Product Overview

GLOBE VALVE LINKAGES
3 38-00020—01
LINKAGE SELECTION INSTRUCTION
When selecting your linkage look at the Table 3 for the valve model list. Select the correct valve size to see the recommended
linkage and bonnet adapter. Choose the correct actuator torque based on necessary close-off pressure. If model you are looking
for is not listed fill out the Special Order Form located below.
If you do not have the exact part number or valve size, measure the valve stroke and select the corresponding linkage from Table 1.
Next, select the appropriate bonnet adapter kit from Table 5. This kit includes variety of bonnet adapters for you to choose from at
the job site.
Table 3. Linkage and Actuator Selection.
Manufacturer Valve Model Single Actuator Linkage
Honeywell V5011
V5013
Valve
Connection
Size
(inch)
Linkage and
Bonnet Adapter
Actuator Torque (lb-in)
44 88 175 300
Close-Off (psi)
0.5 Q5024A1123
and
HU5024-001
230 230
0.75 130 230
1 80 140 230
1.25 50 90 200
1.5 65 140
2 35 80 140
2.5 55 90
3 35 65
Dual Actuator Linkage
Valve
Connection
Size
(inch)
Linkage and
Bonnet Adapter
Actuator Torque (lb-in)
350 (2 x 175) 600 (2 x 300)
Close-Off (psi)
2 Q5024B2230
and
HU5024-001
118
2.5 75 123
3 50 80
4 Q5024B2240
and
HU5024-002
18 38
5 12 21
6 10 16
VGF Single Actuator Linkage
Valve
Connection
Size
(inch)
Linkage and
Bonnet Adapter
Actuator Torque (lb-in)
44 88 175 300
Close-Off (psi)
2.5 Q5024A1123
and
HU5024-001
52 88
3
26 42
Dual Actuator Linkage
Valve
Connection
Size
(inch)
Linkage and
Bonnet Adapter
Actuator Torque (lb-in)
350 (2 x 175) 600 (2 x 300)
Close-Off (psi)
2.5 Q5024B2240
and
HU5024-002
110 190
3 55 94
4 27 47
5 11 18
6 11 18