R8184G Protectorelay® Oil Burner Control
Provides automatic, nonrecycling control of an intermittent
ignition oil burner system.
• Controls oil burner, oil valve (if desired) and the ignition transformer
in response to a call for heat.
• Solid state flame sensing circuit.
• LED on terminal strip indicates system lockout.
• Remote lockout indication available on some models.
• Enclosed safety switch with external reset button.
• Manual trip lever opens safety switch for system maintenance.
• Mounts on standard 4 x 4 in. junction box; select models may be
mounted directly on burner housing.
• C554A Cadmium Sulfide Flame Detector and 24 Vac thermostat
required.
Dimensions, Approximate: 4 3/8 in. high x 4 1/8 in. wide x 2 1/2 in.
deep (111 mm high x 104 mm wide x 64 mm deep)
Ignition Type: Intermittent
Temperature Range: -40 F to +130 F (-40 C to +54 C)
Mounting Bracket: For mounting on a standard 4 in. X 4 in. junction
box or direct mounting on burner housing.
Electrical Rating, Contacts
Full Load: 7.4 A @ 120 Vac; 3.7 a @ 240 Vac
Locked Rotor: 44.4 A @ 120 Vac; 22.2 A @ 240 Vac
Alarm Load Ratings:
Pilot Duty: 75 VA @ 120/240 Vac, 50-60 Hz; 25 VA @ 24V, 50-60 Hz
Resistive: 1.5 A @ 120/240V, 50-60Hz; 3 A @ 24 V, 50-60 Hz
Approvals:
Canadian Standards Association: CSA Certified; File no. LR95329-1
Underwriters Laboratories, Inc. UL Component Recognized; File no.
MP268, Vol. 35 Sec. 1,3
R8184M Protectorelay® Oil Burner Control
Operates the oil burner and oil valve (if desired) in response to a
call for heat from a low voltage control circuit.
• Ignition is on whenever the burner is on (intermittent ignition-also
called constant ignition).
• Solid state flame sensing circuit.
• External button to manually reset safety switch after lockout.
• Enclosed safety switch must be manually reset after safety
shutdown.
• R8184M includes 40 VA transformer and Y and G terminals for
connection of cooling equipment.
• Mounts on standard 4 x 4 in. junction box.
• C554A Cadmium Sulfide Flame Detector and a 24 Vac thermostat
required.
Dimensions, Approximate: 4 3/8 in. high x 4 1/8 in. wide x 2 1/2 in.
deep (111 mm high x 104 mm wide x 64 mm deep)
Ignition Type: Intermittent
Temperature Range: -40 F to +130 F (-40 C to +54 C)
Electrical Rating, Contacts:
Full Load:
7.4 A @ 120 Vac; 3.7 a @ 240 Vac;
Locked Rotor: 44.4 A @ 120 Vac; 22.2 A @ 240 Vac
Approvals:
Underwriters Laboratories, Inc. UL Component Recognized; File no.
MP268, guide no. MCCZ2
Product Number
Timing, Safety
Switch Comments Includes
* R8184G4009 45 sec. With LED for lockout indication, and manual trip lever on safety switch to assure burner
shutdown during servicing.
—
* R8184G4025 45 sec. With LED for lockout indication, and manual trip lever on safety switch to assure burner
shutdown during servicing.
Remote Alarm Power
* R8184G4066 15 sec. With LED for lockout indication, and manual trip lever on safety switch to assure burner
shutdown during servicing.
—
* R8184G4074 30 sec. With LED for lockout indication, and manual trip lever on safety switch to assure burner
shutdown during servicing.
—
* R8184G4082 45 sec. With LED for lockout indication, and manual trip lever on safety switch to assure burner
shutdown during servicing. Includes remote alarm dry contacts.
Alarm
* TRADELINE models • SUPER TRADELINE models
Product Number
Timing, Safety
Switch Mounting Bracket Description
* R8184M1051 45 sec. Mounts on standard 4 x 4 in. junction box Protectorelay® Oil Burner Control with 45 seconds lock out timing
* TRADELINE models • SUPER TRADELINE models