelliKnight 5820XL. Table 1-2: 5820XL Compatible Products Type of Device Model Description Addressable See Section 5.2 for a list of compatible devices. SLC Devices Other Modules 5815XL SLC Expander Allows an additional 127 Hochiki SLC devices, or 99 SK detectors and 99 SK modules to be added to the system. Up to three 5815XLs per system.
IntelliKnight 5820XL Installation Manual The following modems have been tested by Silent Knight for compatibility with the 5820XL and the Silent Knight Software Suite software packages: Table 1-3: Compatible Modems Manufacturer US Robotics Model 28.8 LifeStyle Motorola 28.8, 3400 series Premier 33.6 MultiTech 1.4 MT19321ZDX How to Contact Silent Knight If you have a question or encounter a problem not covered in this manual, contact Silent Knight Technical Support at 800-446-6444.
Introduction Limitations of Fire Alarm Systems Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer’s recommendations, State and local codes, and the recommendations contained in Guide for the Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers.
IntelliKnight 5820XL Installation Manual • Heat detectors do not sense particles of combustion and are designed to alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Heat detectors are designed to protect property, not life. • Warning devices (including horns, sirens, and bells) may not alert people or wake up sleepers who are located on the other side of closed or partially open doors.
Introduction Requirements and recommendations for proper use of fire alarm systems including smoke detectors and other fire alarm devices: Early fire detection is best achieved by the installation and maintenance of fire detection equipment in all rooms and areas of the house or building in accordance with the requirements and recommendations of the current edition of the National Fire Protection Association Standard 72, National Fire Alarm Code (NFPA 72), the manufacturer’s recommendations, State and loca
IntelliKnight 5820XL Installation Manual 1-8 151209
Section 2 Agency Listings, Approvals, and Requirements 2.1 Federal Communications Commission (FCC) 1. The following information must be provided to the telephone company before the IntelliKnight 5820XL can be connected to the phone lines: A B C D E Manufacturer: Model Number: FCC registration number: Ringer equivalence: Type of jack: Facility Interface Codes: F Service Order Code: Silent Knight IntelliKnight 5820XL AC6USA-23901-AL-E 0.8B RJ31X Loop Start: 02LS2 Ground Start: 02GS2 9.
IntelliKnight 5820XL Installation Manual This product cannot be adjusted or repaired in the field. It must be returned to the factory for service. This equipment is not designed for use with party line service. Connection to party line service is subject to state tariffs. You may contact the state public utility commission, public service commission or corporation commission for information.
Agency Listings, Approvals, and Requirements Restricted Options: • The loss of AC signal is defaulted to 3 hours however the system allows settings from 0 30 hours. For UL certified installations this number must be set from 1 to 3 hours. • The system allows the use of non-latching spot type smoke detectors. This feature may not be used in commercial applications whereby a general alarm is sounded. It is intended for elevator recall, door holding applications, and hotel/motel room applications.
IntelliKnight 5820XL Installation Manual 2-4 151209
Section 3 Before You Begin Installing This section of the manual is intended to help you plan your tasks to facilitate a smooth installation. Please read this section thoroughly, especially if you are installing a 5820XL panel for the first time. 3.
IntelliKnight 5820XL Installation Manual 3.3 Electrical Specifications Rating Terminal # and Label Description Voltage 1 L 2 3 N 4 X 5 O 6 X 7 O 8 X 9 O 10 X 11 O 12 X 13 O 14 X 15 O 16 B 17 A 18 + 19 - 20 B 21 A 22 + 23 - 24 N.C. 25 C 26 N.O. 27 N.C. 28 C 29 N.O. *I/O 6 AC input (hot) 120 VAC, 60 Hz 2.5 A N/A Earth ground N/A N/A N/A AC input (neutral) 120 VAC 60 Hz 2.5 A N/A 24 VDC 3.
Before You Begin Installing Rating Terminal # and Label Description Voltage 37 Ring Phone Line 1 Telco Ring 38 Tip Phone Line 1 Telco Tip 39 Ring Phone Line 1 Premises Ring 40 Tip Phone Line 1 Premises Tip Current N/A 0Ω N/A 0Ω 41 Ring Phone Line 2 Telco Ring 42 Tip Phone Line 2 Telco Tip 43 Ring Phone Line 2 Premises Ring 44 Tip Phone Line 2 Premises Tip 45 SC- SLC Programming Terminal ( - ) 32 VDC 150 mA 46 SC+ SLC Programming Terminal ( + ) 32 VDC 150 mA 3.
IntelliKnight 5820XL Installation Manual Figure 3-1 Wire Routing Example 3-4 151209
Before You Begin Installing 3.5 Board Assembly Diagram On-board Annunciator To AC Chassis Mounting Nuts Chassis Mounting Nuts Key Switch Input Ground Start Relay Socket Programming Ports Figure 3-2 Model 5820XL Assembly Figure 3-2 shows the circuit boards, metal housing and annunciator that attach the 5820XL assembly to the cabinet. If you should need to remove the board assembly for repair, remove the four mounting nuts which hold the assembly in the cabinet.
IntelliKnight 5820XL Installation Manual 3.6 Calculating Current Draw and Standby Battery This section is for helping you determine the current draw and standby battery needs for your installation. 3.6.1 Current Draw Worksheet Requirements The following steps must be taken when determining 5820XL current draw and standby battery requirements. 1. You will use the Current Draw Worksheet to determine current draw and standby battery requirements.
Before You Begin Installing 3.6.2 Current Draw Worksheet for SK SLC Devices Use Table 3-1 to determine current requirements during alarm/battery standby operation when SK SLC devices are installed. You can install up 99 SK detectors per loop (396 max per panel) and 99 SK modules per loop (396 max per panel). Copy this section if additional space is required.
IntelliKnight 5820XL Installation Manual Device # of Devices Current per Device Standby Current Alarm Current Addressable SLC Modules SLC SK-Control Aux Pwr SK-Monitor SK-Minimon SK-Pull-SA SK-Pull-DA SK-Monitor-2 SK-Mon10 SK-Relay-6 Standby/ Alarm Standby/ Alarm: Standby/Alarm: (99 max/loop & 396 max/ panel)1 SK-Control-6 SK-Relay SK-Zone SK-Zone-6 0.375mA 0.375mA 1.7mA 7mA 0.375 mA mA mA mA mA mA mA Standby/Alarm: 0.75 mA Standby/Alarm: 3.5 mA Standby/Alarm: 1.45 mA Standby/ 2.
Before You Begin Installing Device # of Devices 5865-4 LED Annunciator (with reset and silence switches) 5865-3 LED Annunciator (8 max.) 5880 I/O Module 5883 Relay Interface A Auxiliary Devices3 B C D E F G H I J (32 max.) Current per Device Standby: Alarm: Standby: Alarm: Standby: Alarm: Standby: Alarm: Standby Current 35 mA 145 mA 35 mA 145 mA 35 mA 200 mA 0 mA 220 mA (22 mA per relay) Total System Current Alarm Current mA mA mA mA mA mA mA mA Refer to devices manual for current rating.
IntelliKnight 5820XL Installation Manual 3.6.3 Current Draw Worksheet for Hochiki SLC Devices Use Table 3-2 to determine current requirements during alarm/battery standby operation when Hochiki SLC devices are installed. You can install up 127 Hochiki devices per loop (508 max per panel). Copy this section if additional space is required.
Before You Begin Installing A B C D E F G H I J Device # of Devices 5824 Serial/Parallel Printer Interface 5895XL IntelliKnight Power Expander 5496 Intelligent Power Module 5865-4 LED Annunciator (with reset and silence switches) (2 max.) (8 max.) Current per Device Standby Current Alarm Current Standby/Alarm: 45 mA mA Standby/Alarm: 10 mA mA Standby/Alarm: 10 mA mA Standby: 35 mA mA Alarm: 145 mA Standby: 35 mA mA (8 max.
IntelliKnight 5820XL Installation Manual 3.6.4 Maximum Battery Standby Load Table 3-3 shows the maximum battery standby load for the 5820XL based on 24 and 60 hours of standby. The standby load calculations of line D in the Current Draw Calculation Worksheet (Table 3-1 for SK devices and Table 3-2 for Hochiki devices) must be less than the number shown in Table 3-3 for the battery size used and standby hours required * 33AH max battery size for FM (Factory Mutual) installations..
Before You Begin Installing Task See Sec. (for more info.) SLC Device Hardware Installation Perform these steps before running JumpStart. U Connect device bases to the loop. SK 5.5 Hochiki 5.3 U Set device addresses. SK 5.6 Hochiki 5.8 U Physically connect detectors to their bases. Connect relay and contact monitor modules. 5.4 & see device install instructions JumpStart JumpStart is for initial system programming. JumpStart automatically selects some options for SLC devices.
IntelliKnight 5820XL Installation Manual Task See Sec. (for more info.) U Select alarm delay options (detection characteristics) for zone. 7.4.1.2 U Select heat detector trip temperature. (JumpStart selects 150°F for heat detectors.) 7.4.1.2 Output Point Configuration Conventional notification circuits (circuits 1-6): U Enable circuits used for notification appliances through programming, if necessary. (JumpStart enables circuits 1-6 as Notification.) 7.5.
Section 4 Control Panel Installation Caution! To avoid the risk of electrical shock and damage to the unit, power should be OFF at the control panel while installing or servicing. 4.1 Mounting the Control Panel Cabinet Read the environmental specifications in Section 3.2 before mounting the control panel cabinet. This will ensure that you select a suitable location. The panel should be accessible to main drop wiring runs.
IntelliKnight 5820XL Installation Manual 4.2 AC Connection At installation, connect the AC terminals to the power source as shown in Figure 4-1. It may be necessary for a professional electrician to make this connection. The AC terminals are rated at 120 VAC, 50 or 60 Hz, 2.5A.
Control Panel Installation 4.3 Battery Connection The control panel battery charge capacity is 7.0 to 35 AH. Use 12V batteries of the same AH rating. Determine the correct AH rating as per your current load calculation (see Section 3.6). Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase the AH rating. It is recommended that you replace batteries every five years.
