Submittal Sheet

SPECIFICATION DATA
63-1313
N05 Series
Non-Spring Return
Direct Coupled Actuators
MN6105, MN7505
N314
MN6105, MN7505 Non-Spring Return Direct Coupled
Actuators (DCA) are used within heating, ventilating, and air-
conditioning (HVAC) systems. They can drive a variety of
quarter-turn, final control elements.
Applications include:
Volume control dampers, mounted directly to the drive
shaft or remotely (with the use of accessory hardware).
Quarter-turn rotary valves, such as ball or butterfly valves
mounted directly to the drive shaft.
Linear stroke globe or cage valves mounted with linkages
to provide linear actuation.
FEATURES
Access cover to facilitate connectivity.
Declutch for manual adjustment.
Mechanical end limits.
Field-installable auxiliary switches.
Rotation direction selectable by switch.
Mountable in any orientation.
UL listed.
SPECIFICATIONS
Torque Ratings:
44 lb-in. (5 Nm).
Electrical Ratings:
See Table 1.
Electrical Connections:
Field wiring 14 to 22 AWG (2.0 to 0.344 mm sq) to screw
terminals, located under the removable access cover.
Stroke:
95° ±3°.
Controller Type:
See Models.
Input Impedance: 95K ohms minimum for MN7505.
Feedback Signal: 0 or 2-10 Vdc for MN7505.
Driving Current: 3 mA minimum for MN7505.
Timing (At Rated Torque and Voltage):
Drive Open (typical): 90 seconds.
Temperature Ratings:
Ambient: -5°F to 140°F (-20°C to 60°C).
Shipping and Storage: -22°F to 176°F (-30°C to 80°C).
Humidity Ratings:
5% to 95% RH noncondensing.
Design Life (at Rated Voltage):
60,000 full stroke cycles; 1,500,000 repositions.
End Switches (Two SPDT):
Settings (fixed): 5° nominal stroke, 85° nominal stroke.
Class II circuits only.
Dimensions:
See Fig. 1.
Device Weight:
1 lb (0.45 kg).
Mounting:
Self-centering shaft adapter (shaft coupling).
Round Damper Shafts: 3/8 to 5/8 in. (9 to 16 mm).
Square Damper Shafts: 1/4 to 1/2 in. (6 to 13 mm).
Actuator can be mounted with shaft in any position.
Minimum Damper Shaft Length:
1-5/8 in. (41 mm); 3 in. (76 mm) recommended.
Noise Rating at 1m (Maximum):
35 dB(A) max at 1 m.
Environmental Protection Ratings:
NEMA2 IP54.
Models
Approvals:
UL/cUL.
UL873 Plenum Rating, File No. E4436; Guide No. XAPX.
•CE.
M Electrical Motor
N Fail Safe Function (Non-Spring Return)
61 24 Vac Floating, Two-Position Control; Reversible Mount
75 24 Vac Modulating
05 44 lb-in. (5 Nm)
A Standard U.S. Model
1 No Feedback
2 Voltage Feedback Signal
0 No End Switches
2 Two End Switches
XX System Controlled Numbers
MN61 05A10XX

Summary of content (2 pages)