Install Instructions

RM7898A 7800 SERIES VALVE PROVING PRIMARY RELAY MODULES
66-1161—04 14
Fig. 19. Confirm Correct screen.
19. Use the down arrow to confirm correct.
Getting Data” will be displayed.
The following steps are used to confirm your selection.
Fig. 20. Confirm Postpurge time.
20. Press Enter.
Fig. 21. Confirm correct/incorrect screen.
21. Press Enter.
22. Press the down arrow to confirm the correct postpurge
time. “Getting Data” will be displayed until the screen in
Fig. 20 appears.
Fig. 22. Setup Done screen.
23. Press and hold the relay module’s RESET button for
five seconds to program the Valve Proving setup into
the relay module.
The Release Reset screen will appear on the KDM.
Fig. 23. Release Reset screen.
Future changes to the Valve Proving and PostPurge features
are still possible. With the relay module in Standby, scroll to
the Setup line and enter the password to change the settings.
Once the system is in operation, the settings of the Valve
Proving and Postpurge can be viewed in Diagnostics, using
your S7800 Keyboard Module (KDM).
Select Mounting RM7898 Relay
Module
1. Mount the RM7898 vertically on the Q7800 Subbase, or
mount horizontally with the knife blade terminals
pointing down. (For mounting on the Q7800A, mount
the RM7898 in an electrical enclosure.)
2. When mounting in an electrical enclosure, provide
adequate clearance for service, installation and removal
of the RM7898, KDM, flame amplifier, flame amplifier
signal voltage probes, electrical signal voltage probes,
and electrical connections.
a. Allow an additional 2 in. (51 mm) below the RM7898
for the flame amplifier mounting.
b. Allow an optional 3 in. (76 mm) minimum to both
sides of the RM7898 for electrical signal voltage
probes.
3. Make sure no subbase wiring is projecting beyond the
terminal blocks. Tuck in wiring against the back of the
subbase so it does not interfere with the knife blade
terminals or bifurcated contacts.
IMPORTANT
Install the RM7898 with a plug-in motion rather than
a hinge action.
4. Mount the RM7898 by aligning the four L-shaped corner
guides and knife blade terminals with the bifurcated
contacts on the wiring subbase and securely tightening
the two screws without deforming the plastic.
Mounting Other System Components
(Fig. 24)
Mount other required and optional system components by
referring to Fig. 24 and the instructions provided with each
component.
=Confirm correct
=Incorrect
M22671B
BACK
ENTER
Edit:
-+
M22674A
BACK
ENTER
Edit:
-+
CONFIRM: Postpurge
±PostTime: 00:30 ?
SC
=Confirm correct
=Incorrect
M22671B
BACK
ENTER
Edit:
-+
SETUP DONE: Press
Reset for 5 sec . . .
M22676B
BACK
ENTER
Edit:
-+
SETUP DONE:
... release Reset
M22765B
BACK
ENTER
Edit:
-+