Specifications

AQUATROL Zoning System
214 customer.honeywell.com 70-6910
AQ2000 Series Replacement Control Modules
Dimensions, Approximate
AQ15000B and AQ15400B: 3 1/2 in wide x 2 1/2 in high x 4 1/4 in wide
(
9 cm wide x 94 cm high x 10.09 cm deep)
AQ15100B, AQ15200B and AQ15A00B:
7 1/8 in wide x 2 1/2 in high x 4 1/4 in deep
(
18 cm wide x 94 cm high x 10.09 cm deep)
Electrical Connections (Line Voltage): Wire-clamp screw terminals,
Maximum 2 x 14 AWG each on line voltage terminals
Control and Zoning Panel Temperature Rating: 32 F to 130 F (0 C to
55 C)
Boiler Heat Post Purge: Off, 10 seconds to 30 minutes (factory default
is 30 seconds)
Boiler (T-T) Output Rating: 24 Vac, 0.5A, 12VA
Boiler Differential: 2F to 41F (1C to 23C), or Auto (minimum 2 minutes
on time)
DHW Demand Input: External dry contacts connection only
Pump/Valve exercise: 30 seconds per 2 weeks of space heating
inactivity
Slab/Floor Sensor: Heat Demand (Thermostat R-W) Input: External
dry contacts connection only
B-B Communication Bus Terminals: Low voltage, Class II, 2-wire
polarity-insensitive, digital communicating link to other Control or
Zoning modules.
R-C Input (on Control and Zoning Modules): 24 Vac Class II (input
on Control and Zoning Modules)
Operating Humidity Range (% RH): 5 to 90% RH, non-condensing
Weight
AQ15000B: 0.5 lbs (0.23 kg)
AQ15400B: 0.7 lbs (0.3 kg)
AQ15100B, AQ15200B and AQ15A00B: 1.0 lbs (0.5 kg
Approvals:
Canadian Standards Association: CSA C/US Certified to CSA and UL
Standards, File No. LR76030
AQ2000 Series Replacement Zoning Modules
Dimensions, Approximate: 3 1/2 in wide x 2 1/2 in high x 4 1/4 in deep
(
9 cm wide x 94 cm high x 10.09 cm deep)
Electrical Connections (Line Voltage): Wire-clamp screw terminals,
Maximum 2 x 14 AWG each on line voltage terminals
Control and Zoning Panel Temperature Rating: 32 F to 130 F (0 C to
55 C)
Thermostat Compatibility: AQ1000 Series 2-wire communicating
thermostats and most digital thermostats
Zone Module Thermostat input: Low voltage, Class II, 2-wire polarity-
insensitive, digital communicating with power link to AQ1000 series
thermostat.
Zone Output Contact Rating: 120 Vac/250 Vac, 5A, 1/3 HP
B-B Communication Bus Terminals: Low voltage, Class II, 2-wire
polarity-insensitive, digital communicating link to other Control or
Zoning modules.
R-C Input (on Control and Zoning Modules): 24 Vac Class II (input
on Control and Zoning Modules)
Operating Humidity Range (% RH): 5 to 90% RH, non-condensing
Weight:
0.6 lbs (0.3 kg)
Approvals:
Canadian Standards Association: CSA C/US Certified to CSA and UL
Standards, File No. LR76030
Product Number Mixing Valve Floating Output (Com,O,C) Mixing Valve Modulating Output User Interface (Setting, Programming)
AQ15000B DIP Switches
AQ15100B 0-10 Vdc to boiler LCD Display and a 7 button Key Pad
AQ15200B 24Vac rated dry contacts 0-10 Vdc to boiler or mixing valve LCD Display and a 7 button Key Pad
AQ15400B 24Vac rated dry contacts 0-10 Vdc to mixing valve LCD Display and a 3 button Key Pad
AQ15A00B 0-10 Vdc to boiler LCD Display and a 7 button Key Pad
Product Number Type of Zoning Devices Controlled Number of Zones Controlled User Interface (Setting, Programming)
AQ15540B Zone pumps or 2-wire valves (line voltage) 4 (Non-communicating) DIP Switches
AQ15740B Zone valves with end switches 4 (Non-communicating) DIP Switches