Specifications

Aquastat Controllers
192 customer.honeywell.com 70-6910
L4008; L6008 Remote Bulb Controller
Aquastat® Controllers are immersion type devices for limiting or
regulating the temperature of liquids in boilers, storage tanks, and
other applications where temperature control is required.
Remote temperature sensing element detects and responds rapidly
to temperature changes.
Totally enclosed Micro Switch® snap-acting switch.
Visible control point scale and external adjustment screw permit
easy setting.
Horizontal or vertical mounting of the remote element into boiler,
tank, or other container.
Case mounts to a vertical surface.
Dimensions in inches (millimeters)
Case Dimensions: 5 5/8 in. high x 2 in. wide x 2 1/8 in. deep
(143 mm high x 51 mm wide x 54 mm deep)
Bulb Size: 3/8 in. x 2 7/8 in. (10 mm x 73 mm) copper
Mounting: Horizontal or Vertical
Maximum Ambient Temperature: 150 F (66 C)
Electrical Ratings
Full Load: 8A @ 120 Vac; 5.1A @ 240 Vac
Locked Rotor: 48A @ 120 Vac; 30.6A @ 240 Vac
Millivolt: 0.25 A @ 0.25 to 12 Vdc
Approvals:
Canadian Standards Association: Certified: File No. LR95329-1
Underwriters Laboratories, Inc. UL Component Recognized: File No.
MP466, Vol. 6, Sec.1, Guide No. MBPR2
SENSING
ELEMENT
CAPILLARY
3/8 (10)
1-1/4
(32)
ALTERNATE POSITION
OF SENSING ELEMENT
CAPILLARY
13/64
(5) (3)
MOUNTING
HOLE FOR
3/16 IN. (5 MM)
SCREW (3)
15/16
(24)
4-3/16
(106)
ALTERNATE POSITION
OF SENSING ELEMENT
CAPILLARY
M8823
Product Number Application
Operating
Temperature
Range
Differential
Temperature
Capillary
Length
(inch) Switching Action Includes(F) (C) (F) (C)
L4008A1015 High or Low limit 100 F to
240 F
38 C to
116 C
5 F to 30 F
adj.
3 C to 17 C
adj.
66 in. SPST, contacts break
on temperature rise.
5 1/2 ft (1.7 m) capillary
L4008A1130 High or Low limit 130 F to
270 F
54 C to
132 C
5 F to 30 F
adj.
3 C to 17 C
adj.
120 in. SPST, contacts break
on temperature rise.
Stop factory-set at 200 F (93 C);
10 ft (3.04 m) capillary
L4008B1013 Circulator 100 F to
240 F
38 C to
116 C
5 F to 30 F
adj.
3 C to 17 C
adj.
66 in. SPST, contacts make
on temperature rise.
5 1/2 ft (1.7 m) capillary
* L4008E1156 High Limit;
Manual Reset
130 F to
270 F
54 C to
132 C
Manual
Reset
Manual
Reset
66 in. SPST, contacts break
on temperature rise.
5 1/2 ft (1.7 m) capillary;
Stop factory-set at 250 F (121 C);
Heat-conductive compound
* L4008E1305 High Limit;
Manual Reset
100 F to
240 F
38 C to
116 C
Manual
Reset
Manual
Reset
66 in. SPST, contacts break
on temperature rise.
Stop factory-set at 240 F (116 C)
L4008E1313 High Limit;
Manual Reset
100 F to
200 F
38 C to
116 C
Manual
Reset
Manual
Reset
66 in. SPST, contacts break
on temperature rise.
* L6008A1192 Circulator
Control and Low
Limit
100 F to
240 F
38 C to
116 C
5 F to 30 F
adj.
3 C to 17 C
adj.
SPDT 66 in. capillary;
Stop factory-set at 240 F (116 C)
L6008A1242 Circulator
Control and Low
Limit
100 F to
200 F
38 C to
93 C
5 F to 30 F
adj.
3 C to 17 C
adj.
SPDT 66 in. capillary
* TRADELINE models • SUPER TRADELINE models