IntelliKnight 5820XL Installation Manual 4.3.1 RBB Accessory Cabinet The Model RBB Accessory cabinet can be used when your backup batteries requirements use backup batteries that are too large to fit into the main control panel cabinet. The RBB cabinet holds batteries up to the 35 AH size. The RBB dimensions are 16" W x 10" H x 6" D (40.64 cm W x 25.4 cm H x 15.24 cm D). 4.3.1.
Control Panel Installation 3. Run extended battery cable from control panel cabinet through conduit to RBB cabinet. See Figure 4-5. RBB Cabinet Cover Screws Conduit Coupler Conduit + - + - RBB Cabinet Cover Screws Figure 4-5 Battery Connections in the RBB Cabinet Note: Figure 4-5 is an example of how the wire connections can be routed.
IntelliKnight 5820XL Installation Manual 4.4 SBUS Wiring This section contains information on calculating SBUS wire distances and the types of wiring configurations (Class A and B). 4.4.1 Calculating Wiring distance for SBUS modules The following instructions will guide you in determining the type of wire and the maximum wiring distance that can be used with control panel SBUS accessory modules.
Control Panel Installation These cases are marked in the chart with an asterisk (*). Maximum length can never be more than 6,000 feet, regardless of gauge used. (The formula used to generate this chart is shown in the note below). Table 4-1: Wire Distances Per Wire Gauge Using Copper Wire Wiring Distance: SBUS Modules to Panel Total Worst Case Current Draw (amps) 22 Gauge 18 Gauge 16 Gauge 14 Gauge 0.100 1852 ft. 4688 ft. * 6000 ft. * 6000 ft. 0.200 926 ft. 2344 ft. 3731 ft. 5906 ft. 0.
IntelliKnight 5820XL Installation Manual Wiring Distance calculation example: Suppose a system is configured with the following SBUS modules: 2 - Module 5860 Fire Annunciator 1 - 5895XL Intelligent Power Expander 1 - 5865 LED Fire Annunciator 1 - 5824 Serial/Parallel Interface Module The total worst case current is calculated as follows: 5860 Current Draw = 2 x .100 amps = .200 amps 5895XL Current Draw = 1 x .010 amps = .010 amps 5865 Current Draw = 1 x .200 amps = .
Control Panel Installation 4.4.2 Wiring Configurations Figure 4-7 illustrates Class A wiring configuration and Figure 4-8 illustrates Class B configuration. Supervised Power Limited Caution For proper system supervision do not use looped wire under terminals marked A, B, +, and - of the SBUS device connectors. Break wire runs to provide supervision of connections.
IntelliKnight 5820XL Installation Manual 4.5 Remote Annunciator 5860 Installation The optional Model 5860 Remote Annunciator, shown in Figure 4-9, performs the same functions as the on-board annunciator. Operation is identical. Up to 8 annunciators can be added to the IntelliKnight 5820XL system. Figure 4-9 Model 5860 Remote Annunciator, Front View 5860 installation involves the following steps: 1. Make sure power is off at the panel. 2. Mount the 5860 in the desired location (see Section 4.5.1). 3.
Control Panel Installation 4.5.1 Mounting the 5860 This section of the manual describes mounting the remote annunciator. The annunciator can be flush- or surface-mounted. Figure 4-10 shows the parts of the annunciator. Instructions for disassembling and mounting appear on the following pages.
IntelliKnight 5820XL Installation Manual The 5860 comes from the factory fully assembled. You must disassemble it for mounting. To disassemble the annunciator, use a 5/64 hex wrench to remove the set screws, located on the bottom of the annunciator bezel. (See Figure 4-11 for location of the set screws.) Figure 4-11 Annunciator Back Box and Bezel Details 4.5.1.1 Flush Mounting This section of the manual describes flush mounting. You can flush-mount with or without an electrical box.
Control Panel Installation Flush Mounting with an Electrical Box The 5860 annunciator can be used with the following types of electrical boxes: 4S, singlegang, and double-gang. If an electrical box is used, the box must be 1-3/8” back from the face of the wall to accommodate the annunciator. Studs used with an electrical box must be two by fours (or larger). Figure 4-12 Placement of Electrical Box for Flush Mounting Flush Mounting Steps 1.
IntelliKnight 5820XL Installation Manual 4. After the annunciator wiring to the panel has been completed (described in Section 4.5.2), replace the electronic assembly in the back box. Place the bezel over the back box and tighten the set screws on the bezel. Figure 4-13 Flush Mounting the Back Box 4.5.1.2 Surface Mounting The 5860 can be mounted directly to a surface or can be attached to a single, double, or foursquare electrical box.
Control Panel Installation 4.5.2 Model 5860 Connection to the Panel Connect the 5860 to the panel as shown in Figure 4-14.
IntelliKnight 5820XL Installation Manual 4.6 5815XL Installation The 5815XL SLC expander lets you add 127 addressable devices. Up to three 5815XLs (adding 381 SLC devices for a total of 508 points) can be used with the system. To install the 5815XL: 1. Make sure power is off at the panel. 2. Mount the 5815XL in the 5820XL, the 5895XL cabinet, or the 5815RMK remote mounting kit. Use the standoffs located under the control panel board assembly and secure with screws provided with the 5815XL.
Control Panel Installation 4.6.1 5815XL Connection to the Panel Connect the 5815XL to the control panel as shown in Figure 4-16. After the 5815XL is connected to the panel, it must be added to the system. This programming step is described in Section 4.10.
IntelliKnight 5820XL Installation Manual 4.7 5824 Serial/Parallel Interface Module Installation The 5824 serial/parallel interface module allows you to connect a printer to the panel, so you can print a real-time log of system events, a report of detector status, and event history. Instructions for installing the 5824 appear below. The 5824 is for ancillary use only. 5824 installation involves the following steps: 1. Make sure power is off at the panel. 2.
Control Panel Installation Model 5824 (with housing) To Serial Printer To Parallel Printer Figure 4-18 Printer Connection 4.7.1 Selecting 5824 Options Configuring the 5824 includes the following steps: • Add the module to the system. JumpStart will add the module automatically (see Section 6.1). You can also add it manually (see Section 7.3.2). • Select a name, if desired (see Section 7.3.1.1). • Select options for the printer and the output port. See below.
IntelliKnight 5820XL Installation Manual Printer and Output Port Options 1. From the Installer Main Menu, select 2. Select 1 for Module. 3. Select 1 for Edit Module. 7 for Program Menu. 4. From the list that displays, select the 5824 module you want to configure. 5. Press ENTER ENTER to bypass the next two screens. A screen similar to the one shown in Figure 4-19 will display. Figure 4-19 Selecting Printer and Output Port Options 6. Select options for the printer as needed for your installation.
Control Panel Installation 4.8 5880 LED I/O Module The 5880 is an LED driver board that can be used in a wide variety of applications, including as an interface with most customized floor plan annunciator boards. The 5880 can drive up to 40 LEDs and has one PZT controller. The 5880 also has eight inputs for monitoring. The following sub-sections describe hardware installation. Refer to Section 6 for programming information. 4.8.
IntelliKnight 5820XL Installation Manual 4.8.2 FACP Connection The 5880 connects to the panel via the SBUS. Make connections as shown in Figure 4-21. After the 5880 is connected to the panel, it must be added to the system. This programming step is described in Section 4.10.
Control Panel Installation 4.8.3 LED Wiring There are four 12-pin connectors on the 5880 board for connecting LEDs. Each LED gets its power from Pin 11. Internal resistors are sized so that there is approximately 10 mA of current for each LED, no series resistors are required. LED outputs can be mapped to output circuits. See Section 6 for programming details. Wire the LEDs as shown in Figure 4-22. On connector P1, Pin 12 is an open collector output for controlling a PZT.
IntelliKnight 5820XL Installation Manual 4.8.4 Dry Contact Wiring The 8 input circuits on the 5880 board are for monitoring switch inputs-any type of switch supported by the control panel can be used with the 5880. For example, you can use a 5880 to monitor pull stations, water flow, tamper, reset, or silence switches. Wire dry contacts as shown in Figure 4-23. Notice grouping of terminals; power terminals are shared by two inputs.
Control Panel Installation 4.9 5865-3 / 5865-4 LED Annunciator Installation The 5865-3 and 5865-4 are LED annunciators. The 5865-4 has 30 mappable LEDs, remote silence and reset key switches, and a general system trouble LED. The 5865-3 has 30 mappable LEDs only. These are arranged as 15 pairs of red (typically used for alarm) and yellow (typically used for trouble) LEDs. Installation of the 5865-5 and 5865-4 is identical.
IntelliKnight 5820XL Installation Manual 4.9.1 FACP Connection The 5865 connects to the panel via the SBUS. Make connections as shown in Figure 4-25. After the 5865 is connected to the panel, it must be added to the system. This programming step is described in Section 4.10.
Control Panel Installation 4.9.2 5865 Mounting Mount the 5865-4 to a standard 4-gang electrical box. Mount the 5865-3 to a standard 3-gang electrical box. In Figure 4-26, the 5865-4 attached to a 4-gang box is used as an example. Figure 4-26 5865 Mounting Example The 5865 ships with a set of zone description labels that can be inserted into the 5865 board assembly. These labels can be used in a typewriter or can be written on by hand. Slide the labels under the plexiglass as shown in Figure 4-27.
IntelliKnight 5820XL Installation Manual 4.10 Configuring Modules This section describes how to configure any system hardware modules that have been added to the system. 4.10.1 Assigning Module IDs When installing a hardware module (such as, 5815XL, 5824, 5860, 5895XL, 5865-3 or 58654), you must use the dipswitches on the module to assign an ID# to the module. Figure 4-28 shows all possible dipswitch positions and their correlation to a numerical ID.
Control Panel Installation 4.11 Telephone Connection Connect the telephone lines as shown in Figure 4-29. The Model 7860 phone cord is available from Silent Knight for this purpose. A number of programmable options are available for customizing telephone lines. These options are described in Section 7.7. 5211 Ground Start Relay Socket Figure 4-29 Connection of Telephone Lines 4.12 5211 Ground Start Relay Note: Do not use ground start in UL installations.
