Install Instructions

62-0201 B.B. 8-03 7157 676 www.honeywell.com
M6410A, M7410F NON-SPRING RETURN ACTUATORS
Automation and Control Solutions
Honeywell International Inc. Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Scarborough, Ontario
M1V 4Z9
Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.
Fig. 3. Removing protective cover from valve.
Fig. 4. Mounting actuator to valve.
NOTE: Two-way 1, 1-1/4, 1-1/2 in. valve operation is
identical to three-way valve operation.
Fig. 5. M6410A used with T6984F.
Fig. 6. M7410F used with T7984F.
Fig. 7. Electrical installation showing wire colors
and definitions.
Switch Selection (M7410F)
The two built-in selector switches must be set according
to the valve type (two-way or three-way) and the
controller output signal (0 to 10V or 2 to 10V). See Fig. 8.
Fig. 8. Switch selection according to controller
output signal and valve type (two-way or three-way)
[1, 1-1/4, 1-1/2 in. valves shown].
M19625
M5292C
DIRECTION OF ACTUATOR STEM
OPERATION OF TWO-WAY VALVE
OPERATION OF PORT A-AB
OF THREE-WAY VALVE
OPENING
CLOSING
CLOSING
OPENING
OPEN
CLOSE
24 VAC
0 VAC
T6984F
M6410
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
M19616
OPEN
CLOSE
COMMON
L1
(HOT)
L2
1
OUTPUT
CHANGEOVER
24 VAC
0 VAC
T
7984
F
M
7410
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
M19617
INPUT (2-10V)
24 VAC
COMMON
SENSOR
INPUT
CHANGEOVER
CONTACT
L1
(HOT)
L2
1
0 VAC
M822
2
1 = RED = COM ( )
2 = BLUE = (0/2 ...10V
)
3 = WHITE = 24V
M19627
100% (10V)
0% (0V)
A
INLET
OUTLET
AB
B
100% (10V)
0% (2V)
0V ... 10V 100% ...0%
V5852A, V5862A
(1, 1-1/4, 1-1/2 IN.)
V5853A, V5863A
INPUT = 0V ... 10V
2V ... 10V
0% ... 100%
INPUT = 2V ... 10V
LEFT SWITCH
RIGHT SWITCH