P R O -2 2 0 0 E the rne t B o a rd I ns ta lla tio n M a nua l Part Number: PRO22EN TD1145 rev0601
Contents Warnings and Cautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 Disclaimer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 Unpacking Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 Shipping Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 Confidentiality . . . . . . . . . . . . . . . . . . . . . . . . . . .
WARNINGS AND CAUTIONS WARNING Before installation, turn off the external circuit breaker which supplies power to the system. Before connecting the device to the power supply, verify that the output voltage is within specifications of the power supply. Do not apply power to the system until after the installation has been completed.
WARNING Use suppressors on all door strikes. Use S-4 suppressors for installation. Engineering Systems recommends only DC strikes. CAUTION IF ANY DAMAGE TO THE SHIPMENT IS NOTICED, A CLAIM MUST BE FILED WITH THE COMMERCIAL CARRIER RESPONSIBLE. CAUTION Electro-static discharge can damage CMOS integrated circuits and modules. To prevent damage always follow these procedures: Use static shield packaging and containers to transport all electronic components, including completed reader assemblies.
NOTICE Any use of this product is subject to the terms and acceptance of the Engineering Systems Software Agreement. Please request a copy from Engineering Systems, and review the agreement carefully. DISCLAIMER Product Liability; Mutual Indemnification In the event that a Customer receives a claim that a Product or any component thereof has caused personal injury or damage to property of others, Customer shall immediately notify Engineering Systems in writing of all such claims.
If shipping caused damage to the unit, a claim must be filed with the commercial carrier. If any other defect is apparent, call 800-323-4576 for a return authorization. Shipping Instructions To ship equipment back to Engineering Systems: 1. Contact the customer service department at 800-323-4576 before returning equipment. When calling, please have available: A description of the problem or reason for returning the equipment. Original purchase order number, invoice number and if the unit is under warranty.
THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THIS PROVISION. THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS, IMPLIED OR STATUTORY, INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE. NO REPRESENTATION OR WARRANTY OF THE DISTRIBUTOR SHALL EXTEND THE LIABILITY OR RESPONSIBILITY OF THE MANUFACTURER BEYOND THE TERMS OF THIS PROVISION.
PROGRAMMING ETHERNET DEVICES This covers all of the steps needed to get the PRO22EN Ethernet Daughter board on-line and working. Programming of these units will be outlined within this Installation Guide. PRO22EN Programming The PRO22EN will be programmed from a Command Prompt using the ARP command. ARP (Address Resolution Protocol), a TCP/IP protocol used to convert an IP address into a physical address (called a DLC address), such as an Ethernet Address.
2. Set the dipswitches on the PRO22IC (S1) to: Baud Rate is 38, 400 bps Flow Control is ON Panel Address is 1 S1 3. 8 OFF (PASSWORD OFF) 7 ON (BAUD RATE) 6 ON (BAUD RATE) 5 ON (FLOW CONTROL) 4 OFF (PANEL ADDRESS) 3 OFF (PANEL ADDRESS) 2 OFF (PANEL ADDRESS) 1 ON (PANEL ADDRESS) Set the jumpers on the PRO22IC Jumper J14 OFF (NETWORK ENABLED) J12 ON (PORT 2 EOL ACTIVE) J13 ON (PORT 3 EOL ACTIVE) J4 2 AND 3 ON J5 2 AND 3 ON J6 2 AND 3 ON J9 ON 4.
PROGRAMMING THE ETHERNET CARD 1. Go to a MS-DOS prompt. 2. Type arp -s XXX.XXX.XXX.XXX ??.??.??.??.?? XXX.XXX.XXX.XXX = TCP\IP Address for the Ethernet Card ??-??-??-??-??-?? = MAC Address of the Ethernet Card. After pressing Enter the result will show nothing. 3. Type arp -a . Verify the IP Address has been assigned to the Ethernet Card.
4. Type Telnet XXX.XXX.XXX.XXX 1 (IP Address and the number 1) Note: The 1 is port "1". 5. The Telnet window may or may not connect to Host Name: XXX.XXX.XXX.XXX. Click OK 6. Select Connect and Remote System 7. Verify the Host Name is the correct IP Address and type: 9999 in Port.
8. Press for Setup Mode 9. The following screen should appear. 10. Your Choice? Enter 0 for server configuration. 11. IP Address: (000) XXX.XXX.XXX.XXX 12. Set Gateway IP Address Type Y, if a gateway is needed. XXX.XXX.XXX.XXX (Gateway Address) Type N, if a gateway is not needed This number may or may not be needed. Check with the MIS department to verify if the Ethernet Card will need a gateway programmed. 13.
19. Port Number=3001 (Winpak Pro uses port 3001) 20. Select Enter through the rest of the menus 21. When the Main Menu Appears Verify that Channel 1 is Baudrate =38400, I/F Mode 4C, Flow 02 Port 03001 Remote IP Adr: --- none ---, Port 00000 Connect Mode: C0 Disconn Mode: 00 Flush Mode: 00 22. Type 9 to Save and Exit.
PRO22EN Mounting Diagram LANTRONIX UMSS10B CONTROLLER BOARD 1 2 3 Battery Lithium 3V LAN Card Connector J2 Configuration Dip Switches S1 8 7 6 8 5 4 3 2 1 J14 U1 1 2 3 1 2 3 Port 2 J9 J3 J12 U1 1 C Power J13 B 1 2 RS-485 Termination A Port 3 PROM 1 2 3 Memory Expansion Connector Port 1 J4 J5 J6 1 2 3 4 5