NetAXS-123 Access Control Unit Installation Guide May 2010 © 2010 Honeywell. All rights reserved.
Copyright© 2010 Honeywell. All rights reserved. All product and brand names are the service marks, trademarks, registered trademarks, or registered service marks of their respective owners. Printed in the United States of America. Honeywell reserves the right to change any information in this document at any time without prior notice. Ordering Information Please contact your local Honeywell representative or visit us on the web at www.honeywellaccess.com for information about ordering.
CONTENTS Installing the NetAXS-123 Panels 1.0 Introduction .......................................................................................................................................... 2 1.1 Access Control Overview .................................................................................................. 2 1.2 NetAXS-123 Overview...................................................................................................... 2 2.0 Panel Components and Descriptions.................
.3 RS-485 Connection via PCI-3 ......................................................................................... 50 4.4 RS-485 Connection via NetAXS-123.............................................................................. 51 4.5 RS-485 Connections with Multidrop Panels at Both Ends of the Cable ......................... 52 4.6 M-56K Dial-up Modem, RS-485 Connection via Hub (PCI-3) ...................................... 54 4.7 Fiber Converter to RS-485 Connection via PCI-3..................
LIST OF FIGURES Figure 1: NetAXS-123 Compact Enclosure Wiring and Components ....................................... 3 Figure 2: NetAXS-123 Standard Enclosure Panel Wiring and Components ............................. 4 Figure 3: NetAXS-123 Add-On Board Wiring and Components .............................................. 5 Figure 4: Typical Supervised Input Wiring Diagram ................................................................. 6 Figure 5: Wiring Readers to the Controller Board ....................
vi www.honeywell.
LIST OF TABLES Table 1: Supervised Input Terminal Blocks ................................................................................ 5 Table 2: Supervised Tamper Terminal Blocks ............................................................................ 6 Table 3: NetAXS-123 Input/Output Options .............................................................................. 7 Table 4: Readers Supported by NetAXS-123 .............................................................................
viii www.honeywell.
Installing the NetAXS-123 Panels In this chapter ...
Installing the NetAXS-123 Panels Introduction 1.0 Introduction This document describes how to install the NetAXS-123 Standard Enclosure access control unit and the NetAXS-123 Compact Enclosure access control unit. 1.1 Access Control Overview An access control system protects and preserves an enterprise’s resources by providing authentication, authorization, and administration services. Authentication is a process that verifies a user’s identity.
Installing the NetAXS-123 Panels Panel Components and Descriptions 2.0 Panel Components and Descriptions Note: This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Installing the NetAXS-123 Panels Panel Components and Descriptions Figure 2: NetAXS-123 Standard Enclosure Panel Wiring and Components Maintain at least a .25-inch distance between the non-power limited wiring (115 VAC/60 Hz input wiring, power line filter wiring, and battery backup/charger wiring) and all other wiring, which is power-limited Class 2 wiring. Note: 4 www.honeywell.
Installing the NetAXS-123 Panels Panel Components and Descriptions Figure 3: NetAXS-123 Add-On Board Wiring and Components 2.
Installing the NetAXS-123 Panels Panel Components and Descriptions Tampers can also be supervised.
Installing the NetAXS-123 Panels Panel Components and Descriptions Caution: The system has not been verified for compliance with UL1076 Burglar Alarm units and systems. 2.2 NetAXS-123 Access Control Unit The NetAXS-123 panel is a one-door access control unit that you can supplement with an add-on board that supports second and third doors.
Installing the NetAXS-123 Panels Panel Components and Descriptions 2.2.
Installing the NetAXS-123 Panels Panel Components and Descriptions Series Reader Model Honeywell Part Number OmniAssure OT30 OT30HONA OT31 OT31HONA OT35 OT35HONA OT36 OT36HONA OT70 OT70HONA OT75 OT75HONA DR 4200K 92042000000 DR 4220 92042200000 NexWatch Note: For NetAXS-123 reader specifications, see Hardware Specifications, page 60. 2.2.3 Real-Time Clock Protection The panel RTC is backed up using a super capacitor.
