Product Overview

Legacy Building Systems
334 customer.honeywell.com 70-6910
Q667 Switching Subbase
Provide manual switching for T7067 Thermostat/Transmitters.
Mount directly on wall or on vertical 2 x 4 in. outlet box
T7067 mounts on subbase with mounting screws which also complete
electrical connections between thermostat/transmitter and subbase
When fan switch is set to AUTO, the fan is intermittent in HEAT and
continuous in system AUTO or COOL
Dimensions, Approximate: 4 3/4 in. high x 3 15/16 in. wide x 15/16 in.
deep (121 mm high x 100 mm wide x 24 mm deep)
Power Consumption: 1A at 24 Vac Full Load
Description:
Switching Subbase used with T7067
T7067 Thermostat and Transmitter
T7067A Thermostat and T7067B Transmitter control space
temperature when used with W973 Logic Panel.
Separate heat and cool adjustable set point levers provide
adjustable deadband from 3 F to 30 F (2 C to 17 C)
Separate 1-16 Vdc voltage ramps provide independent heating
and cooling signals to W973 Single Zone Logic Panel
Two light-emitting diodes (LEDs) under T7067 cover for system checkout
C7046A Discharge Air Sensor provides temperature anticipation
One T7067 can control up to 6 W973 panels in parallel
Mount on standard 2 x 4 in. vertical outlet box or
on a non-conductive flat surface
All models include wiring plate and locking cover
Application Size:
Depends on Logic Panel (W973)
Dimensions, Approximate: 4 5/8 in. high x 2 13/16 in. wide x 1 1/4 in. deep
(118 mm high x 71 mm wide x 32 mm deep)
Output Type:
Voltage Ramp
Voltage: 20 Vdc from W973 panel
Setpoint Temperature Range: 55 F to 85 F (13 C to 29 C)
Shipping Temperature Range: -40 F to +150 F (-40 C to +65 C)
Approvals
ASHRAE Guidelines:
Meets ASHRAE 90-75
Department of Defense Guidelines: Meets
Accessories:
S963D1001-2 Potentiometers that simulate the ramp signals
of a T7067 Thermostat
Product Number Application
Switch Positions
Comments Used WithSystem Fan
Q667A1005/U Heat Pump Systems,
Split Systems
HEAT-OFF-COOL-
AUTO
AUTO/ON Number of stages of heating and cooling
depends on the chosen Logic Panel
T7067
Q667B1004/U Heat Pump Systems,
Split Systems
HEAT-OFF-COOL-
AUTO
AUTO/ON Number of stages of heating and cooling
depends on the chosen Logic Panel
T7067
Q667B1020/U Heat Pump Systems,
Split Systems
HEAT-OFF-COOL-
AUTO
AUTO/ON Provides intermittent fan operation
in cooling when used with W974B
T7067
Q667C1003/U Single Stage Subbase COOL/AUTO/HEAT/
EM.HT.
AUTO/OFF; OFF
position shuts off
entire system
T7067
Product Number
Control
System Compatible with Description Comments
T7067A1008/U W973 single
zone
Q667 subbase,
W973 Logic Panel
Solid State Thermostat designed to be used with
the W973 logic panel to control the operation of
single zone packaged air conditioning equipment
Integral temperature sensor without thermometer;
Number of stages of heating and cooling depends
on the chosen Logic Panel
T7067B1006/U W973 single
zone
Q667 subbase,
W973 Logic Panel
Transmitter designed for use with a T7047C1025
or T7022A1010 remote temperature sensor
Must order T7047C,G remote temperature sensor or
T7022A remote duct temperature sensor separately

Summary of content (1 pages)