Install Instructions
65-0100—2 60
Printed in U.S.A.
12
Q7800
13
14
15
16
18
17
19
20
21
22
G
L2
9
8
7
6
5
4
3
10
F
S2
2
A
8
6
5
M7448
A
S1
GENERAL FOOTNOTES, SEE PAGE 5.
A
1234
5 7818
19
A
A
B
B
7800 SERIES CONVERSION WIRING DIAGRAM
FROM________________________________ TO ______________________
(DEVICE TO BE MODERNIZED) (O.S. NUMBER OF RELAY MODULE TO BE USED)
1,D
ECLIPSE 5602
RM7800L1012 OR RM7840L1018
A
B
5602 HAS PROOF OF CLOSURE AND HIGH
PURGE DAMPER SWITCH LOCATED BETWEEN
6 AND D. LOCATE PROOF OF CLOSURE SWITCH
AND CONNECT BETWEEN Q7800 TERMINALS
4 AND 20. LOCATE HIGH PURGE DAMPER
SWITCH AND CONNECT BETWEEN Q7800
TERMINALS 4 AND 19.
5602 HAS LOW FIRE PROVING IN SERIES WITH
THE PILOT VALVE. LOCATE PILOT VALVE
CONNECTION AND CONNECT TO Q7800
TERMINAL 8. LOCATE WIRE TO LOW FIRE
PROVING SWITCH AND CONNECT SWITCH
BETWEEN Q7800 TERMINALS 5 AND 18. 5602
HAD PURGE TIME, INTERMITTENT/INTERRUPTED
PILOT, AND RECYCLE/NONRECYCLE SELECTIONS
MADE BY A DIP SWITCH LOCATED ON THE
REAR PLATE OF THE CONTROL UNIT. THE
REPLACEMENT RM7800L/RM7840L IS A
LOCKOUT DEVICE WITH INTERRUPTED PILOT.
SELECT ST7800 TO MATCH 5602 TIMING.
11
12
10
13
MAIN VALVE
10
IGNITION
TRANSFORMER
FOR DIRECT SPARK IGNITION
(OIL OR GAS)
8
9
L2
7
3
4
Lockout Modulation