Specifications

AQUATROL Zoning System
216 customer.honeywell.com 70-6910
AQ1000TN2 Non-Programmable Communicating Thermostat
The AQ1000TN2 thermostat is used to control the ambient air
temperature or floor temperature in hydronic heating applications.
It communicates with and is powered by an AQ2000 series zoning
module to provide zoning control.
2-wire polarity-insensitive non-programmable network
communicating thermostat.
Liquid crystal display with user buttons .
Outdoor, indoor and floor temperature displays.
Floor temperature sensing with minimum and maximum limits (when
used with optional AQ12C20 Slab/Floor Sensor - sold separately)
Selectable temporary and permanent backlight.
Application: Hydronic single-stage zoning heat
Network Zoning: Yes
Zones: Single or Multi-zone
Dimensions, Approximate: 2.8 in wide x 4.6 in high x 1.0 in deep
(7 cm wide x 12 cm in high x 2.5 cm deep)
Electrical Connections: Wire-clamp screw terminals
Network Bus: Low voltage, Class II, 2-wire polarity-insensitive, digital
communicating link to AQ2000 series zoning modules.
User Interface (Programming): LCD Display
User Interface (System Configuration): DIP Switches
Thermostat Type: 2-wire Communicating Thermostat
Sensor Element: Thermistor
Sensors (Floor) Used: 10 kilohm NTC thermistor at 25 C (77 F)
±0.5F (±0.3C) up to 500 ft (150 M) using 18 AWG or larger wire,
beta=3892. Lead Length: 10 ft. (3050 mm).
Mounting: Vertical Mount
Color: Premier White®
Temperature Control Mode Selections: "A" for Ambient Air, "F" for
Floor, "AF" for Ambient & Floor.
Temperatures Displayed: Indoor, Set Point, Outdoor
Temperature Display Interval: ±1.0 F (±0.5 C)
Floor Sensor Temperature Rating: -58F to 230F (-50C to 110C)
Floor Temperature Limit Range (AF Model):
40 F to 100 F (5 C to 38 C)
Outdoor Temperature Display Range: -58 F to 149 F (-50C to 65 C)
Ambient Temperature Range: 32 F to 158 F (0 C to 70 C)
Temperature Range, Storage: -20 F to 130 F (-30 C to 55 C)
Operating Humidity Range (% RH): 5 to 90% RH, non-condensing
Weight: 0.2 lb (0.1 kg)
Product Number
Setting Temperature
Range
Differential
Temperature
Terminal
Designations
Type of Control
Provided
LCD Icons Displayed
(Mode) Power Method(F) (C) (F) (C)
AQ1000TN2 40 F to 100 F 5 C to 38 C ± 1 F ±0.5 C TH, TH, Sensor,
Sensor
Proportional
Integral (PI)
Vacation Mode;
Set point;
Keypad Lock;
Comfort/Unoccupied;
Heat On
Powered (24 Vdc) by
AQ zoning module