PRO-2200 Enclosure Installation Manual Part Number: PRO22ENC1 PRO22ENC2 TD1138 rev0801
PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 Installation Guide 3 Contents Warnings and Cautions ...................................................................................... 4 Disclaimer........................................................................................................... 6 Product Liability; Mutual Indemnification................................................................ 6 Unpacking Procedure ...............................................................................
4 Installation Guide PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 Warnings and Cautions WARNING Before installation, TURN OFF the external circuit breaker which supplies power to the system. Before connecting the device to the power supply, verify that the output voltage is within specifications of the power supply. Do not apply power to the system until after the installation has been completed.
PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 Installation Guide 5 CAUTION If any damage to the shipment is noticed, a claim must be filed with the responsible commercial carrier. CAUTION Electro-static discharge can damage CMOS integrated circuits and modules. To prevent damage always follow these procedures: Use static shield packaging and containers to transport all electronic components, including completed reader assemblies.
6 Installation Guide PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 Disclaimer Product Liability; Mutual Indemnification In the event that a Customer receives a claim that a Product or any component thereof has caused personal injury or damage to property of others, Customer shall immediately notify Engineered Systems in writing of all such claims.
PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 Installation Guide 7 Shipping Instructions To ship equipment back to Engineered Systems: 1. Contact the customer service department before returning equipment at 800-323-4576. Please have the following available when calling: • A description of the problem or reason for returning the equipment. • Original purchase order number, invoice number and if the unit is under warranty. • A new purchase order number if the unit is not under warranty 2.
8 Installation Guide PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 Confidentiality All software, drawings, diagrams, specifications, catalogs, literature, manuals and other materials furnished by Engineered Systems relating to the design, use and service of Products shall remain confidential and shall constitute proprietary rights of Engineered Systems, and Customer agrees to treat such information as confidential.
PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 Installation Guide 9 PRO-2200 Enclosure Description The PRO-2200 system is designed for maximum efficient use of wall space through the use of a secure metal cabinet (PRO22ENC1/PRO22ENC2) that can hold up to nine modules, a 4 amp power supply (PRO22E1PS) and a self-contained replaceable backup battery. Typically, one of the nine modules can be an intelligent controller (PRO22IC).
10 Installation Guide PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 Dimensions Height: Width: Depth: ENC1 13.9" [0.353 m] 17" [0.4318 m] 9" [0.2286 m] ENC2 13.9" [0.353 m] 18.9" [0.48006 m] 9" [0.2286 m] Metal thickness: .05" [1.27 mm] Color: Autumn White Installation holes: Four hangers in a rectangular pattern 12.1” [0.30734 m] H x 16" [0.40640 m] W Conduit Knockouts ½" [0.0127 m] Back: Top: Right Side: Left Side: 9 9 2 2 2" [0.
PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 11 Installation Guide 7. The remainder of the panels can be manually wired for power and RS-485 communications using 18 AWG wire. The wires will be daisy-chained from one panel to the next so the power and the communications are wired in parallel. PRO22DCC is available as an option to be purchased with the equipment.
12 Installation Guide PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 UL1076 Setup PC Minimum Requirements Two required: • 500 Mhz • 128Mb RAM • 9.1Gb hard drive • CD ROM • 10/100 TX network card • 17” SVGA Monitor Peripheral Hardware Requirements • UL approved network HUB with at least 4 ports. • UL approved CAT 5 network cable and connectors. • PRO22IC Controller and accompanying I/O boards. • Cobox network card (PRO22IC mounted) Operating System Requirements • NT Server 4.0 or better.
PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 Installation Guide 13 4. Watchman tour 5. Fire alarm supervision (N/A) WIN PAK PRO is not certified for fire alarm supervision 6. Burglar alarm supervision 7. Industrial supervision 8. Other supervisory services NOTE: 2 and 3 may have equal priority: 5 and 6 may have equal priority & 7 and 8 may have equal priority Other UL1075 Notes • All alarms and troubles must be acknowledged by attending guard.
14 Installation Guide PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 7. Use the Query Analyzer to connect to the WIN-PAK PRO database using the provided script for attachment. 8. Open up the ODBC application in the Control Panel and create a link to the WIN-PAK PRO SQL database. The name used for a description should match the WIN-PAK PRO System Manger DSN Tab name. Default is WIN-PAK Database. See the WINPAK PRO installation manual for complete procedure. 9. The database server can now be started.
PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 Installation Guide 15 6. Click Next. Change the Server to match the name of the LOCAL PC. The database should be selected as WIN-PAK PRO from that Server. (The destination database). 7. Click Next. Select Transfer objects and data between SQL Server 7.0 database. 8. Click Next. Uncheck the Create destination objects box. 9. Click Next. Check the Create DTS package for replication box. Also check the Save DTS Package box. Leave the radial button set for SQL Server.
16 Installation Guide PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 Redundant Test Examples NOTE: Stop watch needed for all three test examples. Example #1 1. Use the MAIN PC’s OFF button to shut it down. Turn on the REDUNDANT PC and start the stop watch. 2. Log into NT with Administrator rights. 3. Launch the User Interface and log in as ADMIN. 4. When the Alarm View pops up with Poll Response Normal, stop the stop watch. This time represents the amount of time that has passed since the MAIN PC went down.
PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 17 Installation Guide Conduit Knockouts 3/4” Top: 3 Bottom: 3 Right Side: 3 Left Side: 1 Power Supply Enclosure Switch Position: 24VDC = SW1 OPEN 12VDC = SW1 CLOSED CAUTION: De-energize unit prior to servicing. For continued protection against fire hazard replace fuse with the same type and rating 3.
18 Installation Guide PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 Installation Installation Instructions 1. Install the PRO22ULPS (Altronix AL400ULX) power supply and battery enclosure per the supplied instructions. 2. Measure and install four mounting screws with heads smaller than .4" (1cm) using proper techniques for the material on which the PRO22ENC1 or PRO22ENC2 is being mounted. Use a rectangular screw pattern 12.1" H x 16" W (0.307m H x 0.4064m W). Leave the screws exposed approximately 1/2" (1.
PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 19 Installation Guide Cable Specifications Application ESG Part No. AWG Description Max. Dist. Imp. 4000' (1200 m) 120Ω 12.
20 Installation Guide PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 ESG Cable Part Numbers Part Number Description Application Length NC1841-GY 18 AWG/4 conductor reader cable 1,000' [305 m] NC1861-BL-500 18 AWG/6 conductor reader cable 500' [152 m] NC1861-BL 18 AWG/6 conductor reader cable 1,000' [305 m] NC18121-YL-500 18 AWG/12 conductor keypad cable 500' [152 m] NC18121-YL 18 AWG/12 conductor keypad cable 1,000' [305 m] NCNET-1 50 ohm network cable 1,000' [305 m] NC2221-BR 22
PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 Installation Guide NOTES 21
22 Installation Guide NOTES PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2
PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2 Installation Guide 23
Honeywell Security & Data Collection 2700 Blankenbaker Pkwy, Suite 150 Louisville, KY 40299 (800) 675-3364 www.honeywellaccess.