Installing the NetAXS-123 Panels Panel Components and Descriptions 2.4 Battery For the NetAXS-123 Standard Enclosure panel, one CASIL CA1270, 12 VDC, 7A-hour sealed lead-acid battery (Honeywell order number 3-000066). The battery provides standby backup power, depending upon system configuration and activity. When AC is lost, the power supply automatically switches to the backup battery for continuous 12VDC power. Replace the battery every 2 to 2.
Installing the NetAXS-123 Panels Installation 3.0 Installation 3.1 Installing the Compact Enclosure Panel Perform the following steps to install the NetAXS-123 Compact panel: Warning: Use a static strap whenever touching the panel to ensure protection from Electrostatic Discharge (ESD). 3.1.1 Installing on a Wall 1. Review the panel layout, cable runs, and power needs. 2. Mount the enclosure’s back at the proper location on the wall: a.
Installing the NetAXS-123 Panels Installation 3. Mount the board onto the back of the panel. 4. Choose the tamper type (standard or off-the-wall tamper) and wire the tamper. • Wiring a standard tamper: 12 www.honeywell.
Installing the NetAXS-123 Panels Installation • Wiring an off-the-wall tamper: 5. Set the tamper, using pliers at the four locations indicated below. Warning: Do not apply power at this time.
Installing the NetAXS-123 Panels Installation 6. Connect the Ethernet cable and the Tamper wire, as shown below. 7. Set DIP switch settings for the panel address, communication termination and biasing. See DIP Switch Settings, page 36. 8. Check all wiring at this time. Caution: Improper wiring can cause damage to the NetAXS-123 at power up and result in a loss of warranty. 9. Apply power to the panel. 10.Check for the Run LED for a successful power-up.
Installing the NetAXS-123 Panels Installation 3.1.2 Installing over a Gang Box 1. Review the panel layout, cable runs, and power needs. 2. Mount the back of the panel on the gang box. 3. Pull the wires from the gang box through the knockout holes in the base of the enclosure. 4. Perform steps 3 through 10 in the preceding section ( Installing on a Wall, page 11) to complete the installation of the panel over a gang box.
Installing the NetAXS-123 Panels Installation 3.1.3 Installing on a Flat Surface 1. Review the panel layout, cable runs, and power needs. 2. Mount the back of the enclosure on the surface, either with drywall screes or threaded wall anchors. 3. Break off the appropriate plastic wiring tabs, using pliers. 4. Perform steps 3 through 10 in Installing on a Wall, page 11 to complete the installation of the panel over a horizontal surface. 16 www.honeywell.
Installing the NetAXS-123 Panels Installation 3.2 Installing the Standard Enclosure Panel Perform the following steps to install the NetAXS-123 Standard Enclosure panel: Warning: Use a static strap whenever touching the panel to ensure protection from Electrostatic Discharge (ESD). 1. (Optional) Remove the green ground wire and the door. 2. Partially install the four power supply screws.
Installing the NetAXS-123 Panels Installation 3. Install the power supply. a. Fit the power supply screws through the key holes in the left side of the cabinet, and seat the power supply by pulling down. b. From the outside of the cabinet, tighten the screws to lock the power supply in place. 18 www.honeywell.
Installing the NetAXS-123 Panels Installation c. Inside the cabinet, screw in the two self-tapping screws (supplied in the product box) at the top and bottom of the power supply. Warning: These screws must be installed to ground the power supply to the enclosure.
Installing the NetAXS-123 Panels Installation d. Plug the connector that is attached to the blue and brown wires into the power supply. 20 www.honeywell.
Installing the NetAXS-123 Panels Installation 4. Select one of the following three possible entry points for the power cable: Warning: Do not apply power at this time. Be sure the power cable is disconnected from the external power source before following this step. • Through the bottom conduit knockout, which directly connects AC power to the terminal block. • Through the side conduit knockout, which also directly connects AC power to the terminal block. • Through the optional AC input receptacle.
