Install Instructions

65-0100—2 60
Printed in U.S.A.
12
Q7800
13
14
15
16
18
17
19
20
21
22
G
L2
9
8
7
6
5
4
3
10
F
S2
2
A
8
6
5
M7448
A
S1
GENERAL FOOTNOTES, SEE PAGE 5.
A
1234
5 7818
19
A
A
B
B
7800 SERIES CONVERSION WIRING DIAGRAM
FROM________________________________ TO ______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)
1,D
ECLIPSE 5602
RM7800L1012 OR RM7840L1018
A
B
5602 HAS PROOF OF CLOSURE AND HIGH 
PURGE DAMPER SWITCH LOCATED BETWEEN 
6 AND D. LOCATE PROOF OF CLOSURE SWITCH
AND CONNECT BETWEEN Q7800 TERMINALS
4 AND 20. LOCATE HIGH PURGE DAMPER 
SWITCH AND CONNECT BETWEEN Q7800
TERMINALS 4 AND 19.
5602 HAS LOW FIRE PROVING IN SERIES WITH 
THE PILOT VALVE. LOCATE PILOT VALVE
CONNECTION AND CONNECT TO Q7800 
TERMINAL 8. LOCATE WIRE TO LOW FIRE
PROVING SWITCH AND CONNECT SWITCH 
BETWEEN Q7800 TERMINALS 5 AND 18. 5602
HAD PURGE TIME, INTERMITTENT/INTERRUPTED
PILOT, AND RECYCLE/NONRECYCLE SELECTIONS
MADE BY A DIP SWITCH LOCATED ON THE 
REAR PLATE OF THE CONTROL UNIT. THE
REPLACEMENT RM7800L/RM7840L IS A 
LOCKOUT DEVICE WITH INTERRUPTED PILOT.
SELECT ST7800 TO MATCH 5602 TIMING.
11
12
10
13
MAIN VALVE
10
IGNITION
TRANSFORMER
FOR DIRECT SPARK IGNITION 
(OIL OR GAS)
8
9
L2
7
3
4
Lockout Modulation