Manual Resetting
When the circuits have broken automatically, they must be
manually reset. After the pressure returns to normal, manually
reset by depressing the manual reset button(s) firmly and
releasing. The circuit is not complete until the reset button is
released. The trip-free manual reset mechanism prevents the
limit controller from operating as an automatic controller (self-
resetting) even if the manual reset button has been tied down.
CHECKOUT
After the control has been installed and wired, test as follows:
Note the boiler pressure by checking the boiler pressure
gauge (boiler pressure should be near the middle of the
PressureTrol
®
pressure scale to perform this test properly).
Rotate the PressureTrol
®
pressure adjusting screw (see FIg.
3) until the pressure setting indicator on the front of the case
corresponds to the boiler pressure gauge reading.
The limit control should break the control circuit(s) when the
boiler pressure gauge reading equals or slightly exceeds the
PressureTrol
®
pressure setting.
If the limit control is operating properly, manually reset it and
adjust the pressure adjusting screw until the pressure setting
indicator is in line with the required limit setpoint.