Water Heater User Manual
PDX SERVICE PROCEDURE VIII
Safety Circuit Voltage Trace
Safety Circuit Voltage 
Trace
WARNING
120 volt potential exposure. Use caution
making voltage checks to avoid personal injury.
Position gas control switch to the “ON” 
position and adjust thermostat dial to call 
for heat, Is there 10 to 13 VAC between red 
wire leading to blower temperature switch 
and green ground wire?
Blower must be running during this
voltage check.
(see photo 25)
Red wire leading to 
blower temp. switch
Green ground wire
25
Yellow wire
leading from 
pressure switch
Y
Is there 10 to 13 VAC between yellow wire 
leading from pressure switch and green 
ground wire?
(see photo 25)
Do you hear or can you see 
the igniter sparking?
Y
Y
Is LED on gas valve flashing the 
“heartbeat” code (alternating 
bright/dim)
N
Safety circuit 
voltage is OK.
No voltage from gas control, 
call for technical support.
Y
NOTE: This procedure assumes a cool tank.
Verify 120VAC to gas 
control (see page 30)
Is there continuity 
through blower 
temperature switch?
(see page 21)
Y
Check for loose or 
broken wire connection 
at switch terminals
N
N
Determine cause of blower 
temperature switch activation 
and correct.
Check igniter/sensor
(see page 17)
is igniter/sensor OK?
If burner does not light, 
observe LED flash code on 
gas valve and refer to 
troubleshooting section on 
page 13
N
N
Page 29
24
Step 2. Remove three screws (Phillips Screw driver) from control 
access cover on blower and remove cover (see photo 24).
Faulty cord set or 
gas control.
Y
Correct igniter/
sensor problem.
PDX Series
29