IntelliKnight 5820XL Installation Manual 4.13 Flexputs™ I/O Circuits The six Flexput™ circuits are an innovative and versatile feature of the control panel. They can be used as: Class A or B notification circuits, Class A or B initiation circuits (either 2 or 4 wire detectors), or as auxiliary power (resettable, continuous, or door holder). The polarity of the Flexput terminals differs depending on whether the circuit is programmed as an input or and output circuit.
Control Panel Installation 2. Configure the circuit through programming (see Section 7.6). Alarm Polarity UL Listed EOL Model 7628 4.7 kΩ Notification Wiring Supervised Power Limited Max. Impedance: 1.5Ω Regulated 24 VDC Full Wave Rectified 27.
IntelliKnight 5820XL Installation Manual 4.13.1.2 Class A Notification Wiring You must use an appliance from the list of compatible appliances in the Appendix at the back of this manual. To install a Class A notification appliance circuit: 1. Wire the Class A notification appliances as shown in Figure 4-31. Caution For proper system supervision do not use looped wire under terminals marked O and X of the Flexput connectors. Break wire runs to provide supervision of connections. 2.
Control Panel Installation 4.13.2 Conventional Input Switch Circuits This section of the manual explains how to install conventional initiating devices for Class A (Style D) or Class B (Style B) configurations. 4.13.2.1 Class B Inputs You can connect conventional Class B switches, such as waterflow switches and pull stations, directly to the Flexput circuits of the control panel. To install a Class B switch: 1. Wire the Class B switch as shown in Figure 4-32. 2.
IntelliKnight 5820XL Installation Manual 4.13.2.2 Class A Inputs You can connect conventional Class A switches, such as waterflow switches and pull stations, directly to the Flexput circuits of the control panel. To install a Class A switch: 1. Wire the Class A switch as shown in Figure 4-33. 2. Configure the circuit through programming (see Section 7.6). Supervised Power Limited Note: Flexput circuit 5 and 6 used as an example. Any Flexput point pairing could be used.
Control Panel Installation 4.13.3 Installing 2-Wire Smoke Detectors Any compatible U.L. listed two-wire smoke detector can be used with the control panel (see Appendix A for list of compatible smoke detectors). Figure 4-34 and Figure 4-35 illustrate how to connect a UL listed 2-wire detector to the control panel. 4.13.3.1 Installing 2-Wire Class B Smoke Detectors To install a Class B two-wire smoke detector, wire as shown in Figure 4-34. Supervised Power Limited UL Listed EOL Model 7628 4.
IntelliKnight 5820XL Installation Manual 4.13.3.2 Installing 2-Wire Class A Smoke Detector To install a Class A two-wire smoke detector, wire as shown in Figure 4-35. Supervised Power Limited Note: Flexput circuit 5 and 6 used as an example. Any Flexput point pairing could be used. Figure 4-35 Two-Wire Class A Smoke Detector Connections Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is used to refer to the circuit pair.
Control Panel Installation 4.13.4 Installing 4-Wire Smoke Detectors Any compatible U.L. listed four-wire smoke detector can be used with the control panel (see Appendix A for list of compatible smoke detectors). Figure 4-34 and Figure 4-35 illustrate how to connect a UL listed four-wire detector to the control panel. 4.13.4.1 Installing a Class B 4-Wire Smoke Detector Figure 4-36 illustrates how to install a 4-wire Class B smoke detector. Conventions used for wiring 4-wire Class B loops: 1.
IntelliKnight 5820XL Installation Manual 4.13.4.2 Installing 4-Wire Class A Smoke Detectors Figure 4-37 illustrates how to install 4-wire Class A detectors. Conventions used for wiring 4-wire Class A loops: 1. Up to two Class A 4-wire loops can be connected to the control panel at once. 2. Smoke power is supplied to each Class A loop as shown in Figure 4-37.
Control Panel Installation 4.13.5 Auxiliary Power Installation Flexput Circuits 1-6 on the control panel can be used as auxiliary power circuits. The three types of auxiliary power available are: • Door Holder (see Section 4.13.5.1) • Constant (see Section 4.13.5.2) • Resettable Power (see Section 4.13.5.3) Auxiliary power circuits are power limited. Each circuit can source up to 3A (total current for all Flexput circuits must not exceed 6.0 A). To install an auxiliary power circuit: 1.
IntelliKnight 5820XL Installation Manual 4.13.5.3 Resettable Power Resettable power is typically used to power beam detectors, flame detectors and conventional 4-wire smoke detectors. For circuits selected as Resettable, 24-volt power is always present at the terminals unless a system reset occurs. If a system reset occurs, power is disconnected from the terminals for 30 seconds, then re-applied. 4.
Control Panel Installation 4.15 Remote Station Applications 4.15.1 Keltron Model 3158 Installation The control panel is compatible with Keltron Model 3158, used for direct connection to a Keltron receiver. The 3158 reports alarms, supervisories, and troubles. The steps for connecting the 3158 to the control panel. Refer to the 3158 installation instructions for complete information. 1. Wire the 3158 to the control panel as shown in the connection list and Figure 4-40. 2.
IntelliKnight 5820XL Installation Manual 4.15.2 City Box Connection Using the 5220 Module This section describes how to connect the control panel to a local energy municipal fire alarm box or “city box” as required by NFPA 72 Auxiliary Protected Fire Alarm systems for fire alarm service. The city (master) box is an enclosure that contains a manually operated transmitter used to send an alarm to the municipal communication center which houses the central operating part of the fire alarm system.
Control Panel Installation 4.15.3 NFPA 72 Polarity Reversal Note: Intended for connection to a polarity reversal circuit of a control unit at the protected premises having compatible rating. 4.15.3.1 Using the 5220 Module When the 5220 is wired and programmed for polarity reversal, it reports alarm and trouble events to a remote site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the control panel is reset.
IntelliKnight 5820XL Installation Manual 4.15.3.2 Using the 7644 Module When the 7644 is used for polarity reversal, it allows alarm and trouble events to be reported to a remote site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the control panel is reset. To install the 7644 for polarity reversal: 1. Wire the 7644 to the control panel as shown in Figure 4-43.
Control Panel Installation 4.15.4 Using the SD500-ARM Addressable Relay Module When the SD500-ARM is wired for polarity reversal, it reports alarm and trouble events to a remote site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the control panel is reset. Wire the SD500-ARM as shown in Figure 4-44. 1 kΩ Intended for Connection to a Polarity Reversal Circuit of A Remote Station Receiving Unit Having Compatible Rating.
IntelliKnight 5820XL Installation Manual 4.15.5 Using a MR-201/T Control Relay From Air Products When the MR-201/T control relay is wired for polarity reversal, it reports alarm and trouble events to a remote site. Alarms will override trouble conditions and it will not be possible to reset the remote indicator until the condition is cleared and the control panel is reset. If an alarm condition occurs, the alarm relay will close, overriding the trouble condition. Current: 15 mA max.
Control Panel Installation 4.15.6 Transmitter Activated by Dry Contacts This section describes the connection of a UL 864 listed remote station transmitter to the 5820XL FACP dry contacts. The FACP contacts must be supervised by the remote station transmitter module using end-of-line resistors (ELRs) with a value determined by the transmitter manufacturer. Power is also provided by the remote station transmitter manufacturer. Refer to the remote station transmitter manufacturer’s manual for details.
IntelliKnight 5820XL Installation Manual 4-48 151209
Section 5 Hochiki and SK SLC Device Installation Caution! To avoid the risk of electrical shock and damage to the unit, power should be OFF at the control panel while installing or servicing. 5.1 List of SK SLC Devices The following SK SLC devices can be used with the control panel. See the device installation instructions for more information (packaged with the device). Note: The control panel supports the use of either SK SLC devices or Hochiki SLC devices.
IntelliKnight 5820XL Installation Manual 5.2 List of Hochiki SLC Devices The following Hochiki SLC devices can be used with the control panel. See the appropriate section number in this manual or the device installation instructions (packaged with the device) for more information. Note: The control panel supports the use of either Hochiki SLC devices or SK SLC devices. You cannot install both SLC device types on this control panel.
Hochiki and SK SLC Device Installation 5.3 Maximum Number of Devices The 5820XL supports SK or Hochiki devices on one 5820XL system. The maximum number of devices per system varies depending on device protocol and the number of 5815XL signaling circuit loop (SLC) expanders added to the system. Device support is as follows: • SK Devices–A 5820XL system can support a total of 396 SK detectors and 396 SK modules. 99 detectors and 99 modules can be connected to the built-in SLC loop.
IntelliKnight 5820XL Installation Manual Figure 5-1 and Figure 5-2 show how wire length is determined for out-and-back tap and T-tap style wiring. Figure 5-1 Calculating wire run length for a simple out and back tap When using T-taps, the total length of all taps and the main bus must not exceed 40,000 feet. This requirement must be met in addition to the maximum distance requirements for the various wire gauges.
Hochiki and SK SLC Device Installation 5.4.2 Wiring 5815XL in Style 6 & 7 (Class A) Configuration Figure 5-3 illustrates how to wire the SLC loop for Style 6 or Style 7 Class A installations. Note: Style 6 does not use short circuit isolator devices. Figure 5-3 Class A SLC Configuration Note: No t-taps allowed on class A SLC loops. Caution For proper system supervision do not use looped wire under terminals marked SLC + and – of the SLC device connectors.
IntelliKnight 5820XL Installation Manual 5.5 Wiring SK SLC Detectors This section describes how to install SK heat and smoke detectors. All detectors ship with installation instructions. Refer to the detector’s installation instructions for more detailed information.
Hochiki and SK SLC Device Installation 5.6 Addressing SK SLC Devices All SK devices are addressed using the two rotary dials that appear on the device board. Use the ONES rotary dial to set the ones place in a one or two digit number, and use the TENS rotary dial to set the tens place in a two digit number. SK device addresses are handled differently than Hochiki device addresses. The control panel recognizes when an SK detector or SK module is installed.
