Product Overview

RM7890; RM7895 100 VAC 7800 SERIES RELAY MODULES
27 66-1195—01
PILOT IGN The LED indicates the burner status, POWER, PILOT, and FLAME, which is the period of time the
relay module permits the pilot valve and ignition to be energized and the pilot flame to be
established.
MAIN IGN
(RM7895 Only)
The LED indicates the burner status, POWER, PILOT, FLAME, and MAIN, which is the period of
time the RM7895 permits the main valve to be open and the main flame to be tested.
RUN The LED indicates the burner status, POWER, PILOT, FLAME and MAIN, which is the period of time
after the Ignition Trials and before the operating controller setpoint is reached. During this time, the
burner is firing under the control of the operating controller.
RESET/ALARM TEST The LED indicates the burner status, POWER and ALARM. This condition indicates that the reset
pushbutton is pressed. If it is held for more than four seconds, the alarm output is energized. The
alarm output will be de-energized after the reset pushbutton is released.
Table 13. Sequence and Status Hold Information. (Continued)
Sequence Information