Q769B 4 to 20 mA Adapter for M7405
and M7415 Actuators
APPLICATION
The Q769B 4 to 20 mA Adapter is used to provide a 4 to
20 mA modulating signal to the M7405 and M7415
Actuators when used with a 4 to 20 mA Controller. The
Q769B can also be used instead of a Q709A to control
the minimum position of an M7405 or M7415 Actuator
when a C7150B is used as a temperature sensor. See
note on page 2 for use with proportional signal.
Maximum power consumption of the Q769B is 15 mW at
25 mA. The housing has an Underwriters Laboratories
Inc. flame rating of 94 V-O. Two female quick connect
terminals on the adapter connect to actuator terminals P
and P1. Two male quick connect terminals are available
for field wiring of an additional actuator. The adapter is
designed to operate in a temperature range from -40°F
to +125°F (-40°C to +52°C) and a relative humidity range
of 5 to 95 percent.
INSTALLATION
When Installing this Product...
1 Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.
2 Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3 Installer must be a trained, experienced service
technician.
4 After Installation is complete, check out product
operation as provided in these instructions.
CAUTION
Disconnect power supply before making wiring
connections to prevent electrical shock and
equipment damage.
All wiring must comply with applicable electrical codes,
ordinances and regulations.
NOTE: When using the Q769B on the M7405 or M7415
Actuators, the W7459 Solid State Economizer
Module cannot be used. TO use the W7459
Solid State Economizer Module and the Q769B
Adapter on the same M7405/M7415 Actuator,
attach the W7459 Economizer Module to the
M7405/M7415 Actuator, then connect separate
wires from the Q769B terminals to actuator
terminals P and P1.
The Q769B Adapter is supplied with female quick connect
terminals that fit over the actuator 1/4 in. (6 mm) make
quick connect terminals P and P1. Plug the Q769B
Adapter into these one way terminals. See Fig. 1. See
Fig. 2 and 3 for wiring information.
M
IN
P
O
S
N
P1
P
4mA to 20 mA
CALIBRATION
POTENTIOMETER
PUSH Q769
ONTO ACTUATOR
M3389
Fig. 1. Mounting Q769B 4 to 20 mA Adapter on
actuator.
Fig. 2. Q769B Adapter connected to actuator for 4 to
20 mA control of actuator minimum position
(M7415 Actuator shown).
63-2455-1
L1
(HOT)
L2
1
1
2
2
MINIMUM
POSITION
SENSOR
24 Vac
24 Vac
TR
TR1
T
T1
P1
P
SENSOR
4-20 mA
SIGNAL
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
Q769B ADAPTER MOUNTED ON P1, P QUICK CONNECTS.
M7415
M2021A
TRANSFORMER
Q769B