IntelliKnight 5820XL Installation Manual 5.7 Hochiki Detector Installation The information in this section applies to the following Hochiki models: SD505-AHS Heat Detector, SD505-AIS Ionization Smoke Detector, and SD505-APS Photoelectric Smoke Detector. Also see Section 5.8 for information on how to address the detectors. 5.7.1 Wiring Hochiki Detectors 1. Wire device bases as shown in Figure 5-6. 2. Set the address for each device as described in Section 5.8. 3.
Hochiki and SK SLC Device Installation 5.8 Addressing Hochiki Devices This section tells how to address detectors and modules. 5.8.1 SD505-APS, SD505-AHS, & SD505-AIS The SD505-APS photoelectric smoke detector, SD505-AHS heat detector, and SD505-AIS ionization smoke detector are easily addressed at the FACP. The Installer Code is required to perform this task. To address a SD505-APS, SD505-AHS, or SD505-AIS: 1. Connect a detector base temporarily to the programming terminals as shown in Figure 5-7.
IntelliKnight 5820XL Installation Manual 5.8.2 SLC Devices with Dip Switches Input and relay module addresses are set using the dip switches on the module board. The chart below shows the available addresses. For example, to select address 3, place dip switches 1 and 2 in the up position. The range of valid addresses is 1-127. 0 is an invalid address.
Section 6 Programming Overview This section of the manual is intended to give you an overview of the programming process. Please read this section of the manual carefully, especially if you are programming the control panel for the first time. The JumpStart feature automates many programming tasks and selects default options for the system. You will run JumpStart at least once when you are installing the system. See Section 6.1 for details.
IntelliKnight 5820XL Installation Manual 6.1.1 Input Points JumpStart will determine the number and type of input points (detectors or contact monitor modules) on each SLC loop. JumpStart assigns the correct detector type (heat, ionization or photoelectric), so the installer does not need to edit device type for detectors. Any contact monitor modules on the system will be assigned type "Manual Pull." The installer will need to manually change the switch type if manual pull is not correct.
Programming Overview 3. From the next menu, select 6 for JumpStart. 4. The message "WARNING Will DELETE all system options" displays on the LCD. Select Yes to continue. A series of messages displays for the next several seconds. JumpStart scans the SLC loops for devices. This can take several minutes, depending on the number of devices attached. 5. When the message, "SLC FAMILY HOCHIKI" flashes. Press installing, or press to display SK and press to accept Hochiki if to accept SK. 6.
IntelliKnight 5820XL Installation Manual 6.2 Mapping Overview This section of the manual is an overview of mapping. Details about how to select mapping options appear in the appropriate subsections in Section 7. Mapping is an important concept with the control panel. In general terms, mapping is assigning or linking events to outputs that should activate when events occur.
Programming Overview 6.2.1 Input Point Mapping Input points are assigned to input zones. Any input point can be assigned to any input zone. (Input points can be assigned to one zone only. An input point can be designated as “Unused,” which means it has not been assigned to a zone.
IntelliKnight 5820XL Installation Manual 6.2.2 Output Circuit Mapping Figure 6-3 is a simple example showing how to assign notification and relay output circuits to groups. For an example of a simple floor above/floor below application, see Figure 6-5.
Programming Overview 6.2.3 Zone Event Mapping There are 8 types of events that can occur in zones (see below). For each event type, you can activate up to 8 output groups and patterns. If it is necessary to map to more than 8 output groups, an output group template may be used (see Section 7.5.5 for information on output group templates).
IntelliKnight 5820XL Installation Manual Figure 6-5 Example of Zone Events Mapped to Output Groups and Patterns 6-8 151209
Programming Overview 6.2.4 Mapping LED Points Figure 6-6 is a simple example showing how LED points are mapped to zones and output groups. Typically you would create two output groups for each zone, one for alarms and one for troubles. (LED points are available when Models 5865-3/4 and/or 5880 are used with the system.
IntelliKnight 5820XL Installation Manual 6.3 Programming Using the 5660 Silent Knight Software Suite You can use the 5660 Silent Knight Software Suite (SKSS) to program the control panel onsite or remotely. SKSS is an optional software package that lets you easily program the control panel using a Windows-based computer and a modem* (not sold by Silent Knight). When using SKSS, you can set up the programming options for the panel, save the options in a file, then download the file to the panel.
Programming Overview 6.4.1 Entering & Exiting the Program Menu To enter Program Mode: 1. Enter the Installer Code (factory programmed default code is 5820). 2. The display prompts you to press the 6-7). or key to bring up the Main Menu (see Figure Figure 6-7 Keypad Enabled Screen 3. Then press 7 . The menu option displays. See Section 7 for detailed menu information and Section 6.5 for a quick reference listing all programmable options and JumpStart defaults.
IntelliKnight 5820XL Installation Manual 6.4.1.2 Selecting Options and Entering Data There are several ways to make programming selections using the control panel depending on which screen you are currently using. The chart below is a generic explanation. To Press Select from a menu. Enter the number of the option. Enter numeric data. Press the appropriate number on the annunciator. Enter text (alphanumeric data).
Programming Overview 6.5 Programming Menu Quick Reference This section of the manual lists all Program Menu options in the order they appear on the submenus. Default settings are indicated in text or marked with an asterisk. The comments column provide quick information and a reference to a section (if applicable) which has more detailed information.
IntelliKnight 5820XL Installation Manual Menu Options/Defaults Group Name Comments Enter Name1 Enter Number1 Enter Name2 Enter Number2 Latching Options Section 7.5.1.
Programming Overview Menu Options/Defaults Comments UNUSED DETECTOR SUP DET PHOTO ION HEAT PHOT DUCT ION DUCT 2WIRE SMK SUP PHOTO SUP ION MAN_PULL WATERFLOW SUPERVSY Select Latching Section 7.6 Select Latching LATCH NLATCH LATCH NLATCH FIREDRILL SILENCE RESET PAS_ACK Point Internal and External 5815XL Enter Pt ZN_AUX1 SWITCH ZN_AUX2 SYS_AUX1 SYS_AUX2 LATCH NLATCH LATCH NLATCH LATCH NLATCH LATCH NLATCH Section 7.
IntelliKnight 5820XL Installation Manual Menu Options/Defaults Enter Pt Select Type Input Point Type (detector/switch) UNUSED B NOTIF A NOTIF AUX PWR B SWITCH Internal Pwr and External Power Point (cont.) A SWITCH B DETECTOR A DETECTOR Select Group or Zone Number Edit Name Enter Point # 5880 Select Group # Edit Name Enter Point # 5865 6-16 Select Group # Edit Name Comments Select Function Per JumpStart Section 7.
Programming Overview Menu Options/Defaults Edit Account # Comments For each account (1-4), select: *123456 Edit Format *Contact ID Y (Yes) N (No) M (Must) Y (Yes) Rep.
IntelliKnight 5820XL Installation Manual Menu Options/Defaults Comments For each phone line (1 & 2), select: Dialing Prefix Up to 9 digits # of Answer Rings Range: 00-15 none 06 TT TT/PL Select Dialing Option Phone Lines System Options (cont.
Programming Overview Menu Options/Defaults Comments 0 - 90 Seconds *30 sec 0 - 30 hours *3 hrs Water Flow Delay Low AC Delay Misc. Options 1 DST CLK System Options (cont.) Misc. Options 2 Misc.
IntelliKnight 5820XL Installation Manual Menu Options/Defaults Comments Edit Name Edit Access Code Access Codes Select Profile (01 - 20) System Reset System Silence System Event Ack.
Section 7 Programming This section of the manual describes how to manually program the control panel from the built-in annunciator. Each subsection discusses these menu options in detail. All options described in this section can be performed using the 5660 Silent Knight Software Suite (SKSS). Important! Before any customized programming is done, JumpStart should be run first. After JumpStart is run, thoroughly test the system.
IntelliKnight 5820XL Installation Manual 7.2 SLC Family The 5820XL supports Hochiki protocol SLC devices or SK series SLC devices. You must configure the 5820XL to accept the protocol of the devices you are installing. You cannot mix SLC devices of different protocols. 1. Press or to display the main menu. 2. Enter the installer code if requested. 3. Select 7 for Program Menu. Display reads: Initializing Please wait . . . 4. Press 5. Press 6. Press 7.3 0 to enter module menu.
Programming 7.3.1 Edit Modules The features that can be edited when this option is selected are module name and class of wiring (Class A or Class B), or features that are specific to the module to be edited. To edit an existing module: 1. Enter the installer code. 2. Press 3. Select to display the main menu. or for Program Menu. 7 Display reads: Initializing Please wait . . . 4. Press 1 to enter module menu. 5. Press 1 to edit a module. 6.
IntelliKnight 5820XL Installation Manual 7.3.1.2 Setting the 5815XL Wiring Class 8. Choose the class of wiring you wish to use for this module by pressing the arrow, then press 7.3.2 or . Adding a Module If you need to add a new hardware module to the system, follow these steps. You must be in the Main Menu to perform this task. If necessary, enter the Installer Code. 1. Enter the installer code. 2. Press 3. Select or 7 to display the main menu. for Program Menu.
Programming 7.3.3 Deleting a Module If you ever need to delete a module, follow these steps. You must be in the Main Menu to perform this task. If necessary, enter the Installer Code. 1. Enter the installer code. 2. Press or 3. Select 7 to display the main menu. for Program Menu. Display reads: Initializing Please wait . . . 4. Press 1 to enter module menu. 5. Press 3 to delete a module. 6. A warning screen will display. If you want to proceed with deleting the module, select Yes.
IntelliKnight 5820XL Installation Manual 7.4.1.1 Edit Zone Name 7. Press 1 to edit the selected zone’s name. A screen similar to the one shown in Figure 7-2 displays. Figure 7-2 Selecting Character for Zone Name 8. Select the characters for the zone name by pressing the character is shown then press or arrow until the desired . OR Enter the Numerical Designator for the character you want, then press a list of available characters and their numeric designators. . See Appendix B for 9.
