Submittal Sheet

2
M6281, M6284, M6294 Modutrol IV™ MOTORS
63-1155—2
SPECIFICATIONS
TRADELINE
®
Models
TRADELINE models (M6284D1000, M6294D1008) are
selected and packaged to provide ease of stocking, ease of
handling, and maximum replacement value. TRADELINE
model specifications are the same as those of standard
models, unless specified otherwise. TRADELINE models
have auxiliary switch cams.
Standard Models
M6281A,F
M6284A,B,C,D,F
M6294A,B,C,D
N NNN
Control Type Suffix Letter
62 is Series 60 with A: Fixed stroke (90° or 160°),
internal feedback No auxiliary switches
potentiometer B: Fixed stroke (90° or 160°),
Torque Rating 1 auxiliary switch
8 is high torque: C: Fixed stroke (90° or 160°),
150 lb-in. at 2 auxiliary switches
standard timing D: Adjustable stroke (90° to 160°),
(60 sec. for 160°) No auxiliary switches
9 is extra high torque: F: Adjustable stroke (90° to 160°),
300 lb-in. at 2 or 4 2 auxiliary switches
minute timing
Output Drive
4 is dual-ended shaft, non-spring return
1 is single-ended shaft, non-spring return
NOTE: Some motors furnished to HVAC equipment
manufacturers have a single-ended shaft, and no
wiring box.
Electrical Ratings:
a
40 VA pilot duty, 120/240 Vac on opposite contact.
Underwriters Laboratories Inc. Listed:
File No. E4436, Guide No. XAPX.
Canadian Standards Association Certified:
General Listing File No. LR1620, Guide No. 400-E.
a
Breakaway torque is the maximum torque available to
overcome occasional large loads such as a seized damper
or valve.
Motor must not be used continuously at this rating.
b
Stalling of 2 or 4 minute motor may damage drive shaft.
Dead Weight Load on Shaft:
Power or Auxiliary End: 200 lb (90.8 kg) maximum.
Maximum Combined Load: 300 lb (136 kg).
Dimensions:
See Fig. 1.
Ambient Temperature Ratings:
Maximum: 150°F (66°C) at 25% duty cycle.
Minimum: Minus 40°F (-40°C).
Crankshaft: 3/8 in. (9.5 mm) square.
M6284, M6294 have dual-ended shaft.
M6281, M6291 have single-ended shaft.
Feedback Potentiometer:
115 ohms. TRADELINE® models are 600 ohms linear,
configurable for W902 Control or for slaving Series 90 motor.
Controller Type:
3-wire floating (Series 60)—drive open, hold, drive closed.
Internal, electrically isolated feedback potentiometer
provides indication of motor position.
Stroke:
Fixed stroke models available with 90° or 160° stroke. Other
models available with stroke field adjustable from 90° to 160°.
Start position of shaft changes with adjustment of stroke.
(Midpoint of stroke remains fixed as stroke is adjusted. Stroke
is adjusted by using cams located in wiring compartment.)
Auxiliary Switch Ratings (Amperes):
Timing Torque in lb.-in (N•m)
90° Stroke
Motors
160° Stroke
Motors
Normal
Running Breakaway
a
15 sec 30 sec 75 (8.5) 150 (17.0)
30 sec 1 min 150 (17.0) 300 (34.0)
1, 2 min
b
2, 4 min
b
300 (34.0) 600 (68.0)
M6281, M6284, M6294
Voltage
(V at 50/
60 Hz)
Current
Draw (A)
Power
Consump-
tion (W)
Without Transformer
a
24 0.69 15
With Internal
120 0.21 20
Transformer
208 0.12 20
240 0.11 20
a
Internal transformer can be field added.
Maximum Damper Rating:
B dim
Motor Torque lb-in. in. mm
75 100 2540
150 202 5131
300 258 6553
One Contact Rating
a
Amps 120V 240V
Full Load 7.2 3.6
Locked Rotor 43.2 21.6