Install Instructions

MP953C-F PNEUMATIC ACTUATORS
CHECKOUT AND TEST
If the valve will not seat properly:
1.
Check for incorrect stem height.
2.
If necessary, adjust the stem button for proper close-off.
3.
If stem height is correct and actuator installed correctly,
but the valve continues to seat improperly, run a check
of the valve. (See instructions provided with the valve.)
4.
If the valve operates correctly independent of the actua-
tor, but still will not seat properly, replace the actuator.
Positive Positioner Adjustment
1.
Set start point on positioner to value in job drawings.
NOTE: Each click of the start-point knob adjusts the
start point 1/4 psi (1.7 kPa).
2.
To lock the start point, tighten the start-point locking
setscrew with a 5/64 in. Allen wrench. (See Fig. 7.)
NOTES:
1. Only the most critical applications require fine tuning
the start point.
2. The range can be changed by replacing the
feedback spring. See Table 1 for feedback spring
details.
POSITIVE POSITIONER BACK VIEW
10
86
4
12
.6.4
.2
.8
START POINT
LOCKING SCREW
2
M17344
Fig. 7. Positive Positioner Start-Point Locking Screw.
Positive Positioner Adjustment Check
1.
Install gages in the main and pilot air lines.
2.
Slowly apply pilot pressure and note the pressure at
which the valve stem travel starts.
NOTE: This pressure should be within 3/4 psi (4 kPa)
of the start-point setting.
3.
Slowly increase pilot pressure until valve stem travel is
complete.
NOTE: This pressure should be within 3/4 psi (4 kPa)
of the start-point pressure plus range setting.
4.
Make fine adjustments, if necessary, with the start-point
adjustment knob.
Table 1. Positioner Feedback Springs.
Model
Stroke in
in. (mm)
Operating Span
in psi (kPa)
Spring Part
Number
MP953E 3/4 (19) 3 (20) 14004006-001
5 (35) 14004007-001
10 (70) 14004008-001
1-1/2 (38) 3 (20) 14004009-001
5 (35) 14004010-001
10 (70) 14004011-001
MP953F 3/4 (19) 3 (20) 14004018-001
5 (35) 14004017-001
10 (70) 14004016-001
Home and Building Control Home and Building Control Honeywell Asia Pacific Inc.
Honeywell Inc. Honeywell Limited-Honeywell Limitée Room 3213-3225
Honeywell Plaza 155 Gordon Baker Road Sun Hung Kai Centre
P.O. Box 524 North York, Ontario No. 30 Harbour Road
Minneapolis, MN 55408-0524 M2H 3N7 Wanchai
Hong Kong
Honeywell Latin American Region Honeywell Europe S.A.
480 Sawgrass Corporate Parkway 3 Avenue du Bourget
Suite 200 1140 Brussels
Sunrise FL 33325 Belgium
Printed in U.S.A. on recycled
95-6044EF B.B. 1-00
paper containing at least 10%
www.honeywell.com
post-consumer paper fibers.