Programming Alarm Delay Characteristics 3. Select the alarm delay characteristics (see Table 7-1) by pressing the or arrow. Table 7-1: Alarm Delay Characteristics Type of Delay Description 1-Count One Count (No Delay). When this option is enabled, an alarm occurs immediately when a single device of any of the following types goes into alarm: detector, manual pull, water flow, Aux1 or Aux2. This is considered the most typical operation and is the default for all zones.
IntelliKnight 5820XL Installation Manual 7. Then press . 7.4.1.3 Zone Outputs Output groups and cadence patterns are mapped to events. They can be programmed to output when an event occurs in a zone. Some system trouble events can be mapped for the entire system. Section 6.2 of this manual contains a general explanation of mapping. The following sections explain how to select mapping options. Note: Use of multiple notification groups may not synchronize with each other.
Programming 8. Select options for each event that could occur in this zone. Figure 7-3 is a complete example of how you might map a zone. Indicates output group 1, cadence pattern 00 has been selected. 00 is a constant output cadence. Indicates type of event (in this case, Manual Pull alarm). See Section 6.5 for choices. “T” Indicates output group template 1. See Section 7.5.5 for more information on output group templates.
IntelliKnight 5820XL Installation Manual groups. Figure 7-4 shows how you would program this application.
Programming 7.4.1.4 Cadence Patterns The cadence patterns shown in Figure 7-5 are available for use with the control panel. Cadence patterns can be selected by event type for each zone or for the entire system. Special cadence patterns can be selected for fire drills and any auxiliary system switches used with the system. Figure 7-5 Cadence Patterns Available with the Control Panel 7.4.1.5 Zone Accessory Options This option applies to detectors that are used with SD505-6SB, SD505-6RB, and SD505-ADHRs.
IntelliKnight 5820XL Installation Manual 7.4.2 Add Zone To add a zone, follow these steps: 1. Enter the installer code. 2. Press 3. Select or 7 to display the main menu. for Program Menu. Display reads: Initializing Please wait . . . 4. Press 2 to enter zone menu. 5. Press 2 to add a zone. A zone will be added. The system will assign the next available zone number. Options for this zone can now be programmed through the Zone Edit sub-menu. Up to 125 zones can be used. 7.4.
Programming 7.4.4 View Zone Points To view the points in a zone, follow these steps: 1. Enter the installer code. 2. Press 3. Select or 7 to display the main menu. for Program Menu. Display reads: Initializing Please wait . . . 4. Press 2 to enter zone menu. 5. Press 4 to view zone points. 6. Enter the number of the zone you wish to view, then press .
IntelliKnight 5820XL Installation Manual 7.5 Group An output group is made up of output points that have been programmed to respond in the same way. Output groups simplify programming because you have to program the output characteristics that are common to all of the group points once, instead of programming each individual point. Once you have defined the characteristics of output groups, you can assign each point to the appropriate group. All valid output points are assigned to only one output group.
Programming 8. Select the characters for the zone name by pressing the character is shown then press or arrow until the desired . OR Enter the Numerical Designator for the character you want, then press . See Appendix B of this manual for a list of available characters and their numeric designators. 9. Repeat step 8 until the name is complete. 10. Press when the name is complete. 7.5.1.
IntelliKnight 5820XL Installation Manual Table 7-2: Silencing Options Option Description AUT UNSIL Auto Unsilenced. If this option is selected, the output group can be silenced for a programmed timeframe. If the condition that caused the output to activate has not cleared during the time-frame, the output reactivates. If you select this option, select the time-frame in the DLY: field. Range is 00-60 minutes. (See Figure 7-8 for location of field.) SIL-INHIB Timed Silence after Inhibit.
Programming 16. Press . 17. Enable group activation for a condition (see Table 7-3) by pressing the select Y (yes) or N (no). 18. Press or arrows to . 19. Repeat steps 14 and 15 for all the activation options. 7.5.2 Add Group To add a group: 1. Enter the installer code. 2. Press 3. Select or 7 to display the main menu. for Program Menu. Display reads: Initializing Please wait . . . 4. Press 3 to enter group menu. 5. Press 2 to add a group.
IntelliKnight 5820XL Installation Manual 7.5.4 View Group Points 1. Enter the installer code. 2. Press 3. Select to display the main menu. or 7 for Program Menu. Display reads: Initializing Please wait . . . 4. Press 3 to enter group menu. 5. Press 4 to view group points. 6. Enter the group number, then press 7.5.5 . Edit Output Group Templates Some installations may require that zones be mapped to more than 8 output groups.
Programming eight output groups. To create Output Group Templates: 1. From the Main Menu, select 7 2. From the Program Menu, select 3. At the next screen, select 5 for Program Menu. 3 for Group. for Edit OPG Template. 4. Select the template number (01 - 08). 5. Select output group number. See Figure 7-9.
IntelliKnight 5820XL Installation Manual 8. Press . 9. Select the type of device by pressing the or arrows. Refer to Table 7-5 under column heading “Type Selection” for a list of choices.
Programming Table 7-5: Point Programming Options for 5815XL Modules Type Selection Function Latching Option MAN_PULL Latching WATERFLOW Non Latching Latching SUPERVISY SWITCH FIREDRILL SILENCE Non Latching Comments Use this switch type for manual pull stations. This input is always latched. The switch can clear only when an alarm is reset. This switch type has the highest priority; it overrides any other type of alarm. Use this switch type for monitoring water flow in a sprinkler system.
IntelliKnight 5820XL Installation Manual Table 7-5: Point Programming Options for 5815XL Modules Type Selection Function ZN_AUX1 ZN_AUX2 SYS_AUX1 SWITCH (cont.
Programming Table 7-5: Point Programming Options for 5815XL Modules Type Selection SLC LED 151209 Function Latching Option Comments Select LED No.
IntelliKnight 5820XL Installation Manual 7.6.2 Point Programming For Internal or External Power Module (5895XL) To program for an internal or external power module points: 1. Enter the installer code. 2. Press 3. Select to display the main menu. or for Program Menu. 7 Display reads: Initializing Please wait . . . 4. Press 4 to enter point menu. 5. Press the choices. 6. Press or arrows to select the desired module. Refer to Section 6.5 for available . 7.
Programming Or Press to skip point name edit. 16. Repeat Steps 1 through 15 for all circuits. Table 7-6: Menu choices for Internal/External Power Module Choices Type Selections Function Selections for each Type Comments Enter Point or Circuit UNUSED B NOTIF A NOTIF AUX PWR CONSTANT Constant auxiliary power. RESETTABLE Resettable auxiliary power. DOOR Door holder auxiliary power. MAN PULL Refer to comments column of Table 7-5 for description of these options.
IntelliKnight 5820XL Installation Manual 7.6.3 Point Programming For 5880 and 5865 Modules To program 5880 or 5865 module points: 1. Enter the installer code. 2. Press 3. Select to display the main menu. or for Program Menu. 7 Display reads: Initializing Please wait . . . 4. Press 4 to enter point menu. 5. Press the choices. 6. Press or arrows to select the desired module. Refer to Section 6.5 for available . Figure 7-10 Programming Points Screen for 5880 and 5865 Modules 7.
Programming 14. Repeat Steps 1 through 13 for all points. 7.6.3.1 Assigning a Name to Points You can assign a name to a point to make it easier to recognize on a display. To edit a point name: 1. Do steps 1 through 4 in Section 7.6.3. 2. Using the or arrow, select the module of the point you want to edit, press . 3. Enter the point number. 4. Press 5. Press until the module name is blinking. . A screen similar to the one shown in Figure 7-2 displays.
IntelliKnight 5820XL Installation Manual 7.7.1 Reporting Account Up to four reporting accounts can be used with the control panel. Events in accounts are reported by zone. Each account is assigned an up-to-6-digit account number. Each account is also assigned a unique ID (1-4) which determines the priority for reporting ("1" has the highest priority; "4" has the lowest). Disable any unused accounts by selecting “N” for all events (see Figure 7-12).
Programming 7.7.1.1 Edit Accounts 6. From the next menu, select 1 for Edit Account. A screen similar to one shown in Figure 7-12 will display. The following subsections describe the options on each field. Figure 7-12 Reporting Account Editing Screen Select Account (ID) The control panel provides up to 4 reporting accounts. The priority of an account is based on its account ID. Account 1 is highest priority; Account 4 is lowest. Use Account 1 to report the highest priority events. 7.
IntelliKnight 5820XL Installation Manual Events to Report The next six options select which types of events (or event families) will be reported to this account. (See Figure 7-12 for location of these options on the screen.) Events are reported by zone. Event Family Alarms Events Included in this Family All alarms (Water Flow, Manual Pull, Detectors, Auxiliary Switches) Alarm Restore All alarm restores. Supervisory/Trouble All trouble and supervisory conditions and trouble and supervisory restores.
Programming 15. Repeat step 14 for the secondary phone line. Telephone Number Enter up to 40 characters for phone number for this account. The following special characters are available: Table 7-7: Special Character for Dialing # Pound (or number) key on the telephone * Star key on the telephone , Comma (character for 2-second pause) Use the number buttons on the annunciator or the up- and down-arrow keys to select special characters. Characters begin displaying after “9”.
IntelliKnight 5820XL Installation Manual 7.7.1.2 Auto Test Time To access the automatic dialer test time screen: 1. Enter the installer code. 2. Press 3. Select to display the main menu. or 7 for Program Menu. Display reads: Initializing Please wait . . . 4. From the Program Menu, select for System Options. 5 5. From the next menu, select 0 for Reporting Account. 6. From the next menu, select 2 for auto test time. 7.
Programming 6. Select the phone line to be edited (1 or 2) by pressing the or arrow, then press . Figure 7-13 Phone Lines Editing Screen 7.7.2.1 Dialing Prefix Enter up to 8 characters to be used for such things as PBX dial-out codes, a pause, and so on.
IntelliKnight 5820XL Installation Manual 7.7.2.2 Number of Answer Rings This option is used in conjunction with the 5660 SKSS. Use the option to determine the number of rings before the panel answers a call from the computer. Range is 00-15 rings. This option is factory-programmed as 06 rings, which should be compatible for most installations where the answering machine bypass feature is used. You may need to adjust it depending on the installation’s telephone system.