Installing the NetAXS-123 Panels Installation 5. Use a pencil to mark the location of the holes on the wall. 6. Screw the NetAXS-123 Controller Board with the four captive screws 22 www.honeywell.
Installing the NetAXS-123 Panels Installation 7. Hold the Add-On Board over the Controller Board and seat the board-to-board connector into the Controller Board. Secure the Add-On Board onto the Controller Board with the four captive finger screws. For more explanation of the Add-On Board installation, see the next section, Installing the Add-On Board.
Installing the NetAXS-123 Panels Installation 8. Connect the wiring harness, as shown. Warning: DO NOT CONNECT the AC power or the battery wires yet! 9. Power up the NetAXS-123 Controller Board and configure the system. Refer to the NetAXS-123 Startup Guide (800-05780) for instructions. 24 www.honeywell.
Installing the NetAXS-123 Panels Installation 10.Connect the battery. 11.Attach the door to the cabinet. 12.Re-connect the green ground wire to the cabinet door.
Installing the NetAXS-123 Panels Installation 3.3 Installing the Add-On Board Warning: To prevent damage to the NXC1 Controller Board, remove power from the NetAXS-123 panel before installing or removing a NetAXS-123 Add-On Board. 1. On the NetAXS-123 Controller Board, locate the four posts called out in the image shown below: NetAXS-123 Controller Board 26 www.honeywell.
Installing the NetAXS-123 Panels Installation 2. Pick up the Add-On Board and notice the four posts on the bottom. 3. Seat the Add-On Board posts into the four posts on the NetAXS-123 Controller Board, aligning the terminal-block edge of the Add-On Board with the terminal-block edge of the Controller Board. 4. With your fingers, tighten the posts’screws.
Installing the NetAXS-123 Panels Installation 5. Set the relay jumpers. a. Use the following figure to locate the jumpers. b. See Add-On Board DIP Switch and Jumper Settings, page 40, to set the power source (12VDC power or external power) and the relay contact position (Normally Open or Normally Closed). 6. Wire the door strikes. See Wiring Door Strikes, page 33, for instructions. 28 www.honeywell.
Installing the NetAXS-123 Panels Installation 3.4 Wiring the Readers Each reader port supports one or two readers (entry and exit readers) with Wiegand output format. The maximum power draw is 500 mA for readers and AUX Power combined. To fully utilize each reader port, a shielded 7-conductor cable (18-22 AWG) is required. If you don’t need the HOLD LINE feature, you can use the standard 6-conductor cable (HAS part number NC186-BL).
Installing the NetAXS-123 Panels Installation Table 5 shows the input/output factory default wiring for a one-door configuration on the Controller Board.
Installing the NetAXS-123 Panels Installation Notes: • The Controller Board includes Inputs 7 and 8 but they are reserved for system use. • The Controller Board also includes Output 5, a general-purpose output, and Output 6, which is reserved by the system to control the boards’ RUN LEDs and thus is unavailable for user control. • Reader LED, while it is an output, should never be used to control anything other than its associated reader’s LED.
Installing the NetAXS-123 Panels Installation Table 7 lists the factory Add-On Board default settings for a door 3. These mappings should be used for the readers, inputs, and outputs when either a 1- or 2-door Add-On Board is attached to the board-to-board connector on the controller board.
Installing the NetAXS-123 Panels Installation • NetAXS-123 supports a variety of Wiegand reader models. Some readers have only one brown wire for LED control; others have two possible LED control inputs--orange for the green LED and brown for the red LED. RED is the normal state of the Reader LED operation. The LED turns GREEN for two seconds after a valid card read. Although readers operate similarly, LED control can vary, depending on the manufacturer.
Installing the NetAXS-123 Panels Installation 2. Use the following figure to wire the door strike/mag lock according to the power supply used. Be sure to use the S4 suppressor kits as shown below. On-Board +12VDC Configuration NO/NC Dry C Return NO/NC Dry C Return S4 External Power Supply Configuration OR S4 S4 S4 Locking Device Locking Device + DC DC Notes: • As shown in the illustration above, the Dry C terminal for the On-Board option should not be connected.
