Water Heater User Manual
PDX SERVICE PROCEDURE  VI
Gas Control/Thermal Well Testing and 
Replacement
PDX Series
Thermal Well Testing
Thermal well testing
Position gas control power switch to 
the “OFF” position and disconnect 
thermal well harness from gas 
control.
N
Y
Using a multi-meter set to the ohms setting, insert one meter probe (see caution) 
into center wire position of thermal well connector, insert the second probe (see 
caution) into either of the outside wire positions (see photo 20).
Alternate the probe on the outside position to the opposite outside wire position
(see photo 21). 
Replace thermal well
(see page 27)
Using a multi-meter set to the 
Ohms setting, determine the 
resistance of thermal well sensor 
(see caution photos 20 & 21)
Disconnect thermal 
well wire harness
20
21
Replace gas control
(see page 27)
Page 24
Gas Control Testing
See pages 27 & 28 for gas control
input & output testing.
Once the thermal well resistance values are known, the water 
temperature must also be known to determine if the resistance 
values are correct. See page 25 to obtain water temperature.
Are thermal well resistance values correct?
CAUTION
DO NOT use standard multimeter probes for this test. Doing 
so will damage connector. Use special pin type electronic 
probes or small diameter wire pins inserted into connector.
If Control has gone into TCO lockout due to excessive 
tank temperature (four flash, 3 second pause) reset 
control by rotating knob of temperature control to the 
minimum setting for at least 6 seco nds before returning 
to desired temperature setting. 
Observe heater operation. If control 
continues to lockout due to excessive 
tank temperature, proceed to thermal 
well testing to determine cause.
24