Programming disabled by default. For 5211 installation, see Section 4.12. Note: Ground start cannot be used in UL installations. 12. Select Y (ground start used monitor line) or N (ground start not used don’t monitor line) by pressing the or arrow, then press . 7.7.2.7 Answering Machine Bypass This option is used in conjunction with the 5660 SKSS. This feature ensures that an answering machine will not interfere with communication between the panel and the computer.
IntelliKnight 5820XL Installation Manual 7.7.3.1 Trouble Events You can map certain system trouble events to an output group. To access the screen for selecting output groups and cadence patterns for system trouble events. 6. Press 1 for Trouble Events. A screen similar to the one in Figure 7-14 will display. Select a group and a cadence pattern for each event as needed for your application. The U: field is for a user-specified trouble condition.
Programming 7.7.3.2 System Alarm Cadence Fire drill and system auxiliary alarm events can have special cadence patterns to distinguish them from other types of alarms. See Section 7.4.1.4 for available cadence patterns. A typical use of the System Aux1 and Aux2 patterns is to distinguish fire emergencies from other types of emergencies. The System Aux1 and Aux2 alarms would be triggered by a system-wide switch.
IntelliKnight 5820XL Installation Manual 7.7.4 Miscellaneous Options 1 Through this programming option you can set the water flow delay time, low AC report delay, enable or disable automatic daylight savings time adjustment, clock format, and AC clock frequency. 7.7.4.1 Water Flow Delay You can program a delay of 0-90 seconds (zero means no delay) to be used in conjunction with a water flow switch. The delay is system-wide. All water flow switches on the system will use the same delay period.
Programming 6. Enter the number of seconds (0 to 90 ) to delay an a water flow switch alarm, then press .
IntelliKnight 5820XL Installation Manual 7.7.4.2 Low AC Report Delay Note: You must select 1-3 hours in UL central station installations and UL remote signaling installations. You can adjust the number of hours before a Low AC report will be sent to the central station. To program low AC report delay, follow these steps: Note: Steps continued from step 6 of Section 7.7.4.1. Low AC Report Delay in Hours (00 - 30) Figure 7-17 Low AC Report Delay Programming Screen 7.
Programming 7.7.5 Miscellaneous Options 2 Through this programming option you can turn the strobe synchronization during silence feature On or Off, and select the control panel to report events by zone or by point. To edit miscellaneous options 2: 1. Enter the installer code. 2. Press 3. Select to display the main menu. or for Program Menu. 7 Display reads: Initializing Please wait . . . 4. Select 5 for System Options. 5. Select 6 for Miscellaneous Options 2. 7.7.5.
IntelliKnight 5820XL Installation Manual 7.7.6 Miscellaneous Options 3 From Miscellaneous Options 3, you set the alarm verification time, turn the Plex Door option on/off, and set the start and end week and month of Daylight Saving Time. To edit Miscellaneous Options 3: 1. Enter the installer code. 2. Press 3. Select or 7 to display the main menu. for Program Menu. 4. Enter code if prompted. Display reads: Initializing Please wait . . . 5. Select 5 for System Options. 6.
Programming 7.7.6.3 Daylight Saving Time Start and End This option lets you to adjust the week and month Daylight Saving Time (DST) starts and ends. For this feature to work, you must enable (set to Yes) the DST option under Misc. Options 1 (see Section 7.7.6.3). You can view and change the settings in this option anytime, however, settings will not take effect until 2007.
IntelliKnight 5820XL Installation Manual 7.7.7 Edit Banner Message The banner is the message that displays on the panel LCD when the system is normal, that is, when no alarms or troubles exist and no one is currently using system menus. You can create a customized message, which can be up to 40 characters, two lines of 20 characters each. If you do not create a customized message, the system will use the internal banner. You cannot change the internal banner. To customizing the banner display message: 1.
Programming 7.8 JumpStart Autoprogramming IMPORTANT! JumpStart is intended to be used prior to performing any custom programming. Each time JumpStart is executed, all options will be reset to their default values. Do not run JumpStart after you have configured the system through programming. To run JumpStart: 1. Enter the installer code. 2. Press 3. Select to display the main menu. or 7 for Program Menu. Display reads: Initializing Please wait . . . 4. Select 6 for System Options. 5.
IntelliKnight 5820XL Installation Manual 7.9 Computer Account An installer at the panel site can initiate communications between the panel and a computer running the 5660 SKSS (see also Section 8.5.16). In order for this communication to function properly both the computer (running the software) and the control panel must have matching computer account numbers and computer access codes.
Programming 7.10 Access Codes Access codes provide the user access to the control panel functions. Each access code can be customized for each user. This allows some users the ability to access programming and other higher level panel functions, while other users may only need access to lower level functions such as preforming fire drills, or acknowledging trouble conditions. Profile 1 is the profile that dictates what functions the Fire Fighter Key has access to.
IntelliKnight 5820XL Installation Manual Please wait . . . 4. Select 8 for System Options. Display reads: Select Profile 01 Fire Fighter’s Key 5. Select the access code you wish to edit by pressing the 6. Then press or arrow. . 7.10.1 Profile Edit Menu From the Profile Edit Menu you can change the users name, access code, and the panel functions that the user will have access to with their code. Note: Profile 1 (Fire Fighter’s Key) the user name and access code can not be edited.
Section 8 System Operation Operation of the control panel is simple. Menus guide you step-by-step through operations. This section of the manual is an overview of the operation menus. Please read this entire section carefully before operating the panel. Press to view Main Menu: Select the desired menu option. Enter your access code if prompted. Note: See Section 7.10 for information on how to modify user access code profiles. 8.1 User and Installer Default Codes User Code (factory-programmed as 1111).
IntelliKnight 5820XL Installation Manual 8.2.1 LCD Displays The control panel LCD displays system messages, annunciates alarms, supervisories and troubles; provides status information; and prompts for input. These messages can be up to 80 characters, displaying over four lines of 20 characters each. Annunciator keys beep when they are pressed. 8.2.
System Operation 8.4 Menu System The control panel is easy to operate from Main Menu. To view the Main Menu press the or button on the control panel or remote annunciator, then turn the firefighter’s key clockwise or enter your access code. The Main Menu will appear as shown in Section 8.4.1. Select the desired option. If you have entered a code or firefighter’s key does not have access to the menu item you have selected the following display message will appear: -Access denied.
IntelliKnight 5820XL Installation Manual 8.4.2 Using the Menus To move through the menus: Use and previous menu. To select an option: Enter the number of the option. –OR– to move through the options in a menu. Use to move to a Press ENTER (Enter key) if the option appears at the top of the menu (= symbol displays after the option number in this case). 8.5 Basic Operation 8.5.1 Setting Time and Date 1. From the Main Menu, select 4 for Set Date and Time. 2.
System Operation 8.5.4 View Event History Use the View Event History feature to display events on LCD. From the Main Menu, press to select Event History. Events will begin displaying with most recent events first. 3 The panel can store up to 1000 events. When it reaches its 1000-event capacity, it begins deleting, starting with the oldest events. If a printer is attached to the system (via a Module 5824 serial/parallel interface module), you can print event history (see Section 8.5.17).
IntelliKnight 5820XL Installation Manual 8.5.7 Conduct a Walk Test 1. From the Main Menu, press 1 for System Tests. IMPORTANT! If any alarm verification zones are being used, the user will be asked if they wish to disable alarm verification during walk test. This occurs for either walk test option. 2. Select 3 for Walk Test-No Rpt. The LCD will display “WALK TEST STOPPED” on Line 1 and “ENTER = start test” on Line 2.
System Operation 8.5.9 Silence alarms or troubles Press SILENCE and enter your code or rotate the key at the prompt. If an external silence switch has been installed, activating the switch will silence alarms or troubles. If you are already using system menus when you press SILENCE , you will not need to enter your code or rotate the key. Note: Alarm and trouble signals that have been silenced but the detector remains un-restored will un-silence every 24 hours until it is restored. 8.5.
IntelliKnight 5820XL Installation Manual 5. A screen similar to those shown in Figure 8-4 will display. Figure 8-4 Checking Detector Sensitivity Compliance If a printer is attached to the system (via a Module 5824 serial/parallel interface module), you can print detector status (see Section 8.5.17). 8.5.12 View Status of a Point 1. From the Main Menu, select 2 for Point Status. 2. From the list that displays, press ENTER to select the module where this point is located.
System Operation 8.5.16 Communicating with a Remote Computer An installer at the panel site can initiate communications between the panel and a computer running the SKSS 5660. You can use this feature to upload a panel configuration. For example, if you have made programming changes to an installation on site using an annunciator, you can send your changes to the computer, so that the central station will have the latest data about the installation. See the software manual for more information (PN 151240).
IntelliKnight 5820XL Installation Manual 8.5.17 Working with a Printer If you are using the Model 5824 serial/parallel interface module, several printing options are available. See Section 4.7 for information about installing the 5824. 1. From the Main Menu, select Printer Options. 5 2. From the next screen, select the 5824 module where the printer is connected. 3. If the printer is not currently busy printing another report, a screen with the following options will be available.
System Operation 8.6 Operation Mode Behavior The control panel can be in one of seven conditions at any given moment: Normal, Alarm, Prealarm, Supervisory, Trouble, Silenced, and Reset. Table 8-1 describes the behavior of the panel in each of these modes. Table 8-1: Operation Mode Behavior Operation Mode Normal Occurs When No alarm or trouble condition exists and menus are not in use. System Behavior In This Mode You Can SYSTEM POWER LED is on.
IntelliKnight 5820XL Installation Manual Table 8-1: Operation Mode Behavior Operation Mode Supervisory Occurs When The system detects a supervisory condition. System Behavior The dialer seizes control of the phone line and calls the central station. In This Mode You Can Press (down arrow) to view the supervisory condition. A screen similar to this one displays. The on-board annunciator sounds a loud, pulsing beep in the sequence one second on, one second off. SUPERVISORY LED flashes.