Installing the NetAXS-123 Panels Installation 3.6 Setting DIP Switches and Jumpers 3.6.1 Controller Board DIP Switch and Jumper Settings Figure 6 locates the NetAXS-123 DIP switch panel and the output 1 and output 3 relay jumpers.
Installing the NetAXS-123 Panels Installation DIP Switch Settings Use the following DIP switch configurations to set the panel address.
Installing the NetAXS-123 Panels Installation Table 8: NetAXS-123 SW1 DIP Switch Settings (continued) S1 S2 S3 S4 S5 S6 OFF ON ON OFF ON Address 22 ON ON ON OFF ON Address 23 OFF OFF OFF ON ON Address 24 ON OFF OFF ON ON Address 25 OFF ON OFF ON ON Address 26 ON ON OFF ON ON Address 27 OFF OFF ON ON ON Address 28 ON OFF ON ON ON Address 29 OFF ON ON ON ON Address 30 ON ON ON ON ON Address 31 S7a S8b S9b S10 Selection OFF Downstream Pan
Installing the NetAXS-123 Panels Installation b. Both DIP Switch 8 and DIP Switch 9 need to be either ON or OFF to be properly configured. Table 9: NetAXS-123 SW2 DIP Switch Settings S1a S2a Selection OFF OFF RS-485_2 termination (EOL) DISABLED ON ON RS-485_2 termination (EOL) ENABLED (FUTURE) (Default) a. Both DIP Switch 1 and DIP Switch 2 need to be either ON or OFF to be properly configured.
Installing the NetAXS-123 Panels Installation Jumper Settings The NetAXS-123 Controller Board provides two jumper sets, one each for output relay 1 and output relay 3. Each relay has two 3-pin jumpers associated with it. One jumper selects either external power (EXT) or self-whetted (on-board, +12V) power to be applied to the relay contact load. The other jumper is used to select Normally Open (NO) or Normally Closed (NC) relay contacts.
Installing the NetAXS-123 Panels Installation Note: The power source selected by the jumper settings shown above configure the power source for the relay. It does not configure the power source for the panel. • Setting the jumpers to configure the relay contact type: Normally Open Normally Closed 3.6.2 Add-On Board DIP Switch and Jumper Settings Figure 8 locates the NetAXS-123 Add-On Board DIP switch panel and the output 1 and output 3 relay jumpers.
Installing the NetAXS-123 Panels Installation used to select Normally Open (NO) or Normally Closed (NC) relay contacts. There is a total of four 3-pin jumpers (two per relay) on the controller board.
Installing the NetAXS-123 Panels Installation 3.7 Communications 3.7.1 USB Communications The NetAXS-123 Controller Board provides a version 2.0 USB port that connects to the web browser or to a WIN-PAK host. The following figure identifies the location of the port on the board. Note: USB communication requires the USB A to MicroUSB B cable that is supplied with the panel. You will need to install a USB driver to support the connection.
Installing the NetAXS-123 Panels Installation 2. Click Install USB Drivers on the product menu to start the USB driver installation wizard. 3. Click Next to display the Ready to Install the Program screen. If confirmation dialog boxes pop up before or during the installation, click the appropriate boxes to allow or approve the installation. Note: 4. Click Install to initiate the installation.
Installing the NetAXS-123 Panels Installation 5. When the installation is complete, the closing screen appears: 6. Click Finish. 7. Connect the computer to the NetAXS-123 controller with a USB-A to Micro USB-B cable. 8. Turn on the power to the NetAXS-123 controller. For login information, go to https://192.168.2.150. 3.7.2 RS-485 Communications If a NetAXS-123 panel is to be placed onto a prexisting RS-485 dropline loop (NetAXS) it must be setup as the Gateway panel.
