User's Manual

LYNXR-I Installation and Setup Guide
- 20 -
Data Field Descriptions
Defaults (where applicable) are Indicated in bold text.
The following pages list all data fields in this Control (in numerical order). Use the blank programming form
to record the data for this installation. Note that both keypad LEDs flash while in Programming mode.
Note: Entering a number other than the one specified will give unpredictable results.
20
Installer Code
Enter 4 digits, 0-9
The Installer Code is used to enter the 4-digit Master Security
Code. See "Master Code" in the System Operation section for
procedure.
21
Quick Arm Enable
0 = do not allow quick arm
1 = allow quick arm
If enabled, security code is not required to arm the system. The
user simply presses and holds down the AWAY or STAY key to
arm.
22
Keypad Backlight Timeout
0 = no timeout; always backlight keys
1 = turn backlighting off after inactivity
This option allows the choice of either always backlighting the
keypad or turning the backlighting off after 10 seconds of
keypad inactivity.
23
Forced Bypass
0 = no forced bypass
1 = provide automatic bypass of all open (faulted) zones
All zones bypassed by this function will be displayed after the
bypass is initiated.
UL installations: must be 0 (no forced bypass)
24
RF House ID Code
00 = disable all wireless keypad usage
01-31 = House ID
The House ID identifies receivers and wireless keypads.
If a 5804BD/5804BDV Transmitter is to be used, a House ID
Code MUST be entered, and the keypad should be set to the
same ID.
25
Powerline Carrier Device (X10) House ID
0 = A 4 = E 8 = I # + 12 = M
1 = B 5 = F 9 = J # + 13 = N
2 = C 6 = G # + 10 = K # + 14 = O
3 = D 7 = H # + 11 = L # + 15 = P
Powerline Carrier Devices require a House ID. This field
identifies this House ID to the Control. The Powerline Carrier
Devices are programmed in field 80.
26
Chime by Zone
0 = no (chimes on fault of any entry/exit or perimeter
zone when Chime mode is activated
1 = yes (chimes on fault of those zones assigned to
Zone List 3 when Chime mode on)
This option allows the installer to define the specific zones
intended to chime when faulted while the system is in Chime
mode. If enabled, these zones are defined in zone list 3 (see 81
Zone List Menu Mode).
27
Real Time Clock Display
0 = do not display the time
1 = display the time
Refer to the User’s Manual for setting the clock time and date.
29
Daylight Savings Time Start/End Month
0, 0 = no daylight saving time used
1-12 = start month and end month
Enter # + 10 for 10, # + 11 for 11, and # + 12 for 12.
30
Daylight Savings Time Start/End Week
0 = disable 4 = fourth weekend
1 = first weekend of month 5 = last weekend
2 = second weekend 6 = next to last
3 = third weekend 7 = 3
rd
from last
Enter the appropriate start and end weekend of the month.
31
Single Alarm Sounding Per Zone
(per armed period)
0 = no limit on alarm sounding per zone
1 = limit alarm sounding to once per arming period for
a given zone
This field applies only to burglary zones (zone response types 1-
5, 10), and affects long range radio reporting but does not affect
central station reporting.
Note: This field applies only to the bell and does not affect
keypad sounds.
UL installations: must be 0 (no limit)
32
Fire Sounder Timeout
0 = yes, fire sounder timeout after time programmed in
field
33
1 = no fire sounder timeout; continue sounding until
manually turned off
This Control complies with NFPA requirements for temporal
pulse sounding of fire notification appliances.
Temporal pulse sounding for a fire alarm consists of the
following: 3 pulses – pause – 3 pulses – pause – 3 pulses. . .
33
Alarm Bell Timeout
0 = No timeout 2 = 8 min 4 = 16 min
1 = 4 min 3 = 12 min
This field determines whether the external sounder will shut
off after time allowed, or continue until manually turned off.
UL installations: must be set for a minimum of 4 min
(option 1)