System Operation Table 8-1: Operation Mode Behavior Operation Mode Prealarm Occurs When System Behavior A single detector Touchpad PZT beeps. trips in a 2The LCD displays a screen similar to this Count zone. (2- one. Count means two detectors must trip before an alarm is reported.) In This Mode You Can Press (down arrow) to view the prealarm. A screen similar to this one displays. All system operations are available in this mode.
IntelliKnight 5820XL Installation Manual 8.7 Releasing Operations This control panel supports two types of releasing, Double Interlock Zone, and Single Interlock Zone. The Double Interlock Zone operation requires an interlock switch input in the system, and the Single Interlock does not. An interlock switch is typically a dry-contact pressure switch.
System Operation 8.7.1 Single Interlock Zone Releasing A single interlock zone utilizes a minimum of two addressable detectors and a designated manual release switch. Important! Only addressable detectors can be used. No conventional detectors can be used. Each Single Interlock Zone input requires at least one manual release switch. Conditions Required for an Pre-Alert Output Activation If any single addressable detector is activated, the “Pre-Alert” output will activate.
IntelliKnight 5820XL Installation Manual 8.7.2 Double Interlock Zone Releasing A Double Interlock Zone uses a minimum of two Addressable detectors, a designated manual release switch, and an interlock switch input. An interlock switch is typically a dry-contact pressure switch and will be referred to as an interlock/pressure switch in this document. Important! Only addressable detectors can be used. No conventional detectors can be used.
System Operation 8.8 Smoke Alarm Verification Figure 8-6 illustrates how the Smoke Alarm Verification cycle operates. Figure 8-6 Smoke Verification Cycle During the Confirmation Period if there is no alarm indication then the system will return to normal operation.
IntelliKnight 5820XL Installation Manual 8-18 151209
Section 9 Reporting This section lists receivers that are compatible with this control panel, and the reporting codes sent by the control panel for SIA and Contact ID formats. 9.1 Receivers Compatible with the Control Panel Table 9-1 shows receivers compatible with the control panel. Table 9-1: Receivers Compatible with the Control Panel Manufacturer Model Silent Knight 9.
IntelliKnight 5820XL Installation Manual SIA Reporting Format Event Family Event Class (System, Zone, or Point) Panel time has been changed Trouble System Event Local programming begin Trouble Phone line 1 trouble restore Phone line 2 trouble restore Module ID # (if any) SIA Event Code Contact ID Reporting Format Qualifier Event Code Group # Contact # JT 1 625 00 000 System Event LB 1 627 00 000 Trouble System Event LR 1 3 351 00 001 Trouble System Event LR 2 3 352 0
Reporting SIA Reporting Format Event Family Event Class (System, Zone, or Point) SLC LED Module trouble restore Trouble SLC LED Module trouble Module ID # (if any) Contact ID Reporting Format SIA Event Code Parameter (if any) Qualifier Event Code Group # Contact # Zone Event ER 0000 3 333 00 000 Trouble Zone Event ET 0000 1 333 00 000 Manual pull switch alarm Alarm Zone Event FA Zone 1 115 00 Zone Detector alarm Alarm Zone Event FA Zone 1 110 00 Zone Manual pul
IntelliKnight 5820XL Installation Manual SIA Reporting Format Event Family Event Class (System, Zone, or Point) System-based AUX2 switch alarm restore Restore Zone-based AUX1 switch trouble restore Module ID # (if any) Contact ID Reporting Format SIA Event Code Parameter (if any) Qualifier Event Code Group # Contact # Zone Event UH 2000 3 140 02 000 Trouble Zone Event UJ 1000+Zon e 3 373 01 Zone Zone-based AUX2 switch trouble restore Trouble Zone Event UJ 2000+Zon e 3 373
Reporting SIA Reporting Format Contact ID Reporting Format Event Family Event Class (System, Zone, or Point) Module ID # (if any) SIA Event Code Parameter (if any) Qualifier Event Code Group # Contact # Interlock switch trouble restore (Water Release Zone) Trouble Point Event pi Exp. ID FJ Pnt # 3 373 Exp. ID Pnt # Detector trouble restore Trouble Point Event pi Exp. ID FJ Pnt # 3 373 Exp.
IntelliKnight 5820XL Installation Manual SIA Reporting Format Contact ID Reporting Format Event Family Event Class (System, Zone, or Point) Module ID # (if any) SIA Event Code Parameter (if any) Qualifier Event Code Group # Contact # Disable Point Event pi Exp. ID SU Pnt # 3 571 Exp. ID Pnt # Supervisory/Tamper switch or Disable supervisory duct dectector re-enabled Point Event pi Exp. ID SU Pnt # 3 571 Exp. ID Pnt # Zone-based AUX1 switch alarm Alarm Point Event pi Exp.
Reporting SIA Reporting Format Event Description An unexpected SLC device has been removed 151209 Contact ID Reporting Format Event Family Event Class (System, Zone, or Point) Module ID # (if any) SIA Event Code Parameter (if any) Qualifier Event Code Group # Contact # Trouble Point Event pi Exp. ID XI Pnt # 3 380 Exp.
IntelliKnight 5820XL Installation Manual 9-8 151209
Section 10 Testing and Troubleshooting 10.1 Troubleshooting This section of the manual offers suggestions for troubleshooting hardware problems. Please read this section if you encounter a problem when installing the control panel. If these suggestions do not solve your problem or if you encounter a problem that is not listed here, contact Silent Knight Technical Support at 800-446-6444 for assistance. 10.
IntelliKnight 5820XL Installation Manual Problem SLC devices are not being recognized (trouble message "Missing" displays on the annunciator). Possible Cause / Suggested Actions Check that SLC loop impedance is within the required range. To measure impedance, use the following procedure. 1. Disconnect both wires from the terminal block at the panel (SLC devices can remain connected). 2. Measure the impedance from positive to negative and from negative to positive.
Testing and Troubleshooting 3) When necessary, activation of Notification Appliances can be prevented by the DISABLE function Testing: 1) Activate a input via an alarm initiating device and check that the correct outputs activate (Notification Appliances sound/flash, relays activate, alarm LED lights). Reset system. Repeat for each alarm initiating device. 2) Momentarily open the following circuits one at a time and check for a trouble signal: • Notification Appliance (bell) Circuits.
IntelliKnight 5820XL Installation Manual 10.3 Built-in Troubleshooting and Testing Tools The fire control panel has several built-in testing and troubleshooting tools that can be utilized to save time while testing and troubleshooting points and SLC devices. 10.3.1 SLC Device Locator SLC device locator can be used to locate a device on a SLC loop. Follow these steps to locate a particular SLC device: 1. Select 2 (Point Functions) from the Main Menu. 2. Select 4 (SLC Dev Locator).
Testing and Troubleshooting 10.3.2 SLC Multi Locator This feature is the same as SLC Device Locator, except you can locate up to 8 devices on a single search. Follow these instructions to locate multiple SLC devices: 1. Select 2 (Point Functions) from the Main Menu. 2. Select 5 (SLC Dev Locator). A message similar to the one shown in Figure 10-1 will display. Figure 10-2 Shut Down Warning 3. Press the or arrow to toggle NO to YES then press .
IntelliKnight 5820XL Installation Manual 10.3.3 I/O Point Control This feature allows you to toggle any output on or off and trip any input device. This can be useful to test a point’s output mapping. Follow these steps to control a I/O point: 1. Select 2 (Point Functions) from the Main Menu. 2. Select 6 (I/O Point Control). 3. Select the Module the point is on. 4. Enter the zone number , or press the then press 5. Press arrow to select the point you wish to test, .
Testing and Troubleshooting 10.3.4 Earth Fault Resistance Table 10-1 lists the earth fault resistance detection for each applicable terminal on the FACP.
IntelliKnight 5820XL Installation Manual 10-8 151209
Section 11 Installation Records This section of the manual is for you to use if you wish to track of how points, zones, and groups have been programmed. 11.1 SLC Point Record You can use the chart that begins below to keep track of SLC points.
IntelliKnight 5820XL Installation Manual Table 11-1: Installation Record Module Addr Zone / Group Description Module Addr On-board 49 On-board 89 On-board 50 On-board 90 On-board 51 On-board 91 On-board 52 On-board 92 On-board 53 On-board 93 On-board 54 On-board 94 On-board 55 On-board 95 On-board 56 On-board 96 On-board 57 On-board 97 On-board 58 On-board 98 On-board 59 On-board 99 On-board 60 On-board 100 On-board 61 On-board 101 On-board 62 On-
Installation Records Table 11-1: Installation Record Module Addr Zone / Group Description Module Addr 5815-1 1 5815-1 42 5815-1 2 5815-1 43 5815-1 3 5815-1 44 5815-1 4 5815-1 45 5815-1 5 5815-1 46 5815-1 6 5815-1 47 5815-1 7 5815-1 48 5815-1 8 5815-1 49 5815-1 9 5815-1 50 5815-1 10 5815-1 51 5815-1 11 5815-1 52 5815-1 12 5815-1 53 5815-1 13 5815-1 54 5815-1 14 5815-1 55 5815-1 15 5815-1 56 5815-1 16 5815-1 57 5815-1 17 5815-1 58 5815
IntelliKnight 5820XL Installation Manual Table 11-1: Installation Record Module Addr Zone / Group Description Module Addr 5815-1 83 5815-1 123 5815-1 84 5815-1 124 5815-1 85 5815-1 125 5815-1 86 5815-1 126 5815-1 87 5815-1 127 5815-1 88 5815-1 89 5815-2 1 5815-1 90 5815-2 2 5815-1 91 5815-2 3 5815-1 92 5815-2 4 5815-1 93 5815-2 5 5815-1 94 5815-2 6 5815-1 95 5815-2 7 5815-1 96 5815-2 8 5815-1 97 5815-2 9 5815-1 98 5815-2 10 5815-1 99 581
Installation Records Table 11-1: Installation Record Module Addr Zone / Group Description Module Addr 5815-2 35 5815-2 75 5815-2 36 5815-2 76 5815-2 37 5815-2 77 5815-2 38 5815-2 78 5815-2 39 5815-2 79 5815-2 40 5815-2 80 5815-2 41 5815-2 81 5815-2 42 5815-2 82 5815-2 43 5815-2 83 5815-2 44 5815-2 84 5815-2 45 5815-2 85 5815-2 46 5815-2 86 5815-2 47 5815-2 87 5815-2 48 5815-2 88 5815-2 49 5815-2 89 5815-2 50 5815-2 90 5815-2 51 5815-2
IntelliKnight 5820XL Installation Manual Table 11-1: Installation Record Module Addr Zone / Group Description Module Addr 5815-2 115 5815-3 28 5815-2 116 5815-3 29 5815-2 117 5815-3 30 5815-2 118 5815-3 31 5815-2 119 5815-3 32 5815-2 120 5815-3 33 5815-2 122 5815-3 34 5815-2 123 5815-3 35 5815-2 124 5815-3 36 5815-2 125 5815-3 37 5815-2 126 5815-3 38 5815-2 127 5815-3 39 5815-3 40 5815-3 1 5815-3 41 5815-3 2 5815-3 42 5815-3 3 5815-3 43 58
Installation Records Table 11-1: Installation Record Module Addr Zone / Group Description Module Addr 5815-3 68 5815-3 98 5815-3 69 5815-3 99 5815-3 70 5815-3 100 5815-3 71 5815-3 101 5815-3 72 5815-3 102 5815-3 73 5815-3 103 5815-3 74 5815-3 104 5815-3 75 5815-3 105 5815-3 76 5815-3 106 5815-3 77 5815-3 107 5815-3 78 5815-3 108 5815-3 79 5815-3 109 5815-3 80 5815-3 110 5815-3 81 5815-3 111 5815-3 82 5815-3 112 5815-3 83 5815-3 113 5815-
IntelliKnight 5820XL Installation Manual 11.2 Conventional Output Point Record This chart can be used to keep track of how conventional output points (circuits) have been configured.