Installing the NetAXS-123 Panels Installation DIP switch SW1 positions 8 and 9 are provided for supplying biasing and end-of-line termination for the RS-485 network. The board ships with the switches active. For a Multidrop RS-485 Line, you must turn ON both switch positions 8 and 9 of SW1. (terminated and biased) at the two end-point panels. At all other panels, set DIP switches 8 and 9 in the OFF position. Both switches on a given panel must be set the same.
Installing the NetAXS-123 Panels Installation Figure 10: RS-485 Configuration via NetAXS-123 Gateway Reader 1 Ethernet NetAXS-123 Gateway .. . Terminal RS-485 Multidrop Line .. . .. . .. . Reader 4 Reader 3 Reader 4 This configuration supports a total of 31 NetAXS and NetAXS-123 panels per Multidrop line. 46 www.honeywell.
Installing the NetAXS-123 Panels Installation 3.7.3 Ethernet TCP/IP Communications Figure 11: Ethernet TCP/IP Configuration Ethernet Network Interface Card inside PC Up to 255 TCP/IP Connections per System Terminal Reader 1 Ethernet 10/100 NetAXS-123 Gateway RS-485 Multidrop Line Reader 1 NetAXS Panel .. . Reader 4 Reader 3 Reader 1 NetAXS-123 Panel .. . .. . Reader 1 NetAXS Panel Reader 3 .. .
Installing the NetAXS-123 Panels System Configuration 4.0 System Configuration This section provides wiring diagrams for each of the NetAXS-123 system configurations. 4.1 Ethernet Connection Figure 12: Ethernet Connection NIC 100BaseT (CAT 5) 328 Ft. Max.
Installing the NetAXS-123 Panels System Configuration 4.2 USB Connection Figure 13: Note: NetAXS-123 USB Connection The USB connection is intended to be used for system maintenance and troubleshooting. You should ground each NetAXS-123 Standard (Metal) Enclosure panel individually with an Earth Ground.
Installing the NetAXS-123 Panels System Configuration 4.3 RS-485 Connection via PCI-3 This connection supports thirty-one NetAXS-123 panels for each drop line. Note that PCI-3 units can also be wired in interior, as well as in endpoint, positions. See Figure 16 on page 52 and Figure 17 on page 53. Figure 14: RS-485 Connection via PCI-3 RS-232 (50 Ft. Max.) RS-485 (4000 Ft. Max.
Installing the NetAXS-123 Panels System Configuration 4.4 RS-485 Connection via NetAXS-123 This connection supports a total of 31 NetAXS-123 panels (including the Gateway) for each drop line. Figure 15: RS-485 Connection via NetAXS-123 You should ground each NetAXS-123 Standard (Metal) Enclosure panel individually with an Earth Ground.
Installing the NetAXS-123 Panels System Configuration 4.5 RS-485 Connections with Multidrop Panels at Both Ends of the Cable You can connect Multidrop panels at both ends of an RS-485 cable via either a NetAXS-123 panel or a PCI-3 device. Figure 16: RS-485 Connection via NetAXS-123 with Multidrop Panels at Both Ends You should ground each NetAXS-123 Standard (Metal) Enclosure panel individually with an Earth Ground. Note: 52 www.honeywell.
Installing the NetAXS-123 Panels System Configuration Figure 17: RS-485 Connection via PCI-3 with Multidrop Panels at Both Ends COM Port RS-232 (50 Ft. Max.) See RS-485 Cable Note RS-485 (4,000 Ft.
Installing the NetAXS-123 Panels System Configuration 4.6 M-56K Dial-up Modem, RS-485 Connection via Hub (PCI-3) This configuration supports 31 NetAXS-123 panels for each drop line.
Installing the NetAXS-123 Panels System Configuration 4.7 Fiber Converter to RS-485 Connection via PCI-3 This connection supports 31 NetAXS-123 panels for each drop line.
