Specifications

Oil Primaries
70-6910 181
Home
Controls Indoor Air Quality
Residential
Combustion Controls Hydronic Controls
Water
Controls Building Automation
Commercial
Components Pneumatic Controls
Industrial Combustion
Controls
R8184G Protectorelay® Oil Burner Control
Provides automatic, nonrecycling control of an intermittent
ignition oil burner system.
Controls oil burner, oil valve (if desired) and the ignition transformer
in response to a call for heat.
Solid state flame sensing circuit.
LED on terminal strip indicates system lockout.
Remote lockout indication available on some models.
Enclosed safety switch with external reset button.
Manual trip lever opens safety switch for system maintenance.
Mounts on standard 4 x 4 in. junction box; select models may be
mounted directly on burner housing.
C554A Cadmium Sulfide Flame Detector and 24 Vac thermostat
required.
Dimensions, Approximate: 4 3/8 in. high x 4 1/8 in. wide x 2 1/2 in.
deep (111 mm high x 104 mm wide x 64 mm deep)
Ignition Type: Intermittent
Temperature Range: -40 F to +130 F (-40 C to +54 C)
Mounting Bracket: For mounting on a standard 4 in. X 4 in. junction
box or direct mounting on burner housing.
Electrical Rating, Contacts
Full Load: 7.4 A @ 120 Vac; 3.7 a @ 240 Vac
Locked Rotor: 44.4 A @ 120 Vac; 22.2 A @ 240 Vac
Alarm Load Ratings:
Pilot Duty: 75 VA @ 120/240 Vac, 50-60 Hz; 25 VA @ 24V, 50-60 Hz
Resistive: 1.5 A @ 120/240V, 50-60Hz; 3 A @ 24 V, 50-60 Hz
Approvals:
Canadian Standards Association: CSA Certified; File no. LR95329-1
Underwriters Laboratories, Inc. UL Component Recognized; File no.
MP268, Vol. 35 Sec. 1,3
R8184M Protectorelay® Oil Burner Control
Operates the oil burner and oil valve (if desired) in response to a
call for heat from a low voltage control circuit.
Ignition is on whenever the burner is on (intermittent ignition-also
called constant ignition).
Solid state flame sensing circuit.
External button to manually reset safety switch after lockout.
Enclosed safety switch must be manually reset after safety
shutdown.
R8184M includes 40 VA transformer and Y and G terminals for
connection of cooling equipment.
Mounts on standard 4 x 4 in. junction box.
C554A Cadmium Sulfide Flame Detector and a 24 Vac thermostat
required.
Dimensions, Approximate: 4 3/8 in. high x 4 1/8 in. wide x 2 1/2 in.
deep (111 mm high x 104 mm wide x 64 mm deep)
Ignition Type: Intermittent
Temperature Range: -40 F to +130 F (-40 C to +54 C)
Electrical Rating, Contacts:
Full Load:
7.4 A @ 120 Vac; 3.7 a @ 240 Vac;
Locked Rotor: 44.4 A @ 120 Vac; 22.2 A @ 240 Vac
Approvals:
Underwriters Laboratories, Inc. UL Component Recognized; File no.
MP268, guide no. MCCZ2
Product Number
Timing, Safety
Switch Comments Includes
* R8184G4009 45 sec. With LED for lockout indication, and manual trip lever on safety switch to assure burner
shutdown during servicing.
* R8184G4025 45 sec. With LED for lockout indication, and manual trip lever on safety switch to assure burner
shutdown during servicing.
Remote Alarm Power
* R8184G4066 15 sec. With LED for lockout indication, and manual trip lever on safety switch to assure burner
shutdown during servicing.
* R8184G4074 30 sec. With LED for lockout indication, and manual trip lever on safety switch to assure burner
shutdown during servicing.
* R8184G4082 45 sec. With LED for lockout indication, and manual trip lever on safety switch to assure burner
shutdown during servicing. Includes remote alarm dry contacts.
Alarm
* TRADELINE models • SUPER TRADELINE models
Product Number
Timing, Safety
Switch Mounting Bracket Description
* R8184M1051 45 sec. Mounts on standard 4 x 4 in. junction box Protectorelay® Oil Burner Control with 45 seconds lock out timing
* TRADELINE models • SUPER TRADELINE models