Appendix A Compatible Devices A.1 Notification Appliances For proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL resistor on each loop. All supervised notification appliances used with the control panel must be polarized. Note: Not all devices can use the Sync feature, be sure to check Table A-1 to ensure the device you have chosen will work with this feature. This control is UL listed for panel wide Synchronization.
IntelliKnight 5820XL Installation Manual Table A-1: Compatible Notification Appliances Manufacturer Faraday A-2 Model Audio Visual Type 446 Vibrating Bell 476 Vibrating Bell 477 Single Stroke Bell 2700 -M.
Compatible Devices Table A-1: Compatible Notification Appliances Manufacturer Faraday 151209 Model Audio Visual Type 5510 Strobe 5511 Strobe 5512 Strobe 5516 Strobe 5517 Strobe 5518 Strobe 5519 Strobe 5521 4” Square Sync Strobe 5522 4” Square Sync Strobe 6120 Horn 6140 Horn 6223 Horn 6226 Horn/Strobe 6227 Horn/Strobe 6228 Horn/Strobe 6243 Electron-Mechanical Horn 6244 Electron-Mechanical Horn 6245 Electron-Mechanical Horn 6246 Electron-Mechanical Horn/Strobe 624
IntelliKnight 5820XL Installation Manual Table A-1: Compatible Notification Appliances Manufacturer FCI FCI Federal Signal A-4 Model Audio Visual Type S2415-FC Strobe S241575-FC Strobe S2430-FC Strobe 130-3117C Mini Horn 130-3147C Mini Horn BLV-6 Vibrating Bell BLV-10 Vibrating Bell BLVCH Vibrating Chime H12/24-FC Horn H12/24W-FC Horn H12/24K-FC Horn HC12/24-FC Horn HC12/24W-FC Horn HC12/24K-FC Horn P2415-FC Horn/Strobe P2415W-FC Horn/Strobe P2415K-FC Horn/Strobe
Compatible Devices Table A-1: Compatible Notification Appliances Manufacturer Gentex Gentex Model Audio Visual GEC-24-15 Horn/Strobes GEC-24-30 Horn/Strobes GEC-24-60 Horn/Strobes GEC-24-75 Horn/Strobes GEC-24-177 Horn/Strobes GEC-24-110 Horn/Strobe GEC-24-15/75 Horn/Strobe GX91 MiniHorn Steady Tone GX93 MiniHorn Temporal Tone HG124 Horn HS24-15 Horn/Strobe HS24-30 Horn/Strobe HS24-60 Horn/Strobe HS24-75
IntelliKnight 5820XL Installation Manual Table A-1: Compatible Notification Appliances Manufacturer Model Visual Type CHR Chime CHW Chime CHSR 2-Wire Chime/Strobe CHSW 2-Wire Chime/Strobe HR Horn HW Horn HRK Horn P2R 2-Wire Horn/Strobe P2R-P 2-Wire Horn/Strobe PC2R 2-Wire Horn/Strobe PC2R-P 2-Wire Horn/Strobe P2RH 2-Wire Horn/Strobe High Candela P2RH-P 2-Wire Horn/Strobe High Candela PC2RH 2-Wire Horn/Str
Compatible Devices Table A-1: Compatible Notification Appliances Manufacturer Audio Visual System Sensor PC4W 4-Wire Horn/Strobe P4WH 4-Wire Horn/Strobe High Candela PC4WH 4-Wire Horn/Strobe High Candela P4RK 4-Wire Horn/Strobe PC4RK 4-Wire Horn/Strobe P4RHK 4-Wire Horn/Strobe High Candela PC4RHK 4-Wire Horn/Strobe High Candela PC4RH 151209 Model Type 4-Wire Horn/Strobe High Candela SR Strobe SR-P Strobe SCR Strobe SCR-P
IntelliKnight 5820XL Installation Manual Table A-1: Compatible Notification Appliances Manufacturer Wheelock Model Audio Type AH-12 Horn AH-24 Horn AH-12WP Horn Weatherproof AH-24WP AMT-241575W AMT-24MCW Horn Weatherproof Multi-Tone Horn Strobe Mutli-Tone Horn Strobe Multi-Tone Horn Strobe AMT-241575W-NYC AMT-12/24 Multi-tone Horn AMT-12/24 NYC Multi-tone Horn AS-121575W A-8 Visual Horn/Strobe NH-12/24 AS-241575W Horn/Strobe AS-24MCC
Compatible Devices Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type Wheelock CH90-24MCCH Con’t HS-24 HS4-241575W Horn/Strobe HS4-24MCW Horn/Strobe HS4-24MCWH Horn/Strobe HS4-24MCC Horn/Strobe MIZ-24S Mini Horn Strobe MultitoneHorn Strobe Multitone Horn Strobe MT-24MCW Multitone Horn Strobe MTWP-2475W Multitone Horn Strobe MT-121575W MT-241575W Horn Multitone Horn Strobe MTG-121575W Mult
IntelliKnight 5820XL Installation Manual Table A-1: Compatible Notification Appliances Manufacturer Wheelock Con’t A-10 Model Audio Visual Type RSS-121575W Strobe RSS-241575W Strobe RSS-24MCC Strobe RSS-24MCCR Strobe RSS-24MCCH Strobe RSS-24MCCHR Strobe RSS-24MCW Strobe RSS-24MCWH Strobe RSSP-121575W Strobe RSSP-241575W Strobe RSSR-2415W Strobe RSSR-2415C Strobe RSSR-2475W Strobe RSSR-2475C Strobe RSSR-24110C Strobe RSSA-2411
Compatible Devices Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type Wheelock RSSWP-24MCWH Strobe Weatherproof con’t ZRS-MCWH Strobe ZRS-24MCC Strobe ZRS-24MCCH Motor Bell MB-G10-24 Motor Bell MB-G6-12 Motor Bell MB-G10-12 Motor Bell MIZ-24-R Mini-Horn MT-12/24-R Multitone Horn MT4-12/24 Multitone Horn Strobe Multitone Horn Strobe ZRS-MCW 151209 Strobe MB-G6-24 MTWPR-24MCCH NH-12/24R Horn HSR Horn/S
IntelliKnight 5820XL Installation Manual A.2 Two-Wire Smoke Detectors Table A-2 lists two-wire smoke detectors that are compatible with the fire control panel. The table is organized by manufacturer. The columns show the number of detectors per loop that can be used. Table 1-1: 5820XL 24H Identifier Operating Voltage Range 18.5–27.4 VDC Note: The maximum number of smoke detectors per zone is determined by both the current draw and the impedance of the smoke detector.
Compatible Devices Table A-2: Compatible Two-Wire Smoke Detectors Manufacturer ESL Falcon Hochiki 151209 Model Name or Number (Base model name or number in parentheses.
IntelliKnight 5820XL Installation Manual Table A-2: Compatible Two-Wire Smoke Detectors Manufacturer System Sensor A-14 Model Name or Number (Base model name or number in parentheses.
Appendix B Special Characters Lists This section contains tables of programmable characters that may be used for device, module, and zone names or phone numbers. B.1 Characters used for Naming Table B-1 list the available character and their associated numeric designator. When programming these numbers can be entered as a short cut to using the up or down arrow keys, to select characters when naming a point or zone.
IntelliKnight 5820XL Installation Manual B-2 151209
Silent Knight Fire Product Warranty and Return Policy General Terms and Conditions • All new fire products manufactured by Silent Knight have a limited warranty period of 36 months from the date of manufacture against defects in materials and workmanship. See limited warranty statement for details. • This limited warranty does not apply to those products that are damaged due to misuse, abuse, negligence, exposer to adverse environmental conditions, or have been modified in any manner whatsoever.
Advanced Replacement Policy • Silent Knight offers an option of advance replacement for fire product printed circuit boards that fail during the first 6 months of the warranty period. These items must be returned with transportation charges prepaid and must be accompanied by a return authorization.
Limited Warranty SILENT KNIGHT warrants products manufactured by it to be free from defects in materials and workmanship for thirty-six (36) months from the date of manufacture, under normal use and service. Products are date stamped at time of manufacture. The sole and exclusive obligation of SILENT KNIGHT is to repair or replace, at its option, free of charge for parts and labor, any part that is defective in materials or workmanship under normal use and service.