INSTALLATION INSTRUCTIONS
62-0274-03
S03, S05 Series Spring Return
Direct Coupled Actuators
MS8103, MS4103, MS7503, MS7403, MS8105,
MS4105, MS7505, MS7405
N314
MS8103, MS4103, MS7503, MS7403, MS8105, MS4105,
MS7505, MS7405 Spring Return Direct Coupled Actuators
(DCA) are used within heating, ventilating, and air-condition-
ing (HVAC) systems. They can drive a variety of quarter-turn,
final control elements requiring spring return fail-safe
operation.
Applications include:
Volume control dampers, mounted directly to the drive
shaft or remotely (with the use of accessory hardware).
Quarter-turn rotary valves, such as ball or butterfly valves
mounted directly to the drive shaft.
Linear stroke globe or cage valves mounted with linkages
to provide linear actuation.
SPECIFICATIONS
Models:
See Table 1.
Device Weight:
3.5 lbs (1.60 kg)
Ambient Operating Temperature:
-40° to 150°F (-40° to 65°C)
-22° to 150°F (-30° to 65°C) (Two position only)
Shipping and Storage Temperature:
-40° to +150°F (-40° to +65°C) for 24 hours
Table 1. Models.
OS# Torque Control Signal Power Supply and Frequency Switch
Drive
Timing
VA
Driving
MS8103A1030/U 27 lb-in (3 Nm) Two Position SPST 24Vac @ 50/60 Hz, +/-20% 24Vdc +/-10% 0 45 sec 7 VA
MS8103A1130/U 24Vac @ 50/60 Hz, +/-20% 24Vdc +/-10% 1 45 sec 7 VA
MS4103A1030/U 120/230 Vac @ 50/60 Hz, +/-10% 0 45 sec 10 VA
MS4103A1130/U 120/230 Vac @ 50/60 Hz, +/-10% 1 45 sec 10 VA
MS7503A2030/U (0)2-10 Vdc, Floating 24Vac @ 50/60 Hz, +/-20% 24Vdc +/-10% 0 90 sec 7 VA
MS7503A2130/U 24Vac @ 50/60 Hz, +/-20% 24Vdc +/-10% 1 90 sec 7 VA
MS7403A2030/U 2-10, Floating,
Economizer (3 kOhm,
3-Position)
24Vac @ 50/60 Hz, +/-20% 24Vdc +/-10% 0 90 sec 7 VA
MS8105A1030/U 44 lb-in (5 Nm) Two Position SPST 24Vac @ 50/60 Hz, +/-20% 24Vdc +/-10% 0 45 sec 8 VA
MS8105A1130/U 24Vac @ 50/60 Hz, +/-20% 24Vdc +/-10% 1 45 sec 8 VA
MS4105A1030/U 120/230 Vac @ 50/60 Hz, +/-10% 0 45 sec 11 VA
MS4105A1130/U 120/230 Vac @ 50/60 Hz, +/-10% 1 45 sec 11 VA
MS7505A2030/U (0)2-10 Vdc, Floating 24Vac @ 50/60 Hz, +/-20% 24Vdc +/-10% 0 90 sec 8 VA
MS7505A2130/U 24Vac @ 50/60 Hz, +/-20% 24Vdc +/-10% 1 90 sec 8 VA
MS7405A2030/U 2-10, Floating,
Economizer (3 kOhm,
3-Position)
24Vac @ 50/60 Hz, +/-20% 24Vdc +/-10% 0 90 sec 8 VA