Installing the NetAXS-123 Panels System Configuration 4.8 Fiber Converter to RS-485 Connection via NetAXS-123 This connection supports 31 NetAXS-123 panels for each drop line. Figure 20: Fiber Converter to RS-485 Connection via NetAXS-123 You should ground each NetAXS-123 Standard (Metal) Enclosure panel individually with an Earth Ground. Note: 56 www.honeywell.
Installing the NetAXS-123 Panels System Configuration 4.
Installing the NetAXS-123 Panels System Configuration 4.
Installing the NetAXS-123 Panels System Configuration 4.11 Mixed Loops This mixed-loop configuration supports a combined total of 31 N1000 III, N1000 IV, NetAXS, NetAXS-123, and NS2 panels per Multidrop line.
Installing the NetAXS-123 Panels Hardware Specifications 5.0 Hardware Specifications The specifications in this section apply to both the Standard Enclosure and Compact Enclosure panels. 5.1 Relay Contacts Maximum of six Form-C SPDT relays, 3A (at dry contact) or 0.5A (at self-whetted) @ 30VDC (PTC limited in the self-whetted mode). The Form-C SPDT relays are configured as Normally Open or Normally Closed outputs only. Normally Open and Normally Closed contacts cannot be used simultaneously. 5.
Installing the NetAXS-123 Panels Hardware Specifications Example: Device Element Current Door strike or magnetic lock current 250 mA Reader A maximum current 50 mA Reader B maximum current 50 mA Buzzer or sounder current 20 mA Door position switch 20 mA Request to exit switch 30 mA Total current for this example 420 mA If the total current consumption of your external devices exceeds the 450mA maximum current maximum, then use one of the following system configurations: • Power the panel wi
Installing the NetAXS-123 Panels Hardware Specifications 5.6 Environment • Temperature: 0C to 49C operating, -55C to +85C storage. • Humidity: 5% to 85% RHNC. 5.7 Cable Use industry-standard cables that meet the following specifications: Table 10: Reader Wiring Cable Specifications 62 Description AWG Maximum Distance: Feet (Meters) Readers 6 Conductor, Shielded 18 500 (153) Alarm Input Twisted Pair, Shielded 18 2,000 (610) Relay Outputs Twisted Pair, Shielded 18 2,000 (610) www.honeywell.
Installing the NetAXS-123 Panels Basic Standalone Operation 6.0 Basic Standalone Operation 6.1 Card Read / Door Lock Operation 1. Present a card to a reader. 2. The reader sends the card number to a reader input on the panel. 3. The panel searches its database and: • If it is a valid card, then energize the door relay associated with the particular reader input. The card is valid when it is in the card database on the panel and the current time and date conforms to the time zone associated with the card.
Installing the NetAXS-123 Panels Maintenance 7.0 Maintenance Perform the following maintenance on the NetAXS-123 enclosure: • Change the backup battery every two to two-and-a-half years. • Oil the lock once per year. • Use the following procedure to change the 1A, 250V, Bussan type GMA fuse in the fuse terminal block Power Supply module. Warning: Be sure to disconnect the AC power before replacing the terminal block fuse.
Installing the NetAXS-123 Panels Troubleshooting 8.0 Troubleshooting Table 11 Troubleshooting Problems and Solutions Problem Solution The panel powers up, but it does not respond to any communication, cards reads, or input activation. Ensure that the Address DIP switches are set to a value other than zero. Turn off the power (including battery), change the settings, and re-apply the power. No communications exist with the Ethernet port.
Installing the NetAXS-123 Panels Technical Support 9.0 Technical Support 9.1 Normal Support Hours Monday through Friday, 7:00 a.m. to 7:00 p.m. Central Standard Time (CST), except company holidays: (800) 323-4576. 9.2 Web For technical assistance please visit http://www.honeywellaccess.com 66 www.honeywell.
Installing the NetAXS-123 Panels Technical Support This page is left blank for printing purposes.
Honeywell Access Systems 135 W. Forest Hill Avenue Oak Creek, WI 53154 United States 800-323-4576 414-766-1798 Fax www.honeywellaccess.com Specifications subject to change without notice. © Honeywell. All rights reserved.