Product Overview

RM7890; RM7895 100 VAC 7800 SERIES RELAY MODULES
66-1195—01 2
Expanded safe-start check.
Internal hardware status monitoring.
Tamper resistant timing and logic.
Access for external electrical voltage checks.
Application flexibility.
Dependable, long-term operation provided by
microcomputer technology.
Five light emitting diodes (LEDs) for sequence
information.
Interchangeable type plug-in flame amplifiers.
Nonvolatile memory retains history files and
sequencing status after loss of power.
Selectable relight or lockout on loss of flame.
OPTIONAL FEATURES
Communication interface capability.
First-out annunciation and system diagnosis are
provided by a two-row by 20-column display located on
the optional keyboard display module (KDM).
Local or remote annunciation operation and fault
information.
Remote reset.
Burner controller data using S7800 Keyboard Display:
Flame signal strength.
Hold status.
Lockout/alarm status.
Sequence status.
Sequence time.
Total cycles of operation.
Total hours of operation.
Fault history providing the six most recent faults:
Cycles of operation at the time of the fault.
Fault message and code.
Hours of operation at the time of the fault.
Sequence status at the time of the fault.
Sequence time at the time of the fault.
Diagnostic information:
•Device type.
Flame amplifier type.
Flame failure response time.
Manufacturing code.
On/Off status of all digital inputs and outputs.
Software revision and version of RM7890/
RM7895 and optional Keyboard Display Module.
Status of configuration jumpers.
SPECIFICATIONS
Electrical Ratings:
See Table 1.
Voltage and Frequency:
100 Vac (+10/-15%), 50/60 Hz (± 10%).
Power Dissipation: 10W maximum.
Maximum Total Connected Load: 2000 VA.
Fusing Total Connected Load: 15A maximum, type SC or
equivalent.